FUJI EDS11-166A

PUM Series
Multi-loop module type
Temperature controller
Enhanced communication
Module (CC-Link) [PUMCL]
DATA SHEET
PUMCL
PUMCL is a communication module, which connects module
type temperature controller PUM series with CC-Link system. Compatible with CC-Link Ver1.1 and 2.0, and designed
for high-speed communication at the maximum speed of
10Mbps. Being able to up to 16 units (64 channel) of PUMA
(control module), PUMCL requires minimum wiring, less
space, and saves labor for engineering.
FEATURES
I. Program-less connection to CC-Link
1. CC-Link Ver1.1 / Ver2.0 compatible
High-speed communication at max.10Mbps
2. Access to all parameters of control module (PUMA/
PUMB) via CC-Link
3. High-speed data communication with connected control
modules (PUMA/PUMB)
- Quick data importing and setting data reflection
II.User-friendly structure and functions
1. Lateral connection : Max.16 units (64 channels) + event
input/output module 16 units = total 32 units
Simple wiring for power supply and communication
2. Detachable structure: Terminal block, main unit, and
the base part
→ Easy wiring with detachable terminal blcok
→ Main units exchangeable without re-wiring
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2.Module type
1)Analog module: Total maximum 16 units
a)Control module (4 loop/unit)
b)Extended input/output module
-Analog input/output module
(Input/output 4 points/unit)
-Analog input module (Input 4 points/unit)
-Analog output module (output 4 points/unit)
2)Extended input/output (digital) module:
Maximum 16 units
-Event input/output module
(Input/output ; 8 points/unit)
3)Enhanced communication module: 1 unit
3.Connecting method:
Lateral connecting with connectors
-For power supply and RS-485 communication,
any one of connected modules is required to be
connected.
4.No. of loop, input/output
1)Control loop:
Max. 64
2)No.of input / output: DI 128 points / DO 128 points
Enhanced communication module
(CC-Link) specification
1. General specification
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
[when 24V DC is applied]
(3) Insulation resistance: 20MW or more (500V DC)
(4) Withstand voltage:
Power supply ↔ loader communication
1000V AC 1 min.
Power supply ↔ SLD/FG terminal, CC-Link
communication
500V AC 1 min.
SLD/FG terminal ↔ CC-Link communication
50V AC 1 min.
(5) Applied standards:
UL, C-UL, RoHS directive
[Pending for UL and C-UL]
2. CC-Link communication module
2.1 CC-Link communication
(1) Compliant version: CC-Link Ver.2.00 / 1.10
(2) Station type: Remote device
(3) Communication speed and distance
Speed
156kbps
Distance 1200m
or less
625kbps
2.5Mbps 5Mbps
10Mbps
900m
or less
400m
or less
100m
or less
200m
or less
(4) Occupation No. of channel/station:
4 stations/station No.setting; 1 to 61
(5) Commnication data length
No.of occupied stations/extended cyclic
Remote
Remote
input/output
registor
(RX/RY)
(RWr/RWw)
Control module
(PUMA/B) No.
of connectable
units
4 stations occupied × 1
128 bit
16 words
4 stations occupied × 2
256 bit
32 words
2 or 4 units
4 or 8 units
4 stations occupied × 4
512 bit
64 words
8 or 16 units
(6) Connecting cable: Ver1.10 compatible cable for CC-Link
(7) Connecting method: M3 screw terminal block
(8) Termination resistace: External (110W, 1/2W)
EDS11-166a
Date
Apr. 1, 2011
PUMCL
2.2 Display, configuration
Status display LED
(2 colors × 2 points + 4 points)
(2) Display contents:
RUN/FAULT, control module connection
status (TX/RX), CC-Link status (L.RUN,
L.ERR, SD, RD)
(3) Setting device and set contents
(1) Display:
Setting device
Set contents
Front
Rotary SW × 2
CC-Link Station No. setting
Inside
Rotary SW × 1
CC-Link speed setting
Dip SW (6bit) × 1 CC-Link mode setting
3. Power outage
(1) Impact of power outage:
Outage of 2ms or less ; no impact
(2) Operation after power outage:
Start from the first step (cold start)
(3) Memory backup:
Nonvolatile memory (EEPROM)
No. of update ; 100,000
4. Self diagnosis
Diagnosis method:
Program error monitoring by watch dog
timer
5. Structure
(1) Installation method:
DIN rail mounting or mounting with M3
screws inside a cabinet
(2) Dimensions: 30 (W) × 100 (H) × 85 (D) mm
(excluding terminal cover and projected
part)
(3) Weight:
Approx. 200 g
(4) Extrenal terminal
- CC-Link communication:
Detachable terminal block
(M3 screw × 20 terminals)
- Power supply connection:
Terminal block on the base part
(M3 screw × 2 terminals)
Power is supplied via side connectors
in case of lateral connecting. (Max. 33
units)
- Loader communication port:
2.5 diameter mini-plug / jack
[on the front of the module]
(5) Case material: Polyphenylene oxide
(flame retardant grade : UL94V-0 equivalent)
(6) Case color: Case ; red
Terminal, base part ; black
(7) Protection
- Body:
IP20 grade protection
(ventilation slits on the top and the bottom of the body)
- Terminal: IP00 grade protection, terminal cover is
available as an option
6. Normal operating condition
2
(1) Ambient temperature*: -10 to 50°C
* “Ambient temperature” is the temperature underneath the controller inside
the equpiment or the cabinet where
the controller is installed.
(2) Ambient humidity:
90% RH or less (non condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
7. Transporting, storage condition (packing condition)
(1) Storage temperature: -20 to 60°C
(2) Ambient humidity: 90%RH or less (no condensing)
(3) Vibration:
10 to 70Hz, 9.8m/s2 (1G) or less
(4) Shock:
294m/s2 (30G) or less
8. Packing list
Temperature controller:1unit
Instruction manual:
1 copy
Termination resistor of internal communication:
1 unit
9. Loader software
(1) Distribution medium:
Free download from Fuji Electric Systems HP (http://www.fic-net.jp/eng/index.
html)
(2) Recommended operating environment
PC:
DOS/V (PC-AT compatible)
OS:
Windows XP (operation confirmed in
Japanese / English)
RAM:
256M bytes or more
Free space on the hardware: 500M bytes or more
Display resolution: 1024 × 768 or over
Serial interface: RS-232C 1 port
(without RS-232C, USB serial converter
cable required)
(3) Connection with PUM
Via loader interface on the front face of the module
(special cable available from Fuji is required) or via
RS-485
CODE SYMBOLS
[Enhanced communication module]
Digit
1 2 3 4 5 6 7 8
9 10
P UM
0
Digit
Description
4 < Module type >
Enhanced communication module
5 < Communication function >
CC-Link communication
10 < Operation manual >
Japanese
English
C
L
A
B
Digit
[Accessories]
YY1
1 2 3 4 5 6 7 8
P UM Z *
Digit
Description
6 DIN rail mounting end plate
7 Side conneting terminal cover
(right & left 1 set)
8
Front face screw terminal cover
Loader connecting cable (RS-232C)
A 0 2
A 0 3
A 0 4
L 0 1
[Table 1]Insulation block diagram
Power
SLD/FG terminal
(CC-Link connecting terminal)
Loader communication port
CC-Link communication
Functional insulation (1000VAC)
Functional insulation (500VAC)
Functional insulation (50VAC)
OUTLINE DIAGRAM (Unit : mm)
Front terminal cover (Option)
(10)
30
Base part
(Main unit is detached)
Terminal block
(at attach/detach)
85
Hole for screw mounting
STATION No. LOADER
×10
50
×1
6
100
1.5
DIN rail
6.1
Terminal screw
M3
5
Terminal
screw M3
(8)
(30)
Hole for screw
mounting
At mounting to the DIN rail
Main unit (at attach/detach)
Dimensions for screw mounting
Notice at the installation
Please keep the distance of 30mm from this instrument to radiate.
[50mm is recommended]
30 or more
88.5±0.2
(3)
(100)
30 or more
2-M3
(30)
9±0.2
Locking tab
30 +0.7
+0.2
3
PUMCL
Terminal connection diagram
Loader interface plug (RS-232C)
3 TX
2 RX
1 GND
φ2.5 3-pole miniature plug
STATION No. LOADER
×10
×1
DA
DB
CC-Link
DG
21
22
23
SLD 24
25
FG
21
11
22
12
23
13
24
14
25
15
26
16
Terminating
resistor of
internal
communication
11
12
13
14
15
Don’t
connect
16
26
Don’t
connect
17
27
27
17
28
28
18
19
29
19
20
30
20
29
18
30
Base part
Power
3
2
4
1
2
-
+
1
DC24V
5
3
4
5
Don’t connect
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan