Digital Temperature Controllers E5CN/E5CN-U This Best-selling General-purpose 48´48-mm Temperature Controller Is Now Even Better. Easy, Dependable, Complete Functionality, and 11-segment Displays. • Controllers now available with analog inputs. • Faster sampling at 250 ms. • Transfer output provided for easy output to recorders. • Voltage outputs (to drive SSRs) for both heating and cooling control. Can be used for alarms to provide three alarm outputs. • Models available with three-phase heater burnout detection and SSR fault detection. • Easy setting with 11-segment displays. • Connect to either a thermocouple or platinum resistance thermometer with the same model. • Easily see the status from a distance with PV display with threecolor switching function. • Setting protection indicator informs operator when protection is enabled. • Manual output provided. • Controller available with long-life relay output (available soon). Note: Refer to page 19 for information on changes in comparison to previous models. Note: Refer to Precautions on page 21. Features Improved Functions for a Wider Range of Application Control Analog Values, such as Pressures, Flowrates, and Levels The new E5CN Series now also includes models that accept analog inputs, enabling control applications other than for temperature, including pressure, flowrate, level, humidity, and weight control. Note: E5CN-@L (Models with Analog Inputs) Voltage Outputs (to Drive SSRs) for Both Heating and Cooling Control. Can Be Used for Alarms to Provide Three Alarm Outputs. Voltage outputs can be used for both heating and cooling for Models with Two Control Outputs. Also, control output 2 can be set for use as an alarm output, to enable using up to three alarm outputs. Note: E5CN-@Q (Option Board) Faster Sampling at 250 ms The previous sampling time of 500 ms has been reduced by half to 250 ms. This enables the new E5CN to handle application requiring even greater response speed and accuracy. Three-phase Heater Burnout Detection A transfer output now makes it easy to connect to a recorder or PLC Analog I/O Unit. With Models with Three-phase Heater Burnout and SSR Failure Detection, two current transformers can be connected to detect both heater burnout and SSR failure at the same time, reducing costs because a separate heater burnout alarm device is not required. SSR failure detection can be used even with Models with Singlephase Heater Burnout Alarms. Note: E5CN-C@ (Models with Current Outputs) Note: E5CN-@HH@ (Option Board) Easy Connector to a Recorder Easy, Dependable, and Even Faster Easy Setting with 11-segment Displays The new E5CN features 11-segment displays to make text easier to read, eliminating the need to decode displays when trying to set parameters, as was necessary with previous temperature controllers. Multi-input Capability with One Controller Connect to either a thermocouple or platinum resistance thermometer with the same model. Model selection is simplified, stocks are reduced, and fewer maintenance parts are required. Easily See Status from a Distance with PV Display with Three-color Switching Function Setting Protection Indicator Informs Operator when Protection Is Enabled A special icon on the display panel lights to let the operator know when setting protection has been set. Digital Temperature Controllers E5CN/E5CN-U 1 Model Number Structure ■ Model Number Legend E5CN-@@M@-500 1 2 3 4 1. Output type R: Relay Q: Voltage (for driving SSR) C: Current Y: Long-life relay output (available soon) 2. Number of alarms Blank: No alarm 2: Two alarms 3. Option Unit M: Option Unit can be mounted 4. Input type T: Thermocouple/platinum resistance thermometer (multi-input) L: Analog input This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5CN-U Temperature Controller User's Manual (Cat. No. H129) E5CN Temperature Controller Communications User's Manual (Cat. No. H130) 2 Digital Temperature Controllers E5CN/E5CN-U Ordering Information ■ Controllers with Temperature Inputs (Multi-input) Size Power supply voltage Number of alarm points 100 to 240 VAC 1/16 DIN 48 ´ 48 ´ 78 (W ´ H ´ D) 0 Control outputs Relay Model E5CN-RMT-500 Voltage (for driving SSR) E5CN-QMT-500 2 Current E5CN-CMT-500 Relay E5CN-R2MT-500 Voltage (for driving SSR) E5CN-Q2MT-500 24 VAC/DC 0 Current E5CN-C2MT-500 Long-life relay E5CN-Y2MT-500 Relay E5CN-RMT-500 Voltage (for driving SSR) E5CN-QMT-500 2 Current E5CN-CMT-500 Relay E5CN-R2MT-500 Voltage (for driving SSR) E5CN-Q2MT-500 Current E5CN-C2MT-500 Long-life relay E5CN-Y2MT-500 ■ Controllers with Analog Inputs Size Power supply voltage Number of alarm points 1/16 DIN 100 to 240 VAC 48 ´ 48 ´ 78 (W ´ H ´ D) 0 Control outputs Relay Model E5CN-RML-500 Voltage (for driving SSR) E5CN-QML-500 2 Current E5CN-CML-500 Relay E5CN-R2ML-500 Voltage (for driving SSR) E5CN-Q2ML-500 24 VAC/DC 2 Current E5CN-C2ML-500 Long-life relay E5CN-Y2ML-500 Relay E5CN-R2ML-500 Voltage (for driving SSR) E5CN-Q2ML-500 Current E5CN-C2ML-500 ■ Option Units The E5CN provides optional functionality when one of the following Option Units is mounted. Functions Communications Model Heater burnout/SSR failure detection E53-CNH03N Communications E53-CN03N Heater burnout/SSR failure detection Communications Event inputs E53-CNHBN Event inputs E53-CNBN 3-phase heater burnout/SSR failure detection E53-CNHH03N Communications Control output 2 (voltage output) E53-CNQ03N Heater burnout/SSR failure detection Control output 2 (voltage output) E53-CNQHN Note: Option Units cannot be used for Plug-in models. These Option Units can be used for the new E5CN models only. E53-CNH03N Communications/ CT B E53-CNHBN Event inputs/ CT 11 11 RS-485 A E53-CN03N Communications B E53-CNBN Event inputs 11 11 RS-485 12 Do not use. 13 EV1 EV2 14 CT1 12 13 14 CT1 15 15 A E53-CNHH03N Communications/ Two CTs B 11 RS-485 12 Do not 13 use. Do not 14 use. Do not 15 use. EV1 EV2 12 A B 11 RS-485 12 A 12 Do not use. 13 13 13 Do not 14 use. Do not 15 use. E53-CNQ03N Communications/ Control output 2 E53-CNQHN Control output 2/ CT + 11 Voltage output − 12 21 mA Control output 2 12 VDC, Do not use. 13 CT2 14 CT1 15 + Control output 2 − 14 14 CT1 15 15 Attach the appropriate terminal labels. Digital Temperature Controllers E5CN/E5CN-U 3 Model Number Structure ■ Model Number Legend (Plug-in-type Controllers) E5CN-@@@U 1 2 3 4 1. Output type R: Relay Q: Voltage 2. Number of alarms Blank: No alarm 1: One alarm 2: Two alarms 3. Input type T: Thermocouple/platinum resistance thermometer (multi-input) 4. Plug-in type U: Plug-in type Ordering Information (Plug-in-type Controllers) ■ Controllers with Temperature Inputs (Multi-input) Size Power supply voltage 1/16 DIN 100 to 240 VAC 48 ´ 48 ´ 78 (W ´ H ´ D) Number of alarm points Control outputs 0 Relay 1 Relay Model E5CN-RTU Voltage (for driving SSR) E5CN-QTU E5CN-R1TU Voltage (for driving SSR) E5CN-Q1TU 2 Relay E5CN-R2TU Voltage (for driving SSR) E5CN-Q2TU 24 VAC/DC 0 Relay E5CN-RTU Voltage (for driving SSR) E5CN-QTU 1 Relay E5CN-R1TU Voltage (for driving SSR) E5CN-Q1TU 2 Relay E5CN-R2TU Voltage (for driving SSR) E5CN-Q2TU Note: Option Units (E53-CN@@N) cannot be used for Plug-in models. ■ Accessories (Order Separately) Terminal Cover Adapter Connectable models Terminal type Connectable models Terminal type Model E53-COV10 Model Y92F-45 Current Transformers (CTs) Note: Use this Adapter when the panel has been previously prepared for the E5B@. Model E54-CT1 E54-CT3 Hole diameter 5.8 dia. 12.0 dia. Sockets (for Models with Plug-in Connectors) 4 Model P2CF-11 P2CF-11-E P3GA-11 Y92A-48G Type Frontconnecting Socket Frontconnecting Socket with Finger Protection Backconnecting socket Terminal Cover for Finger Protection Digital Temperature Controllers E5CN/E5CN-U Specifications ■ Ratings Item Power supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz or 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power E5CN consumption E5CN-U 7.5 VA max. (E5CN-R2T: 3.0 VA at 100 VAC) 5 VA/3 W max. (E5CN-R2T: 2.7 VA at 24 VAC) 6 VA max. 3 VA/2 W max. Sensor input Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, or B Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 160 to 260°C Voltage input: 0 to 50 mV Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 W, Voltage input: 1 MW (Use a 1:1 connection when connecting the ES2-HB.) Control output E5CN SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA E5CN-U SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA E5CN E5CN-U Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit Relay output Voltage output Current output E5CN 4 to 20 mA DC/0 to 20 mA DC, load: 600 W max., resolution: approx. 2,700 Long-life relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, minimum applicable load: 5 V, 100 mA (Do not connect a DC load.) Alarm output Event input E5CN SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 1 V, 1 mA Contact input ON: 1 kW max., OFF: 100 kW min. Non-contact input ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Outflow current: Approx. 7 mA per point Control method ON/OFF control or 2-PID control (with auto-tuning) Setting method Digital setting using front panel keys Indication method 11-segment digital display and individual indicators (7-segments displays also possible) Character height: PV: 11 mm, SV: 6.5 mm Other functions Manual output, heating/cooling control, transfer output (on some models), loop break alarm, multi SP, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, etc. Ambient operating temperature -10 to 55°C (with no icing or condensation), for 3-year warranty: -10 to 50°C Ambient operating humidity 25% to 85% Storage temperature -25 to 65°C (with no icing or condensation) Digital Temperature Controllers E5CN/E5CN-U 5 ■ Input Ranges Thermocouples/Platinum Resistance Thermometers (Multi-inputs) Input Type Platinum resistance thermometer Pt100 Name Thermocouple JPt100 K J T E L Infrared temperature sensor U N R S B 10 to 70°C 60 to 120°C 115 to 165°C 160 to 260°C Temperature range (°C) Setting number 1700 1300 1700 1300 850 850 850 600 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 100.0 100.0 120 165 0 0 0 0 19 20 21 22 90 100 0.0 -200 -199.9 0 1 0.0 -199.9 2 3 0 - 20.0 -100 -20.0 6 7 8 -200 4 5 The applicable standards for the input types are as follows: 0 0 16 17 -100 -200 -199.9 9 10 11 12 - 200 -199.9 - 200 13 14 15 U: Cu-CuNi, DIN 43710-1985 18 Pt100: IEC 751 L: Fe-CuNi, DIN 43710-1985 Models with Analog Inputs Input Type Current Voltage Input specification 4 to 20mA 0 to 20 mA 1 to 5 V Setting range Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 Setting number 0 1 2 0 to 5 V 3 0 to 10 V 4 Digital Temperature Controllers E5CN/E5CN-U 23 Shaded settings are the default settings. K, J, T, E, N, R, S, B: IEC584-1 6 0 to 50 mV Usable in the following ranges by scaling: -1999 to 9999 or -199.9 to 999.9 1800 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 -100.0 -200.0 Analog input Shaded settings are the default settings. ■ Alarm Types Select alarm types out of the 12 alarm types listed in the following table. Set value Alarm type Alarm output operation When X is positive 0 Alarm function OFF 1 Upper- and lower(See note 1.) limit 2 3 Upper limit Lower limit 4 Upper- and lower(See note 1.) limit range 5 Upper- and lower(See note 1.) limit with standby sequence Output OFF H (See note 2.) X SP X ON OFF ON OFF SP L ON OFF ON OFF H X Case 3 (Always ON) ON OFF H ON OFF Absolute-value upper-limit ON OFF 9 Absolute-value lower-limit ON OFF 10 Absolute-value upper-limit with standby sequence ON OFF Absolute-value lower-limit with standby sequence ON OFF H>0, L<0 |H| > |L| SP L H<0, L>0 |H| ≥ |L| L SP H SP H L Case 1 (See note 3.) (See note 4.) Case 3 (Always ON) Case 2 H<0, L<0 L H SP H<0, L>0 |H| < |L| SP L H H H>0, L<0 |H| > |L| H SP L L SP SP X ON OFF SP H L SP X SP X 0 X 0 X 0 X 0 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF H>0, L<0 |H| ≤ |L| 3. Set value: 4, Upper- and lower-limit range X SP (See note 5.) Lower-limit with standby sequence H SP L H H SP SP SP L L H<0, L>0 |H| < |L| SP ON OFF 7 12 LBA (for alarm 1 (See note 6.) only) L ON OFF Upper-limit with standby sequence 11 Case 2 Case 1 H<0, L<0 6 8 When X is negative Note: 1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” 2. Set value: 1, Upper- and lower-limit alarm X SP X SP X 0 X 0 X 0 H<0, L>0 |H| ≥ |L| H>0, L<0 |H| ≤ |L| 4. Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF 5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. 6. Set value: 12, LBA can be set only for alarm 1. Set the alarm types for alarms 1 to 3 independently in the initial setting level. The default setting is 2 (upper limit). X 0 --- Digital Temperature Controllers E5CN/E5CN-U 7 ■ Characteristics ■ Communications Specifications Indication accuracy Transmission line connection method Hysteresis Thermocouple: (See note 1.) E5CN: (±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max. E5CN-U: (±1% of indicated value or ±2°C, whichever is greater) ±1 digit max. Platinum resistance thermometer: (±0.5% of indicated value or ±1°C, whichever is greater) ±1 digit max. Analog input: ±0.5% FS ±1 digit max. CT input: ±5% FS ±1 digit max. Models with thermocouple/platinum resistance thermometer (multi-input) input: 0.1 to 999.9 EU (in units of 0.1 EU) Models with analog input: 0.01 to 99.99% FS (in units of 0.01% FS) Proportional band (P) Models with thermocouple/platinum resistance thermometer (multi-input) input: 0.1 to 999.9 EU (in units of 0.1 EU) Models with analog input: 0.1 to 999.9% FS (in units of 0.1% FS) RS-485 multipoint Communications RS-485 (two-wire, half duplex) Synchronization method Start-stop synchronization Baud rate 1200, 2400, 4800, 9600, 19200, or 38400 bps Transmission code ASCII Data bit length 7 or 8 bits Stop bit length 1 or 2 bits Error detection Vertical parity (none, even, odd) Frame check sequence (FCS) with SYSWAY Block check character (BCC) with CompoWay/F or CRC-16 Modbus Flow control None Interface RS-485 None Integral time (I) 0 to 3999 s (in units of 1 s) Retry function Derivative time (D) 0 to 3999 s (in units of 1 s) (See note 3.) Control period 0.5, 1 to 99 s (in units of 1 s) Communications 40 bytes buffer Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Sampling period 250 ms Affect of signal source resistance Thermocouple: 0.1°C/W max. (100 W max.) (See note 4.) Platinum resistance thermometer: 0.4°C/W max. (10 W max.) Insulation resistance 20 MW min. (at 500 VDC) Dielectric strength 2,000 VAC, 50 or 60 Hz for 1 min (between terminals with different charge) Vibration Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, resistance and Z directions Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions Shock Malfunction 100 m/s2 min., 3 times each in X, Y, and Z resistance directions Destruction 300 m/s2 min., 3 times each in X, Y, and Z directions Weight E5CN Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g E5CN-U Controller: Approx. 110 g, Mounting Bracket: Approx. 10 g Degree of E5CN protection E5CN-U Memory protection Communications 0 to 99 ms response wait Default: 20 ms time Note: The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. ■ Current Transformer (Sold Separately) Ratings Dielectric strength 1,000 VAC for 1 min Vibration resistance 50 Hz, 98 m/s2 Weight E54-CT1: Approx. 11.5 g, E54-CT3: Approx. 50 g Accessories (E54-CT3 only) Armatures (2) Plugs (2) Front panel: NEMA4X for indoor use (equivalent to IP66) Rear case: IP20, Terminal section: IP00 Front panel: Equivalent to IP50, rear case: IP20, terminals: IP00 Non-volatile memory (number of writes: 1,000,000 operations) Note: 1. The indication of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and L thermocouples at any temperature is ±2°C ±1 digit maximum. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. 2. “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F. 3. When robust tuning (RT) is ON, the differential time is 0.0 to 999.9 (in units of 0.1 s). 4. B, R, and S sensors: 0.2°C/W max. (100 W max.) 8 Digital Temperature Controllers E5CN/E5CN-U (E5CN Models with Heater Burnout and SSR Failure Detection Alarms) Maximum 50 A AC heater current Input current indication accuracy ±5% FS ±1 digit max. Heater burnout 0.1 to 49.9 A (in units of 0.1 A) alarm setting 0.0 A: Heater burnout/SSR failure alarm output range turned OFF. 50.0 A: Heater burnout/SSR failure alarm output turned ON. Minimum detection ON time: 190 ms (See note 1.) SSR failure detection alarm setting range 0.1 to 49.9 A (in units of 0.1 A) 0.0 A: Heater burnout/SSR failure alarm output turned ON. 50.0 A: Heater burnout/SSR failure alarm output turned OFF. Minimum detection OFF time: 190 ms (See note 2.) Note: 1. If the ON time of control output 1 is less than 190 ms, heater burnout detection and the heater current will not be measured. 2. If the OFF time of control output 1 is less than 190 ms, SSR failure detection and the heater current will not be measured. ■ Electrical Life Expectancy Curve for Relays (Reference Values) Life (× 104 operations) ■ Heater Burnout Alarms and SSR Failure Detection Alarms 500 300 100 50 30 10 5 E5CN 250 VAC, 30 VDC (resistive load) cosφ = 1 3 1 0 1 2 3 4 5 6 Switching current (A) Note: Do not connect a DC load to a Controller with a Long-life Relay Output. Digital Temperature Controllers E5CN/E5CN-U 9 External Connections • A voltage output (control output) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current. • Standard insulation is applied between any of the following: power supply terminals, input terminals, output terminals, and communications terminals (for models with communications). If reinforced insulation is required, provide additional insulation, such as spacial distance or material insulation, as defined by IEC 60664 suitable for the maximum operating voltage. E5CN Current Output 1 Control output 1 2 Voltage Output + 1 4 to 20 mA DC/ 0 to 20 mA DC 2 − Relay Output Alarm Outputs + 1 12 VDC 21 mA 1 11 6 6 2 12 7 7 3 13 8 8 4 14 9 5 15 10 2 − A + mA Analog input − V + − B B + Pt Alarm 2 Input power supply Note: Output when an input error output is enabled in the Advance Function Setting Level. If an input error output is enabled, the a1-1 operation indication on the front panel will not light and s.err will be displayed on the No. 1 display. TC Platinum Infrared resistance temperature thermometer sensor The input power supply depends on the power supply specification of the Controller and is either 100 to 240 VAC or 24 VAC/DC (no polarity). B 11 B 11 RS-485 12 13 Do not connect. 13 Event input 2 14 Voltage output 12 VDC, 21 mA + 11 Control output 2 12 13 Do not connect. 12 − 13 14 14 Control output 2 CT1 15 Heater burnout/ SSR failure detection input Event input/ Heater burnout / SSR failure detection A + 14 CT2 CT1 11 RS-485 12 A Event input 1 Alarm 1/ Heater burnout alarm/ Input error output (See note.) 15 15 − Heater burnout/ Voltage output SSR failure 12 VDC, 21 mA detection input Communications/ Communications/ Heater burnout/ voltage output SSR failure specification detection (2-CT input) CT1 15 Heater burnout/ SSR failure detection input Voltage output/ Heater burnout/ SSR failure detection Terminals 11 to 15 do not exist on models without an Option Unit (heater burnout detection, control output 2, event inputs, or communications). Terminal applications depend on the model of the Option Unit. E5CN-U Voltage Output − 5 DC12V Control output 1 4 21mA + Relay Output One Alarm Output 5 B B Pt 0 to 50 mV input only Platinum resistance thermometer 7 8 4 A − Analog input + 6 3 − 9 2 1 Do not connect. 10 11 Input power supply + TC Infrared temperature sensor The input power supply depends on the power supply specification of the Controller and is either 100 to 240 VAC or 24 VAC/DC (no polarity). Order the P2CF-11 or P3GA-11 Socket separately. (See page 14.) 10 Alarm 1/ Input error output (See note.) Digital Temperature Controllers E5CN/E5CN-U Two Alarm Outputs 7 8 9 Alarm 1/ Input error output Alarm 2/ Control output 2 Note: Output when an input error output is enabled in the Advance Function Setting Level. If an input error output is enabled, the al-1 operation indication on the front panel will not light and s.err will be displayed on the No. 1 display. Nomenclature E5CN E5CN-U The front panel is the same for the E5CN and E5CN-U. Temperature unit No.1 display Operation indicators No. 2 display Up Key Level Key Mode Key Down Key Dimensions ■ Standard Models E5CN Terminal Models Panel Cutout Group Mounted Mounted Separately (48 × number of units −2.5) +1.0 0 91 6 48 × 48 78 45 +0.6 0 44.8 × 44.8 48.8 58 Group mounting does not allow waterproofing. 60 min. 45 +0.6 0 Mounting Adapter (Accessory) Terminal Cover (E53-COV10) E5CN-U Plug-in Models 45 +0.6 0 • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. Panel Cutout Group Mounted Mounted Separately (48 × number of units −2.5) +1.0 0 6 48 × 48 14.2 70.5 45 +0.6 0 44.8 × 44.8 58 60 min. 45 +0.6 0 Mounting Adapter (Accessory) 45 +0.6 0 Digital Temperature Controllers • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. E5CN/E5CN-U 11 ■ Accessories Terminal Cover 48 E53-COV10 48.8 22 Note: The suffix “500” is added to the model number of each Controller provided with a E53-COV10 Terminal Cover. 9.1 Current Transformers (Sold Separately) E54-CT1 21 15 2.8 5.8 dia. 7.5 25 3 10.5 40 Two, 3.5 dia. 10 30 E54-CT3 Accessory E54-CT3 2.36 dia. Connection Example • Armature 30 Armature Plug 12 dia. 9 Approx. 3 dia. Lead 40 × 40 18 • Plug Two, M3 (depth: 4) Approx. 6 dia. 15 30 12 Digital Temperature Controllers E5CN/E5CN-U (22) Adapter Note: Use this Adapter when the panel has already been prepared for the E5B@. Y92F-45 Fixture (Accessory) 76 4.7 69.6 to 77.6 72 × 72 67 × 67 87 Mounted to E5CN Panel (1 to 8 mm) 72 × 72 48 × 48 2.2 4.7 77.3 (to back of E5CN) E5CN-U Wiring Socket (Sold Separately) Front-connecting Socket P2CF-11 Eleven, M3.5 × 7.5 sems screws 3 Terminal Layout/Internal Connections (Top View) 4.5 7.8 8 7 6 5 Mounting Holes 4 Two, 4.5 dia mounting holes 35.4 70 max. Two, 4.5-dia. holes 4 9 3 10 11 1 2 40±0.2 Note: Can also be mounted to a DIN track. 50 max. 31.2 max. Note: A model with finger protection (P2CF-11-E) is also available. Back-connecting Socket P3GA-11 27 dia. 4 7 3 Terminal Layout/Internal Connections (Bottom View) 5 6 7 8 4 45 25.6 3 9 2 1 11 10 45 4.5 16.3 6.2 6 8.7 Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets. 2. A Protective Cover for finger protection (Y92A-48G) is also available. Digital Temperature Controllers E5CN/E5CN-U 13 14 Digital Temperature Controllers E5CN/E5CN-U Operation ■ Outline of Operation Procedures The following diagram illustrates the entire setting level. A password is required to enter the advance function setting level and the calibration level. Some parameters may not be displayed depending on the protection settings and operation conditions. The control operation will stop when switching from operation level to initial setting level. ] Power ON Starting in manual mode Starting in automatic mode Press the Level Key for at least 1 s. Operation Level C Manual Mode Press the Level Key less than 1 s. a-m Press the Level Key for at least 1 s; display will flash. Press the Level Key (See for at least 3 s while note 3.) a-m is displayed. Manual Control Level Press the Level Key for at least 1 s. Press the Level + Mode Keys; display will flash. Adjustment Level C (See note 1.) Press the Level + Mode Keys. Press the Level Key for at least 1 s 25 100 for at least 1 s; display will flash. 25 100 Press the Level + Mode Keys for at least 3 s. (See note 4.) Press the Level Key for at least 3 s. Control stops . Communications Setting Level Initial Setting Level C Protect Level Press the Level Key for less than 1 s. Press the Level Key for at least 1 s. Input password. Set value −169 Advanced Function Setting Level Control in progress Input password. Set value 1201 Calibration Level Note: 1. 2. 3. 4. (See note 2.) Control stopped Not displayed for some models Level change Operation level entered for software reset. You cannot move to other levels by operating the keys on the front panel from the calibration level. You must turn OFF the power supply. You can move only to the operation level by operating the keys on the front panel from the manual control level. The time taken to move to the protect level can be adjusted by changing the “Move to protect level time” setting. Digital Temperature Controllers E5CN/E5CN-U 15 ■ Parameters Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN/E5CN-U Temperature Controller User's Manual (Cat. No. H129) Press the Level Key for at least 3 s. (Display flashes for at least 1 s.) Displays other than that for switching between automatic and manual Power ON Starting in manual mode Manual Control Level C 25 PID control only Press the Level Key for at least 1 s. PV/MV Starting in automatic mode Press the Level Key less than 1 s. Adjustment Level Operation Level l.adj a Adjustment level display d Derivative time 40 off a a c-sc Cooling coefficient ct1 Heater current value 1 0.0 monitor 1.00 a C a a C a hb1 Heater burnout 1 0.0 detection 50.0 wt-b Wait band 0.0 a a sp-1 SP 1 0 C SP used by multi-SP a sp-2 SP 2 sprt SP ramp set value r-s c-o MV monitor (cooling) 0.0 a Run/stop run a Press the Level + Mode Keys for at least 3 s. Display flashes. The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Communications Setting Level Displayed only for models with communications. Changes are effective after cycling power or after a software reset. a ol-l MV lower limit 0 -5.0 a shift ins Temperature input 1-point shift a 0.0 insh Upper-limit temperature input 0.0 2-point shift a insl Lower-limit 0.0 temperature input pmoV Set either of these parameters. Move to protect level Displayed only when a password 0 is set. Restricts moving to protect level. a oapt a Operation/adjustment protection Restricts displaying and modifying 0 menus in operation, adjustment, and manual control levels. a Initial Setting/ Communications Protection icpt This protect level restricts movement 1 to the initial setting, communications setting, and advanced function setting levels. a change protection wtpt Setting Protects changes to setups by off operating the front panel keys. a on parameter mask is set. a prlp 0 a psel Protocol setting Switches between cwf CompoWay/F a (SYSWAY) and Modbus. u-no Communications 1 a Unit No. CompoWay/F bps Baud rate (SYSWAY) only 9.6 a len Data bits 7 a sbit Stop bits 2 mask enable pmsk Parameter Displayed only when a 16 Press the Level Key less than 1 s. Press the Level + Mode Keys for at least 1 s. Protect Level a 105.0 sp-3 SP 3 a a a off ol-h MV upper limit 0 a C 0.0 a mV-e MV at PV error 0 o MV monitor (heating) rset a sp-0 SP 0 0 0 0.0 a al3l Lower-limit alarm value 3 a Program start soak sktr Remaining time monitor mV-s MV at stop 50.0 C 0.0 a hs2 SSR failure detection 2 0 C a off a al3h Upper-limit alarm value 3 a current lcr2 Leakage value 2 monitor prst al-3 Alarm value 3 0 C a a C 0 a current lcr1 Leakage 0.0 value 1 monitor 1 al2l Lower-limit alarm value 2 a C a soak Soak time a 0 current value 2 ct2 Heater 0.0 monitor chys Hysteresis (cooling) al2h Upper-limit alarm value 2 a 0.0 a hb2 Heater burnout 2 0.0 detection hs1 SSR failure detection 1 current value 1 ct1 Heater monitor C a 1.0 a 0 a Hysteresis settings al-2 Alarm value 2 a C 0 hys Hysteresis (heating) a C 0 a C SP ramp monitor sp-m Manual reset value 1.0 a a C a lcr2 Leakage current value 0.0 2 monitor al1l Lower-limit alarm value 1 0 set m-sp Multi-SP 0 point setting 50.0 of P or PD control. a C switching function is added. a of-r Clear the offset during stabilization 0.0 1 monitor C c-db Dead band Press the Level Key for at least 3 s. (Display flashes for at least 1 s.) 0.0 lcr1 Leakage current value C Heating/cooling a ct2 Heater current value 2 0.0 monitor al1h Upper-limit alarm value 1 Auto/manual switch control only a-m PID Added when auto/manual a cmwt Communications writing C a 233 a 0 C 0 PID settings al-1 Alarm value 1 a value/ 25 Process set point C i Integral time C display is added. a a off C p Proportional band 8.0 at AT execute/cancel C value 25 Process Added when PV C C Displayed only once when entering adjustment level. Set either of these parameters. Set either of these parameters. Set either of these parameters. Press the Level Key less than 1 s. Password to move to protect level Password setting Digital Temperature Controllers E5CN/E5CN-U a prty Communications eVen parity a sdwt Send delay 20 a Press the Level Key for at least 1 s. Initial Setting Level Advanced Function Setting Level Press the Level Key less than 1 s. in-t Input type Parameter a 100 0 c 1300 rest a a ptrn Program C cp Control period (heating) 20 c-cp Set the pulse output cycle. C alt2 Alarm 2 type hbl Heater burnout latch 2 off a hbh 2 tr-h Transfer output upper limit 100.0 0 15.0 alfa α tr-l Transfer output lower limit 0.0 a alm2 assignment csel Display text switch on t-u Soak time unit m alsp Alarm SP selection sp-m cmoV Move to calibration 0 level 0 a a istp Input shift type inf Input digital filter a alm2 Alarm output 2 a3of Alarm 3 OFF delay ins1 0.0 o1-t Linear current output alm1 assignment a a a alm1 Alarm output 1 a a2of Alarm 2 OFF delay st-b ST stable range none assignment a a 0.65 a 0 0 a C a3on Alarm 3 ON delay a1of Alarm 1 OFF delay Heater burnout 0.1 hysteresis out2 Control output 2 a a a Alarm 3 type a 4-20 0 a a o assignment a a2on Alarm 2 ON delay on detection 2 a Linear output 0 a hbu Heater burnout out1 Control output 1 a a1on Alarm 1 ON delay 0.2 a alt1 Alarm 1 type a 5.0 alh3 Alarm 3 hysteresis 3.0 width a pV-b PV stable range a a a off C n-o alarm or-r tr-t a al3n Alarm 3 open in 20 Transfer output type red a Control period (cooling) oreV Direct/reverse operation colr PV display color alh2 Alarm 2 hysteresis lbab LBA detection a a 0.2 a alt3 off switching n-o alarm C a rlrV MB command logic a a a on compensating method a al2n Alarm 2 open in off pattern a cjc Cold junction alh1 Alarm 1 hysteresis lbal LBA detection 8.0 threshold a 0.2 When assigning PID or control output to pulse output C off a a a sero Input error output a For input type of temperature, standard, or PID on 0 a n-o alarm C lba LBA detection time 3 al1n Alarm 1 open in stnd a prlt Move to protect level time Standby sequence a s-hc Standard or heating/ cooling st ST a a reset method onof 0.1 hysteresis off m a a hsh SSR failure a3lt Alarm 3 latch a cntl PID ON/OFF off a spru SP ramp time unit -200 hsl SSR failure latch off a sl-l SP lower limit a a2lt Alarm 2 latch off Limit the set point. a on detection a mspu Multi-SP uses a hsu SSR failure off a sl-h SP upper limit a a1lt Alarm 1 latch stop assignment 2 temperature off a eV-2 Event input unit d-u Temperature For input type of °C, °F a Auto/manual switching function addition rt RT off display mode a a C a none assignment 1 For input type of analog off ret Automatic return of eV-1 Event input dp Decimal point amad off a 0 a a o-dp MV display 1 Four SPs: 2 in-l Scaling lower limit off stop/error a Number of multi-SP uses eV-m Two SPs: 1 a mVse Additional MV for off display off in-h Scaling upper limit C pVad Additional PV init initialization 5 a a Linear output a amoV 0 a Move to advanced function setting level Move by setting password (−169). Displayed when initial setting/ communications protection is set to 0 Digital Temperature Controllers E5CN/E5CN-U 17 Improvements to E5CN Functionality ■ Changes Model numbers have been changed to allow for multi-input specifications. Before Change E5CN-@@@TC (models for thermocouples) E5CN-@@@P (models for platinum resistance thermometers) After Change E5CN-@@@T (Models that support both thermocouples and platinum resistance thermometers) Precautions in Replacing Previous Controllers • The input type setting numbers have changed to allow for multiinput specifications. (The default setting is for a K sensor between -200 and 1,300°C.) • Previous E5CN Controllers cannot be removed from the case for replacement with new models. Replace the case at the same time. • The previous ThermoTools cannot be used with the new Controller models. Use the ThermoTools scheduled for marketing from July 2004. • The height of the front panel that extends when the Controller is mounted to a panel has been reduced from 9 to 6 mm. Note: Items That Have Not Been Changed • Panel cutout dimensions • Panel interior dimensions for panel mounting • Wiring terminal sizes • Wiring terminal arrangement • Parameter setting procedure 6 mm The following items do not change in comparison to the previous E5CN models: Panel cutout, Internal panel dimensions for panel mounting, wiring screw sizes, wiring terminal arrangement, and parameter setting methods. ■ Improved Functions The previous and new models can be easily differentiated by looking at the front panel. The OMRON logo is in a different position. Item Previous models (OMRON logo: lower left) Improved models (OMRON logo: upper left) Front panel ALM1 ALM2 HB OUT1 STOP OUT2 CMW Basically, the Controllers are upwardly compatible. The terminal arrangement, terminal sizes, and depth for panel mounting have not been changed. Changes are listed in the following tables. For details, refer to the E5CN/E5CN-U Temperature Controller User's Manual (Cat. No. H129) and to the E5CN Temperature Controller Communications User's Manual (Cat. No. H130). 18 Digital Temperature Controllers E5CN/E5CN-U ■ Specifications Ratings Item Power E5CN consumption E5CN-U Sensor input Previous models Improved models 7 VA (100 to 240 VAC, 50/60 Hz) 4 VA/3 W (24 VAC, 50/60 Hz or 24 VDC) 7.5 VA (100 to 240 VAC, 50/60 Hz) 4 VA/3 W (24 VAC, 50/60 Hz or 24 VDC) 6 VA (100 to 240 VAC, 50/60 Hz) 3 VA/2 W (24 VAC, 50/60 Hz or 24 VDC) 6 VA (100 to 240 VAC, 50/60 Hz) 3 VA/2 W (24 VAC, 50/60 Hz or 24 VDC) E5CN-@@TC Thermocouple: K, J, T, E, L, U, N, R, S, or B Infrared temperature sensor: 10 to 70°C, 60 to 120°C or 115 to 165°C (160 to 260°C) Voltage input: 0 to 50 mV E5CN-@@T (Multi-input models) Thermocouple: K, J, T, E, L, U, N, R, S, or B Infrared temperature sensor: 10 to 70°C, 60 to 120°C or 115 to 165°C (160 to 260°C) Voltage input: 0 to 50 mV Platinum resistance thermometer: Pt100 or JPt100 E5CN-@@P Platinum resistance thermometer: Pt100 or JPt100 (No models with analog inputs) E5CN-@@L (Models with analog inputs added.) Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V E5CN-R@@ SPST-NO, 250 VAC, 3 A (resistive load) Electrical life: 100,000 operations min. E5CN-R@@ SPST-NO, 250 VAC, 3 A (resistive load) Electrical life: 100,000 operations min. --- E5CN-Y@@ (Added models with long-life relay outputs.) (To be available soon) SPST-NO, 250 VAC, 3 A (resistive load) Electrical life: 1,000,000 operations min. DC loads cannot be connected. Voltage E5CN-Q@@ 12 VDC ±15% (PNP) Max. load current: 21 mA With short-circuit protection E5CN-Q@@ 12 VDC ±15% (PNP) Max. load current: 21 mA With short-circuit protection Current E5CN-C@@ 4 to 20 mA DC Load: 600 W max. Resolution: Approx. 2,600 E5CN-C@@ 4 to 20 mA DC or 0 to 20 mA DC Load: 600 W max. Resolution: Approx. 2,700 Voltage (No models with two control outputs) (Option Unit) 12 VDC ±15% (PNP) Max. load current: 21 mA With short-circuit protection Display method 7-segment digital display and single-LED indicators Character height: PV: 9.9 mm, SV: 6.4 mm 11-segment digital display and single-LED indicator (Improved visibility) (A 7-segment digital display also possible.) Character height: PV: 11.0 mm, SV: 6.5 mm Transfer output (No models with transfer outputs) E5CN-C@@ (current output) Allocated to current output 4 to 20 mA DC or 0 to 20 mA DC Load: 600 W max. Resolution: Approx. 2,700 Control output Control output 2 Relay Digital Temperature Controllers E5CN/E5CN-U 19 Other Functions Item Previous models Display --- Improved models Parameter mask function (provided with setting software) PV display switch between 2 colors (red/green) PV display switch between 3 colors (red/orange/green) --- Display character switch (7-segment/11-segment) Input Temperature input shift (1-point shift for temperature input, Temperature input shift (2-point shift also possible for temperature 2-point shift for no-contact sensor input) input) Output --- Manual outputs --- MV at stop --- MV at PV error Control Alarm Other --- Loop break alarm Control period: 1 to 99 s Control period: 0.5 or 1 to 99 s --- Robust tuning --- Alarm delays --- Alarm SP selection (selection of alarm operation of SP indicator) --- Simple programming function --- Password to move to protect level --- Setting software port Characteristics Item Sampling period Previous models 500 ms Improved models 250 ms Communications Specifications Item Previous models Improved models Communications protocols CompoWay/F (SYSWAY) CompoWay/F (SYSWAY), Modbus Baud rate 1200, 2400, 4800, 9600, 19200 bps 1200, 2400, 4800, 9600, 19200, 38400 bps Heater Burnout/SSR Failure Detection Characteristics Item Maximum heater current SSR failure detection 20 Previous models Improved models Option Units Single-phase 50 A VAC Option Units Single-phase 50 A AC --- Option Units (two CT inputs) Three-phase 50 A AC --- SSR failure detection Digital Temperature Controllers E5CN/E5CN-U Precautions Note: Refer to the ntlp: Electronic Temperature Controller Catalog (Cat. No. ntlp) for common precautions. Precautions for Safe Use !CAUTION Do not touch any of the terminals while the power is being supplied. Doing so may occasionally result in minor electric shock. Do not allow pieces of metal or wire cuttings to get inside the Temperature Controller. Failure to do so may occasionally result in minor electric shock, fire, or damage to equipment. Do not use the Temperature Controller in locations subject to flammable or explosive gas. Doing so may occasionally result in minor injury due to explosion. Do not attempt to disassemble, modify, or repair the Temperature Controller or touch any internal components. Doing so may occasionally result in minor electric shock, fire, or damage to equipment. Caution: Danger of Electric Shock a) This Temperature Controller is UL-listed as an opentype process controller. Use it in a control panel structure so that fire will not leave the panel. b) When using two or more cutoff switches, turn OFF all switches so that no power is supplied to the Temperature Controller before maintenance or inspections. c) Signal inputs are SELV restricted circuits. (See note 1.) d) Caution: To reduce the danger of fire or electric shock, do not internally connect the outputs of different class 2 circuits. (See note 2.) If the output relay is used beyond its life expectancy, its contacts may occasionally become fused or burned. Always consider the actual application conditions and be sure to use the output relay within its rated load and electrical life expectancy. The life expectancy of the output relay varies considerably according to its switching capacity and operating conditions. Fire may occasionally occur if terminal screws become loose. Tighten the terminal screws using a torque between 0.74 and 0.90 N·m. Make settings for the Temperature Controller that are suitable for the controlled system. Failure to do so may result in unexpected operation occasionally resulting in damage to equipment or personal injury. Warning: To reduce the danger or electric shock or fire, use the Temperature Controller in an controlled environment relatively free from polluting materials. Take appropriate safety measures, such as installing a separate monitoring system, to ensure safe operation in the event of a malfunction of the Temperature Controller. Loss of operation control or alarm outputs due to malfunction may occasionally result in physical damage to the controlled system or equipment. Note: 1. An SELV circuit is one separated from the power supply with double insulation or reinforced insulation, that does not exceed 30 V r.m.s. and 42.4 V peak or 60 VDC. 2. A class 2 power supply is one tested and certified by UL as have the current and voltage of the secondary output restricted to specific levels. 1. Do not use the Temperature Controller in the following locations. • Locations exposed to radiated heat from heating devices • Locations subject to exposure to water or oil • Locations subject to direct sunlight • Locations subject to dust or corrosive gas (especially sulfide gas or ammonia gas). • Locations subject to severe temperature changes • Locations subject to icing or condensation • Locations subject vibration or strong shock 2. Use and store the Temperature Controller within the rated ambient temperature and humidity. When two or more Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers. 3. Allow enough space around the Temperature Controller to ensure proper heat dissipation. Do not block the ventilating holes. 4. Be sure to wire terminals properly using the correct polarity. 5. Use crimp terminals with the specified dimensions (M3.5, width 7.2 mm max.). Use wires of a thickness of AWG24 (0.205 mm2) to AWG14 (2.081 mm2). The exposed current-carrying part to be inserted into terminals must be 5 to 6 mm. 6. Do not connect anything to unused terminals. 7. Allow as much space as possible between the Controller and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. Keep the wiring for the Temperature Controller's terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to Temperature Controller wiring. 8. Use the Temperature Controller within a power supply voltage and load that meet all specifications and ratings. 9. Set up the power supply so that the voltage will reach the rated voltage within 2 seconds after turning ON. 10. Allow at least 30 minutes for the Temperature Controller to warm up. 11. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Temperature Controller. 12. Install the appropriate switches and circuit breakers and label them accordingly so that power can be turned OFF in an emergency by the person operating the Temperature Controller. 13. If you remove the Controller from its case, do not touch or apply shock to the electronic parts inside. When placing the Controller back in the case, make sure that electronic parts do not come in contact with the case. 14. Use alcohol to clean the Temperature Controller. Do not use thinner or other solvent-based substances. 15. It will require 2 seconds for the outputs from the Temperature Controller to stabilize after turning ON the power supply. Design the system (e.g., the control panel) to allow for this time. 16. Outputs will turn OFF depending on the mode when switching to the initial setting mode. Confirm system safety before switching the mode. Digital Temperature Controllers E5CN/E5CN-U 21 Mounting Order the P2CF-11 or P3GA-11 Socket separately. Service Life 1. Use the Temperature Controller within the following temperature and humidity ranges: Temperature: -10 to 55°C (with no icing or condensation) Humidity: 25% to 85% If the Controller is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the Controller. 2. The service life of electronic devices like Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Temperature Controller. 3. When two or more Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors. Measurement Accuracy 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. Mount the Temperature Controller so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly. Waterproofing The degree of protection is as shown below. Sections without any specification on their degree of protection or those with IP@0 are not waterproof. Terminal Cover (order separately) Mounting Adapter (Accessory) E5CN-U Front-mounting Socket (Panel mounting is also possible.) Waterproof packing E5CN Panel Mounting to a Panel 1. To mount the Controller so that it is waterproof, insert the waterproof packing onto the Controller. Group mounting does not allow waterproofing. The waterproof packing is not required if waterproofing is not necessary. The Panel Mounting Adapter is also included with the E5CN-U. Waterproof packing is not included with the E5CN-U. 2. Insert the E5CN/E5CN-U into the mounting hole in the panel. 3. Push the adapter along the Controller body from the terminals up to the panel, and fasten it temporarily. 4. Tighten the two fixing screws on the adapter. Alternately tighten the two screws a little at time to keep them balanced. Tighten them to a torque of 0.29 to 0.39 N·m. Attaching the Terminal Cover Make sure that the “UP” letters on the E5CN are at the top and insert the terminal cover into the holes at the top and bottom of the Controller. Removing the Controller from the Case When carrying out maintenance on the Controller, the Controller can be removed from the case with the terminal leads still attached. The Controller can be removed from the case only with the E5CN. It cannot be removed with the E5CN-U. Tool insertion hole Flat-blade screwdriver (Unit: mm) Front panel: NEMA4X for indoor use (equivalent to IP66) Rear case: IP20, Terminal section: IP00 (E5CN-U: Front panel: Equivalent to IP50, rear case: IP20, terminals: IP00) (1) ALM1 20 min. Precautions for Correct Use ALM2 ALM3 HA PV OUT1 (3) OUT2 STOP CMW MANU SV 22 (2) (1) 2.0 1. It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Temperature Controllers in a sequence circuit. 2. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Temperature Controller. If power is turned ON for the Temperature Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. 3. When starting operation after the Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.) Avoid using the Controller in places near a radio, television set, or wireless installing. 4. These devices can cause radio disturbances which adversely affect the performance of the Controller. 0.4 Operating Precautions E5 C N 1. Insert the tool into the slots (one on the top and one on the bottom) and release the hooks. 2. Insert the tool into the gap between the front panel and rear case and pull out the front panel slightly. Hold both sides of the front panel and draw out the Controller towards you. Do not apply unnecessary force. 3. Before inserting the Controller, confirm that the sealing rubber is in place. Insert the Controller into the rear case until you hear a click. Press on the hooks on the top and bottom of the rear case to be sure that the hooks are securely locked in place.Be sure that electronic parts do not come in contact with the case. Digital Temperature Controllers E5CN/E5CN-U Wiring Precautions • Separate input leads and power lines to protect the Controller and its lines from external noise. • Use wires of a thickness of AWG24 (0.205 mm2) to AWG14 (2.081 mm2). The exposed current-carrying part to be inserted into terminals must be 5 to 6 mm. • We recommend using crimp terminals when wiring the terminals. • Tighten terminal screws to a torque of 0.74 to 0.90 N·m. • Use the following type of crimp terminals for M3.5 screws. 7.2 mm min. 7.2 mm min. Digital Temperature Controllers E5CN/E5CN-U 23 Warranty and Application Considerations Read and Understand this Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Disclaimers PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. Cat. No. H128-E1-01 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company Industrial Devices and Components Division H.Q. Measuring Components Department Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7080/Fax: (81)75-344-7189 24 Printed in Japan 0404-??M (0404) (?)