ETC DUB02CT23

Monitoring Relays
1-Phase True RMS AC Over/Under Voltage
Types DUB02, PUB02
DUB02
• TRMS AC over/under voltage monitoring
relays
• Measuring if power supply is within set limits
• Measure on own power supply
• Measuring ranges: 24, 115, 230 VAC
• Power ON delay 1 or 6 s selectable by DIP-switch
• Separately adjustable upper/lower level on relative scale
• Adjustable delay on alarm or on recovery (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DUB02) or plug-in module (PUB02)
• 22.5 mm Euronorm housing (DUB02)
or 36 mm plug-in module (PUB02)
• LED indication for relay, alarm and power supply ON
PUB02
Product Description
Ordering Key
even after the end of the
alarm condition. Inhibit function can be used to avoid
relay operation when not
desired (maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay.
Housing
Function
Type
Item number
Output
Power supply
Mounting
Output
Supply: 24, 115, 230 VAC
DIN-rail
Plug-in
SPDT
SPDT
DUB 02 C T23
PUB 02 C T23
DUB02 and PUB02 are precise TRMS AC window voltage monitoring relays.
The relays monitor their own
power supply which is selectable by DIP-switch (24, 115 or
230 VAC).
The advantage of using the
latch function is that the
relay can be kept energized
DUB 02 C T23
Type Selection
Input Specifications
Output Specifications
Input
Own power supply
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
DUB02:
PUB02:
Measuring ranges
Selectable by DIP-switch
24 VAC
115 VAC
230 VAC
Contact input
DUB02
PUB02
Disabled
Enabled
Pulse width
Hysteresis
A1, A2 (24, 115, 230 VAC)
2, 10 (24, 115, 230 VAC)
Upper level
-5% to +20%
22.8 to 28.8 V
109 to 138 V
218 to 275 V
Lower level
-20% to +5%
19.2 to 25.2 V
92 to 121 V
184 to 242 V
Terminals Z1, Z2
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
~ 2% of set value - fixed
Specifications are subject to change without notice (21.10.00)
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
1
DUB02, PUB02
Supply Specifications
General Specifications (cont.)
Power supply
Rated operational voltage
through terminals:
A1 and A2 (DUB02) or
2 and 10 (PUB02)
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
Dielectric voltage
Dielectric voltage
Supply to output
Rated operational power
Overvoltage cat. III
(IEC 60664, IEC 60038)
24 VAC ± 20%,
115 VAC ± 20% or
230 VAC ± 20%
None
4 kV
4 VA
General Specifications
Power ON delay
Reaction time
Alarm ON delay
Alarm OFF delay
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 200 ms
< 200 ms
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
IP 20
3 (DUB02), 2 (PUB02)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 150 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
DUB02 and PUB02 monitor
the TRMS value of their own
power supply.
Example 1
(no connection between terminals Z1, Z2 or 8, 9 - Delay
ON alarm - N.E. relay)
The relay operates and the
yellow LED is ON as long as
the measured value is within
the upper and lower limits.
The relay releases after the
adjustable time delay when
the measured voltage exceeds
the upper set level or drops
below the lower set level.
The red LED flashes until the
delay time has expired or the
measured value falls off the
limits.
Example 2
(connection between terminals Z1, Z2 or 8, 9 - latching
function enabled - delay on
recovery - N.E. relay)
The relay operates and the
yellow LED is ON as long as
the measured value is within
the upper and lower limits.
The relay releases and latches in alarm position as soon
as the measured voltage
exceeds the upper set level
or drops below the lower set
level. Provided that the voltage has dropped below the
upper set level (minus hysteresis) or exceeded the lower set level (plus hysteresis)
for more than the set delay
time, the relay operates
when the interconnections
between terminals Z1, Z2 or
8, 9 are interrupted. The red
LED flashes until the delay
time has expired or the measured value falls off the limits.
Function/Range/Level and Time Delay Setting
Selection of function:
DIP-switch selector (1 to 4)
3
Power ON delay 6 ± 0.5 s
Power ON delay 1 ± 0.5 s
1
ON
Delay ON recovery
Delay ON alarm
2
Relay de-energized in
normal condition.
Relay energized in normal
condition.
2
4
Contact input as latch function enable. When the contact
is closed, the latch function is
activated. Reset of the latch
condition occurs when the contact is open or by power down.
Contact input as inhibit of
alarm enable. When the contact is closed the relay remains
in normal position even if the
alarm condition occurs.
Selection of ranges:
DIP-switch selector (5 to 6)
Selection of level and time
delay:
56
Upper knob:
Setting of upper level on relative scale: -5% to +20% of
set power supply voltage.
24 VAC ± 20%,
45 to 65 Hz
115 VAC ± 20%
45 to 65 Hz
230 VAC
45 to 65 Hz
Centre knob:
Setting of lower level on relative scale: -20% to +5% of
set power supply voltage.
Lower knob:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
Specifications are subject to change without notice (21.10.00)
DUB02, PUB02
Wiring Diagrams
Example 1
Example 1
L
L
µ
Z1
Z2
A1
16
µ
18
9
U
2
8
4
3
U
A2
15
10
N
1
N
Example 2
Example 2
Latch/inhibit
enable
L
L
Latch/inhibit
enable
µ
Z1
Z2
A1
16
µ
18
9
U
8
2
4
3
U
A2
15
10
N
1
N
PUB02
DUB02
Operation Diagrams
Delay ON alarm
Delay ON alarm - Latch function
Power supply
Power supply
Upper set level
Latch ON
Hysteresis
Upper set level
Hysteresis
Lower set level
Hysteresis
Lower set level
Hysteresis
1 or 6 s
Relay ON
1 or 6 s
Relay ON
Red LED ON
1 or 6 s
Red LED ON
Delay ON recovery
Delay ON recovery - Inhibit function
Power supply
Power supply
Upper set level
Inhibit ON
Hysteresis
Upper set level
Hysteresis
Lower set level
Hysteresis
1 or 6 s
Lower set level
Hysteresis
Relay ON
1 or 6 s
Red LED ON
Relay ON
Red LED ON
Specifications are subject to change without notice (21.10.00)
3