FUJI EDS11-156A

FFI SYSTEM
MASTER STATION
DATA SHEET
PNT···3
This instrument controls signal exchange with FFI system field instruments, and transmits process values and
alarm signals in the field instruments to the host system.
It can support a maximum of 8 field instruments, uses
RS-232C or Ethernet communication for transmission to the
host side and has functions for duplex configuration to secure redundancy.
FEATURES
1. Connection of up to 8 filed instruments
A single master station can support up to 8 field instruments via an optical star coupler.
2. General-use transmission interface
A host system is connectable via the general-use RS232C or Ethernet interface .
This interface allows a personal computer or a control
device to collect the data of field instrument and set
parameters in the field instrument.
3. System duplicable (with Ethernet)
This station has functions compatible with a duplex system so that system redundancy is ensured.
SPECIFICATIONS
Functional specifications
1. Interface with field instruments
Applicable optical fiber cable:
silica fiber ... core/clad diameter
100/140 µm
Optical connector:
FC connector
Transmission distance:
1.5 km max.
(between field instruments and master
station)
Number of connectable field instruments:
Max. 8 instruments via an optical star
coupler
Transmission cycle:
0.2 sec (transmission with each field instrument at intervals of 0.2 sec)
2. Interface with host system
(1) RS-232C
Transmission method:
Polling/selecting method
Code format:
Binary format
Transmission speed:
9600 bps
Synchronous system:
Start-stop synchronization
Communication interval:
1 sec or longer
Transmission distance:
15 m or less
(2) Ethernet
Protocol:
TCP/IP, UDP/IP
Transmission specification:
10BASE-T
Code format:
Manchester code
Transmission speed:
10 Mbps
Communication interval:
200 ms or longer
3. Indicating function (LED lights up on instrument front)
POWER:
LINK/ACT:
FLT/ALM:
BATT:
OPR:
Lights up when power supply is turned
on.
Lights up in Ethernet communication.
Lights up when an error occurs.
Lights up when a battery alarm occurs in
field instrument.
Lights up in the operating status.
4. Duplexing function (available in Ethernet specification)
Using two master stations, the optical star coupler and
host system can be connected in two lines for duplex
configuration. If the primary master station become faulty
or the primary line is disconnected in the duplex configuration, the standby line can be activated owing to system redundancy.
In the duplex configuration, communication with field instruments starts on reception of a working command from
the host system.
EDS11-156a
Date
Apr. 1, 2011
PNT···3
5. Operating conditions
Power supply: 100V AC, 50/60 Hz
Power consumption:
Approx. 10 VA
Ambient temperature:
0 to +50°C
Storage temperature:
-10 to +60°C
Ambient humidity:
90% RH or less
Physical specifications
Enclosure:
Indoor type
Case material: Polycarbonate
Mounting method:
Rack mounting
Mass:
Approx. 0.6 kg
Power supply and ground connection:
Via front panel screw terminals (M4)
RS-232C connection:
Front panel connector (D-SUB 9 pins)
Ethernet connection:
Front panel connector (modular connector of 8 poles)
CODE SYMBOLS
1 2 3 4 5 6 7 8
PNT
0003
1
2
3
Description
Transmission and duplexing functions
Ethernet without duplexing
Ethernet with duplexing
RS-232C (without duplexing)
SCOPE OF DELIVERY
Master station (including fixture)
RELATED DEVICES
• Field instruments (pressure/differential pressure transmitters, temperature transmitter, etc.)
• Optical star coupler ... EDS8-48
• Hand-held communicator ... EDS8-44
ORDERING INFORMATION
1. Part name
2. Model type
3. IP address in Ethernet specification (shown below)
10.55.136.01
These digits need to be specified in hexadecimal notation (allowed within 01 to FF).
2
SYSTEM BLOCK DIAGRAM
Without duplex configuration
Host system
RS-232C or Ethernet
Master station
Control room
Field
Optical star coupler
Field equipment
max. 8 units
Duplex system
(available with Ethernet)
Host system
Ethernet
Master station
Control room
Field
Optical star coupler
Field equipment
max. 8 units
3
PNT···3
OUTLINE DIAGRAM
(Unit : mm)
Space for connector
2 φ 4.7 mounting holes
49
Min. 100
6.5
132
30
1.6
POWER
LINK/ACT
Receptacle
for optical connector
FLT/ALM
BATT.
OPR
Connector
for RS-232C
130
160
170
OPT.
E
AC
100
Terminal block (M4 screw)
Fixture
In RS-232C specification
POWER
LINK/ACT
FLT/ALM
BATT.
OPR
OPT.
Connector
for Ethernet
Ethernet
E
AC
100
In Ethernet specification
Caution on Safety
*Before using this product, be sure to read its instruction manual in advance.
International Sales Div
Sales Group
Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome,
Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fujielectric.com
Phone: 81-3-5435-7280, 7281 Fax: 81-3-5435-7425
http://www.fjielectric.com/products/instruments/
Information in this catalog is subject to change without notice.
Printed in Japan