ETC G3PB-215B-3-VD

Solid-state Contactor and Relay
G3PB
Single-phase and Three-phase
SSRs Ideal for Frequent Switching
Applications Under Heater Load
Slim models available for single-phase
and three-phase output
Lower cost based on new modular
construction
Optimum heat sinks attach to models
without built-in heat sinks
Models for 15 to 45 A are available
DIN-rail mounting possible (when using
the Y92B-P50) in addition to screw
mounting
Conforms to UL, CSA, and CE
This product was manufactured at OMRON Takeo. OMRON Takeo has obtained approvals from
international certification bodies for its quality system and environmental control system.
Ordering Information
CONTACTORS WITH BUILT-IN HEAT SINKS
Number of
phases
Number of
elements
Zero-cross
function
Main circuit voltage
Applicable heater capacity
(with Class-1 AC resistive
load)
Part number
3
3
Yes
100 to 240 VAC
5.1 kW max. (15
( A))
G3PB-215B-3-VD
2
3
G3PB-215B-2-VD
8.6 kW max. (25
( A))
2
3
G3PB-225B-2-VD
12.1 kW max. (35
( A))
2
3
G3PB-225B-3-VD
G3PB-235B-3-VD
G3PB-235B-2-VD
15.5 kW max. (45
( A))
2
G3PB-245B-3-VD
G3PB-245B-2-VD
(This table continues on the next page.)
G3PB
G3PB
Ordering Information -- continued from previous page
Number of
phases
Number of
elements
Zero-cross
function
Main circuit voltage
Applicable heater capacity
(with Class-1 AC resistive
load)
Part number
3
3
Yes
200 to 400 VAC
10.3 kW max. (15
( A))
G3PB-415B-3-VD
2
G3PB-415B-2-VD
17.3 kW max. (25
( A))
3
2
G3PB-425B-3-VD
G3PB-425B-2-VD
24.2 kW max. (35
( A))
3
2
G3PB-435B-3-VD
G3PB-435B-2-VD
31.1 kW max. (45
( A))
3
2
G3PB-445B-3-VD
G3PB-445B-2-VD
CONTACTORS WITHOUT BUILT-IN HEAT SINKS
Number of
phases
Number of
elements
Zero-cross
function
Main circuit voltage
Rated carry current
Part number
3
3
Yes
100 to 240 VAC
15 A max.
G3PB-215B-3H-VD
2
G3PB-215B-2H-VD
25 A max.
3
2
G3PB-225B-3H-VD
G3PB-225B-2H-VD
35 A max.
3
2
G3PB-235B-3H-VD
G3PB-235B-2H-VD
45 A max.
3
2
G3PB-245B-3H-VD
G3PB-245B-2H-VD
200 to 400 VAC
3
15 A max.
2
G3PB-415B-3H-VD
G3PB-415B-2H-VD
25 A max.
3
2
G3PB-425B-3H-VD
G3PB-425B-2H-VD
35 A max.
3
2
G3PB-435B-3H-VD
G3PB-435B-2H-VD
45 A max.
3
2
G3PB-445B-3H-VD
G3PB-445B-2H-VD
Note: The load current vs. ambient temperature characteristics of the Unit vary with the heat radiation of the Unit. Refer to Engineering
Data for details.
SINGLE-PHASE SOLID-STATE RELAYS
No. of phases
Zero-cross
function
Main circuit voltage
Applicable heater capacity
(resistive load: Class-1 AC)
Part number
Single-phase
g
Yes
100 to 240 VAC
3.6 kW max. (15 A)
G3PB-215B-VD
6 kW max. (25 A)
G3PB-225B-VD
8.4 kW max. (35 A)
G3PB-235B-VD
10.8 kW max. (45 A)
G3PB-245B-VD
HEAT SINKS
Heat resistance (°C/W)
Part number
1.67
Y92B-P50
1.01
Y92B-P100
0.63
Y92B-P150
0.43
Y92B-P200
0.36
Y92B-P250
G3PB
G3PB
ACCESSORIES (ORDER SEPARATELY)
Mounting
g rail
50 cm (1) x 7.3 mm (t)
PFP-50N
1 m (1) x 7.3 mm (t)
PFP-100N
1 m (1) x 16 mm (t)
PFP-100N2
Specifications for Contactors
RATINGS (AT AN AMBIENT TEMPERATURE OF 25°C)
Operating Circuit (Common)
Item
Common
Rated operating voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
10 mA max. (at 24 VDC)
Must-operate voltage
9.6 VDC max.
Reset voltage
1 VDC min.
Insulation method
Phototriac
Operation indicator
Yellow LED
MAIN CIRCUIT OF MODELS WITH BUILT-IN HEAT SINKS
Item
G3PB215B-3-VD
G3PB215B-2-VD
G3PB225B-3-VD
G3PB225B-2-VD
Rated voltage
100 to 240 VAC
Operating voltage range
75 to 264 VAC
Rated carry current
15 A
Minimum load current
0.2 A
Inrush current
resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s
260 A2s
1,260 A2s
Applicable load
(with Class-1 AC
resistive load)
5.1 kW max.
8.6 kW
12.1 kW max.
Item
G3PB415B-3-VD
Rated voltage
200 to 400 VAC
Operating voltage range
180 to 440 VAC
Rated carry current
(See Note.)
15 A
Minimum load current
0.5 A
Inrush current
resistance (peak value)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
1,260 A2s
Applicable load
(with Class-1 AC
resistive load)
10.3 kW max.
25 A
G3PB235B-3-VD
G3PB235B-2-VD
35 A
G3PB245B-3-VD
G3PB245B-2-VD
45 A
0.5 A
G3PB415B-2-VD
G3PB425B-3-VD
G3PB425B-2-VD
25 A
17.3 kW max.
G3PB435B-3-VD
15.5 kW max.
G3PB435B-2-VD
35 A
24.2 kW max.
G3PB445B-3-VD
G3PB445B-2-VD
45 A
31.1 kW max.
Note: Rated carry current varies depending on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in
Engineering Data.
G3PB
G3PB
MAIN CIRCUIT OF MODELS WITHOUT BUILT-IN HEAT SINKS
Item
G3PB-215B3H-VD
G3PB-215B2H-VD
G3PB-225B3H-VD
G3PB-225B2H-VD
Rated voltage
100 to 240 VAC
Operating voltage range
75 to 264 VAC
Rated carry current
(See Note.)
15 A
Minimum load current
0.2 A
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s
260 A2s
1,260 A2s
Applicable load
(with Class-1 AC resistive
load)
The applicable load varies with the heat radiation of the Unit. Refer to Engineering Data for details.
Item
G3PB-415B3H-VD
Rated voltage
200 to 400 VAC
Operating voltage range
180 to 440 VAC
Rated carry current
15 A
Minimum load current
0.5 A
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
1,260 A2s
Applicable load
(with Class-1 AC resistive
load)
Refer to Engineering Data for details.
25 A
G3PB-235B3H-VD
G3PB-235B2H-VD
35 A
G3PB-245B3H-VD
G3PB-245B2H-VD
45 A
0.5 A
G3PB-415B2H-VD
G3PB-425B3H-VD
25 A
G3PB-425B2H-VD
G3PB-435B3H-VD
G3PB-435B2H-VD
35 A
G3PB-445B3H-VD
G3PB-445B2H-VD
45 A
Note: The rated carry current varies depending on the radiation device or radiation plate to be connected and the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data.
G3PB
G3PB
CHARACTERISTICS
Models with Built-in Heat Sinks
Item
G3PB215B-3-VD
G3PB215B-2-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current (See
Note.)
10 mA (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude
Shock resistance
Destruction: 294 m/s2 (30G)
Malfunction: 147 m/s2 (15G)
Ambient
t
temperature
t
Operating
--30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage
--30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient
humidity
Operating 45% to 85%
Approx.
750 g
G3PB225B-3-VD
Approx.
900 g
G3PB225B-2-VD
Weight
Approx.
750 g
Approx.
750 g
Approved standards
(under application)
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
EMC
Emission
Emission
Immunity
AC mains
Electromagnetic
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
G3PB235B-3-VD
Approx.
1,150 g
G3PB235B-2-VD
Approx.
900 g
G3PB245B-3-VD
G3PB245B-2-VD
Approx.
1,500 g
Approx.
1,150 g
G3PB445B-3-VD
G3PB445B-2-VD
Approx.
1,500 g
Approx.
1,150 g
EN55011 Group 1 Class B
EN55011 Group 1 Class B
IEC947-4-3
4 kV contact discharge
8 kV air discharge
IEC947-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3
2 kV AC power-signal line
IEC947-4-3
2 kV
IEC947-4-3
10 V (0.15 to 80 MHz)
Note: The leakage current of phase S will be approximately √3 times larger if the 2-element model is applied.
Item
G3PB415B-3-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current (See
Note.)
20 mA (at 400 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude
Shock resistance
Destruction: 294 m/s2 (30G)
Malfunction: 147 m/s2 (15G)
Ambient
t
temperature
t
Operating
--30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage
--30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient
humidity
Operating 45% to 85%
G3PB415B-2-VD
Approx.
750 g
G3PB425B-3-VD
Approx.
900 g
G3PB425B-2-VD
Weight
Approx.
750 g
Approx.
750 g
Approved standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
(This table continues on the next page.)
G3PB435B-3-VD
Approx.
1,150 g
G3PB435B-2-VD
Approx.
900 g
G3PB
G3PB
Characteristics Table -- continued from previous page
Item
G3PB415B-3-VD
G3PB415B-2-VD
G3PB425B-3-VD
EMC
Emission
Emission
Immunity
AC mains
Electromagnetic
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
G3PB425B-2-VD
G3PB435B-3-VD
G3PB435B-2-VD
G3PB445B-3-VD
G3PB445B-2-VD
G3PB245B3H-VD
G3PB245B2H-VD
EN55011 Group 1 Class B
EN55011 Group 1 Class B
IEC947-4-3
4 kV contact discharge
8 kV air discharge
IEC947-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3
2 kV AC power-signal line
IEC947-4-3
2 kV
IEC947-4-3
10 V (0.15 to 80 MHz)
Note: The leakage current of phase S will be approximately √3 times larger if the 2-element model is applied.
Models without Built-in Heat Sinks
Item
G3PB215B3H-VD
G3PB215B2H-VD
G3PB225B3H-VD
G3PB225B2H-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
(See Note.)
10 mA (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction and malfunction: 10 to 55 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 294 m/s2 (30G)
Malfunction: 147 m/s2 (15G)
Ambient
t
temperature
t
Operating
--30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage
--30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient
humidity
Operating 45% to 85%
Approved standards
(under application)
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
Weight (Max.)
300 g max.
EMC
Emission
Emission
Immunity
AC mains
Electromagnetic
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
G3PB235B3H-VD
G3PB235B2H-VD
EN55011 Group 1 Class B
EN55011 Group 1 Class B
IEC947-4-3
4 kV contact discharge
8 kV air discharge
IEC947-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3
2 kV AC power-signal line
IEC947-4-3
2 kV
IEC947-4-3
10 V (0.15 to 80 MHz)
Note: The leakage current of phase S will be approximately √3 times larger if the 2-element model is applied.
G3PB
G3PB
Models without Built-in Heat Sinks
Item
G3PB415B3H-VD
G3PB415B2H-VD
G3PB425B3H-VD
G3PB425B2H-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
(See Note.)
20 mA (at 400 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction and malfunction: 10 to 55 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 294 m/s2 (30G)
Malfunction: 147 m/s2 (15G)
Ambient
t
temperature
t
Operating
--30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage
--30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient
humidity
Operating 45% to 85%
Approved standards
(under application)
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3)
Weight
Approx. 300 g
EMC
Emission
Emission
Immunity
AC mains
Electromagnetic
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
G3PB435B3H-VD
G3PB435B2H-VD
EN55011 Group 1 Class B
EN55011 Group 1 Class B
IEC947-4-3
4 kV contact discharge
8 kV air discharge
IEC947-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3
2 kV AC power-signal line
IEC947-4-3
2 kV
IEC947-4-3
10 V (0.15 to 80 MHz)
Note: The leakage current of phase S will be approximately √3 times larger if the 2-element model is applied.
Heat Sinks
Model
Weight
Y92B-P50
Approx. 450 g
Y92B-P100
Approx. 450 g
Y92B-P150
Approx. 600 g
Y92B-P200
Approx. 850 g
Y92B-P250
Approx. 1,200 g
G3PB445B3H-VD
G3PB445B2H-VD
G3PB
G3PB
Specifications for Single Phase Solid State Relays
RATINGS (AT AN AMBIENT TEMPERATURE OF 25°C)
Operating Circuit (Common)
Item
Common
Rated operating voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
7 mA max.
Must-operate voltage
9.6 VDC max.
Reset voltage
1 VDC min.
Insulation method
Phototriac
Operation indicator
Yellow LED
MAIN CIRCUIT OF MODELS WITH BUILT-IN HEAT SINKS
Item
G3PB-215B-VD
Rated voltage
100 to 240 VAC
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Operating voltage range
75 to 264 VAC
Rated carry current
15 A
Minimum load current
0.2 A
25 A
35 A
45 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s
260 A2s
1,260 A2s
Applicable load
(with Class-1 AC resistive load)
3.6 kW max.
6 kW max.
8.4 kW max.
10.8 kW max.
Item
G3PB-215B-VD
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
10 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude
Shock resistance
Destruction: 294 m/s2 (30G)
Malfunction: 147 m/s2 (15G)
0.5 A
CHARACTERISTICS
20 mA max. (at 200 VAC)
Ambient
t
temperature
t
Operating
--30°C to 80°C (--22°F to 176°F) with no icing or condensation
Storage
--30°C to 100°C (--22°F to 212°F) with no icing or condensation
Ambient humidity
Operating
45% to 85%
Approved standards (under
application)
UL508, CSA22.2 No. 14, IEC947-4-3
Weight
Approx. 240 g
Approx. 240 g
Approx. 400 g
Approx. 400 g
G3PB
G3PB
Engineering Data
LOAD CURRENT VS. AMBIENT TEMPERATURE (CONTINUOUS INPUT)
Models with Built-in Heat Sinks
Three-phase Models
G3PB-225B-3-VD
G3PB-225B-2-VD
G3PB-425B-3-VD
G3PB-425B-2-VD
G3PB-225B-3-VD
G3PB-225B-2-VD
G3PB-425B-3-VD
G3PB-425B-2-VD
G3PB-215B-3-VD
G3PB-215B-2-VD
G3PB-415B-3-VD
G3PB-415B-2-VD
G3PB-235B-3-VD
G3PB-235B-2-VD
G3PB-435B-3-VD
G3PB-435B-2-VD
Load current (A)
Load current (A)
G3PB-215B-3-VD
G3PB-215B-2-VD
G3PB-415B-3-VD
G3PB-415B-2-VD
Ambient temperature (C)
G3PB-245B-3-VD
G3PB-245B-2-VD
G3PB-445B-3-VD
G3PB-445B-2-VD
G3PB-245B-3-VD
G3PB-245B-2-VD
G3PB-445B-3-VD
G3PB-445B-2-VD
G3PB-235B-3-VD
G3PB-235B-2-VD
G3PB-435B-3-VD
G3PB-435B-2-VD
Ambient temperature (C)
Single-phase Models
G3PB-215B-VD
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
G3PB-245B-VD
G3PB-215B-VD
Ambient temperature (C)
Load current (A)
Load current (A)
G3PB-225B-VD
G3PB-235B-VD
Ambient temperature (C)
G3PB
G3PB
Models without Built-in Heat Sinks
G3PB-225B-3H (-2H)-VD
G3PB-425B-3H (-2H)-VD
G3PB-215B-3H (-2H)-VD
G3PB-415B-3H (-2H)-VD
G3PB-235B-3H (-2H)-VD
G3PB-245B-3H (-2H)-VD
G3PB-435B-3H (-2H)-VD
G3PB-445B-3H (-2H)-VD
G3PB-235B-3H (-2H)-VD
G3PB-245B-3H (-2H)-VD
G3PB-435B-3H (-2H)-VD
G3PB-445B-3H (-2H)-VD
Load current (A)
Load current (A)
G3PB-215B-3H (-2H)-VD
G3PB-225B-3H (-2H)-VD
G3PB-415B-3H (-2H)-VD
G3PB-425B-3H (-2H)-VD
Ambient temperature (C)
Ambient temperature (C)
INRUSH CURRENT RESISTANCE: NON-REPETITIVE (LESS THAN HALF FOR REPETITIVE)
G3PB-215B-3 (H)-VD
G3PB-215B-2 (H)-VD
G3PB-225B-3 (H)-VD
G3PB-225B-2 (H)-VD
G3PB-415B-3 (H)-VD
G3PB-415B-2 (H)-VD
Inrush current
Inrush current
Three-phase Models
Energized time (ms)
G3PB-245B-3 (H)-VD
G3PB-245B-2 (H)-VD
G3PB-445B-3 (H)-VD
G3PB-445B-2 (H)-VD
Inrush current
G3PB-235B-3 (H)-VD
G3PB-235B-2 (H)-VD
G3PB-245B-3 (H)-VD
G3PB-245B-2 (H)-VD
Energized time (ms)
Energized time (ms)
G3PB
G3PB
G3PB-215B-VD
G3PB-225B-VD
Inrush current
Inrush current
Single-phase Models
Energized time (ms)
Energized time (ms)
Inrush current
G3PB-235B-VD
G3PB-245B-VD
Energized time (ms)
HEAT SINK SIZE VS. LOAD CURRENT
Three-phase Models
Heat sink size (cm2 )
Ambient temperature: 80°C
Ambient temperature: 40°C
Aluminum plate (t=3.0 mm)
Load current (A)
Heat sink size (cm2 )
G3PB-425B-3H-VD
G3PB-225B-3H-VD
Ambient temperature: 80°C
Ambient temperature: 40°C
Aluminum plate (t=3.0 mm)
Load current (A)
Note: The heat sink size refers to the combined area of the sides of the heat sink that radiate heat. In the case of G3PB-425B-3H-VD,
when a current of 18 A is allowed to flow through the SSR at 40°C, the graph shows that the heat sink size is about 2,500 cm2.
Therefore, if the heat sink is square, one side of the heat sink must be 36 cm (362 × 2 = 2,592) or longer.
G3PB
G3PB
INPUT VOLTAGE VS. INPUT CURRENT AND INPUT VOLTAGE VS. INPUT IMPEDANCE
Input impedance (kΩ )
Input current (mA)
Three-phase Models
Input current
Input impedance
Input voltage (V)
Input impedance (kΩ )
Input current (mA)
Single-phase Models
Input current
Input impedance
Input voltage (V)
THERMAL RESISTANCE RTH (JUNCTION/SSR BACK SURFACE)
Three-phase Models without Heat Sink
Model
Rth (°C/W)
G3PB-215B-3H-VD
1.05
G3PB-225B-3H-VD
0.57
G3PB-235B-3H-VD
0.57
G3PB-245B-3H-VD
0.57
G3PB
G3PB
Dimensions
Unit: mm (inch)
MODELS WITH BUILT-IN HEAT SINKS
Three-phase Models
G3PB-215B-2-VD
G3PB-415B-2-VD
Without Terminal Cover
With Terminal Cover
4.6 dia.
(1.97)
24 (0.94)
80.5
max.
Two, M3.5
100 max.
(3.94)
Six, M4
80 max.
(3.15)
Elliptical hole: 4.6 x 5.6
(1.27)
30.5 max.
(1.20)
Two, 4.5 dia or M4
Terminal Arrangement/
Internal Circuit Diagram
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Input circuit
55 max.
(2.17)
Without Terminal Cover
With Terminal Cover
Four, R2.5
50.5
max.
24 (0.94)
Two, M3.5
80.5 max.
(3.17)
80 max.
Terminal Arrangement/
Internal Circuit Diagram
Six, M4
110.5 max.
(4.35)
(1.27)
B-3-VD
G3PBL1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Mounting Holes
30.5 max.
(1.20)
70 max.
(2.76)
Input circuit
Four, 4.5 dia or M4
B-2-VD
G3PBL1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Input circuit
G3PB-215B-3-VD
G3PB-225B-2-VD
G3PB-415B-3-VD
G3PB-425B-2-VD
G3PB
G3PB
G3PB-225B-3-VD
G3PB-235B-2-VD
G3PB-425B-3-VD
G3PB-435B-2-VD
Without Terminal Cover
With Terminal Cover
Four, R2.5
80.5
max.
24 (0.94)
110.5 max.
(4.35)
Two, M3.5
(1.27)
80 max.
Terminal Arrangement/
Internal Circuit Diagram
110.5 max.
(4.35)
Mounting Holes
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Input circuit
Six, M5
(G3PB- 35B-2-VD)
Six, M4
(G3PB- 25B-3-VD)
30.5 max.
(1.20)
Four, 4.5 dia or M4
Input circuit
70 max.
(2.76)
Without Terminal Cover
With Terminal Cover
Four, R2.5
130.5 max.
80.5
max. 90 (5.14)
24
(0.94)
Two, M3.5
Six, M5
80 max.
Terminal Arrangement/
Internal Circuit Diagram
130.5 max.
(5.14)
(1.27)
B-3-VD
G3PBMounting Holes
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
30.5 max.
(1.20)
Input circuit
Four, 4.5 dia or M4
70 max.
(2.76)
B-2-VD
G3PBL1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Input circuit
G3PB-235B-3-VD
G3PB-245B-2-VD
G3PB-435B-3-VD
G3PB-445B-3-VD
G3PB
G3PB
G3PB-245B-3-VD
G3PB-445B-3-VD
Without Terminal Cover
With Terminal Cover
Four, R2.5
24
(0.94)
80.5
max.
190.5 max.
(7.50)
Two, M3.5
Six, M5
80 max.
130.5 max.
(5.14)
(1.27)
Mounting Holes
30.5 max.
(1.20)
Four, 4.5 dia or M4
Terminal Arrangement/
Internal Circuit Diagram
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
Input circuit
70 max.
(2.76)
Single-phase Models
G3PB-215B-VD
G3PB-225B-VD
4.6 dia.
Two, M4
80
68
24 (0.94)
100 max.900.2
(3.94)
Two, M3.5
4.2
(0.17)
6.3
(0.25)
Elliptical hole: 4.6 x 5.6
4.5
(0.18)
11
22.5 max.
(0.89)
Mounting Holes
Terminal Arrangement/
Internal Circuit Diagram
Two, 4.5 dia. or M4
110.3
Input circuit
900.3
88.6
(3.49)
Trigger circuit
100 max.
(3.94) 83.2
G3PB
G3PB
G3PB-235B-VD
G3PB-245B-VD
4.6 dia.
Two, M5
80
68
(2.68)
24 (0.94)
100 max. 900.2
(3.94)
Two, M3.5
13.4
(0.53)
6.1
(0.24)
4.5
(0.18)
25
Elliptical hole: 4.6 x 5.6
44.5 max.
(1.75)
Mounting Holes
Two, 4.5 dia. or M4
Terminal Arrangement/
Internal Circuit Diagram
100 max.
(3.94)
83.2
88.6
(3.49)
(3.49)
Input circuit
Trigger circuit
90
25
MODELS WITHOUT BUILT-IN HEAT SINKS
G3PB-235B-3H-VD
G3PB-235B-2H-VD
G3PB-245B-3H-VD
G3PB-245B-2H-VD
G3PB-415B-3H-VD
G3PB-415B-2H-VD
G3PB-425B-3H-VD
G3PB-425B-2H-VD
Four, 8 dia.
G3PB-435B-3H-VD
G3PB-435B-2H-VD
G3PB-445B-3H-VD
G3PB-445B-2H-VD
Four, 4.5 dia.
6
(0.24)
8
(0.31)
4
(0.16)
80.5 max.
(3.17)
24 (0.94)
Terminal Arrangement/
Internal Circuit Diagram
B-3H-VD
G3PBTwo, M3.5
L1/R
L2/S
L3/T
T1/U
T2/V
T3/W
80 max.
(3.15)
Six, M4
(G3PB- 15B H-VD/- 25B- H-VD)
Six, M5
(G3PB- 35B- H-VD/- 45B- H-VD)
Input circuit
68
(2.68)
Mounting Holes
Four, 4.5 dia or M4
30.5 max.
(1.20)
B-2H-VD
G3PBL1/R
L2/S
L3/T
Input circuit
G3PB-215B-3H-VD
G3PB-215B-2H-VD
G3PB-225B-3H-VD
G3PB-225B-2H-VD
T1/U
T2/V
T3/W
G3PB
G3PB
HEAT SINKS
Y92B-P100
Y92B-P50
Mounting Holes
Four, M4
100
Two, 4.5 dia. or M4
4.6 dia.
60 80.5 max.
(3.17)
68
(2.68)
80.5
90 100 max.
max.
(3.94)
68
(2.68)
90
Four, R2.5
Elliptical
hole:
4.6 x 5.6
80 max.
(3.15)
68
110.5 max.
(4.35)
50
70 max.
(2.76)
55 max.
(2.17)
Mounting Holes
Four, 4.5 dia. or M4
60
100
G3PB
G3PB
Y92B-P150
Y92B-P200
120
(4.72)
120
(4.72)
Four, M4
100
(3.94)
Y92B-P250
Four, M4
Four, M4
110.5 max.
(4.35)
68
(2.68)
68
(2.68)
130.5 max.
(5.14)
190.5 max.
(7.50)
68
(2.68)
Four,
R2.5
Four, R2.5
110.5 max.
(4.35)
130.5 max.
(5.14)
Four, R2.5
130.5 max.
(5.14)
70 max.
(2.76)
Mounting Holes
70 max.
(2.76)
70 max.
(2.76)
Mounting Holes
Four, 4.5 dia. or M4
Mounting Holes
Four, 4.5 dia. or M4
Four, 4.5 dia. or M4
ACCESSORIES (ORDER SEPARATELY)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
4.5
4.5
35±0.3
15 25
25
25
10
10 25 1,000 (500)
(See Note.)
15 (5)
(See Note.)
Note: Values in parentheses indicate dimensions
for the PFP-50N.
16
Twenty-eight, 25x4.5 elliptic holes
7.3±0.15
35±0.3 27
27±0.15
15
25
10
25
1,000
25 10 25
15
24
1
29.2
1.5
G3PB
G3PB
Precautions
WARNING
!
Caution
Do not apply excessive voltage or current to the input or output
circuit of the G3PB, or the G3PB may malfunction or burn.
Do not use the G3PB unless all the output terminal screws are
tightened securely, or the terminals may generate excessive
heat, and the G3PB may burn.
Be sure to provide enough ventilation to the G3PB and the radiator, or the G3PB may generate excessive heat, and the
G3PB may burn or the output element may short-circuit.
Be sure to turn OFF the power supply to the G3PB before wiring, or an electric shock may be received.
Be sure to wire or solder the terminals of the G3PB properly, or
the G3PB may generate excessive heat and burn.
If the G3PB is mounted directly to a control panel that is used
as a radiator as well, the control panel must be made of aluminum or a steel plate with low thermal resistance.
Do not use any material with high thermal resistance, such as
a wooden plate, or the G3PB may catch on fire or burn.
CORRECT USE
Before Actual Operation
•
•
To avoid accidents, it is necessary to test the G3PB in operation under a variety of conditions. As for the characteristics of
the G3PB, it is necessary to take into consideration the dispersion of the characteristics between G3PB Units.
The ratings in this datasheet are tested values in a temperature range between 15°C and 30°C, a relative humidity range
between 25% and 85%, and an atmospheric pressure range
between 88 and 106 kPa. It will be necessary to provide the
above conditions, as well as the load conditions, if the user
wants to confirm the ratings of actual G3PB Units.
Mounting Method
Since the Relay is heavy, firmly mount the DIN rail and fix both
ends with End Plates for DIN-rail-mounting models.
For direct mounting, firmly mount the Relay on the panel.
Vertical Mounting
Vertical mounting
!
To avoid electric shock, do not touch the terminals (i.e.,
charged parts) of the G3PB while power is supplied.
If the G3PB is provided with a terminal cover, be sure to attach
the terminal cover to the G3PB before operating the G3PB.
The G3PB and radiator are very hot while power is supplied to
the G3PB.
Do not touch the G3PB or the radiator while power is supplied
to the G3PB or immediately after the G3PB is turned OFF, or a
burn may result.
Do not touch the load terminal of the G3PB immediately after
the G3PB is turned OFF, otherwise an electric shock may be
received due to the residual charge of the built-in snubber
circuit.
To avoid electric shock, be sure to turn OFF the power supply
to the G3PB before wiring.
Mount the terminal cover to the G3PB after wiring.
Do not touch the terminals of the G3PB while power is supplied, or an electric shock may be received.
The built-in capacitor will be charged as long as power is supplied. To avoid electric shock, do not touch the terminals of the
G3PB unless the G3PB is turned OFF and the built-in capacitor discharges all of its residual voltage.
Panel
Horizontal Mounting
Panel
Note: Make sure that the load current is 50% of the rated load
current when the G3PB is mounted horizontally.
G3PB
G3PB
Close Mounting
Tightening Torque
Refer to the following and be sure to tighten each screw of the
Unit to the specified torque in order to prevent the Unit from
malfunctioning.
60 mm
Item
Screw terminal
diameter
Tightening torque
Input terminal
M3.5
0.8 N m (7.84 kgf cm)
Output
t
terminal
i l
M4
1.2 N m (11.8 kgf cm)
M5
2.0 N m (19.6 kgf cm)
Mounting Models without Built-in Heat Sink
•
•
30 mm
Note: Be sure to provide a minimum space of 30 mm horizontally and 60 mm vertically between adjacent Units.
Wiring
•
When using crimp terminals, refer to the terminal clearances
shown below.
•
Before attaching an external radiator or Heat Sink to the Unit,
be sure to apply silicone grease for heat radiation, such as
Toshiba’s YG6260 or Sinetsu Silicone’s G746, to the surface
where the radiator or Heat Sink is attached.
Be sure to apply the following torque to secure the Unit and
external radiator or Heat Sink for proper heat radiation.
Tightening torque: 2.0 N m (19.6 kgf cm)
OPERATING CONDITIONS
•
•
Output terminal section
Do not apply current exceeding the rated current, or the temperature of the Unit may rise excessively.
Be sure to prevent ambient temperature rising due to the
heat radiation of the Unit. In the case of enclosed mounting,
install a fan so that the interior of the panel can be fully
ventilated.
OPERATING AND STORAGE
ENVIRONMENTS
Input terminal section
Do not use or store the Unit in the following places, to avoid
malfunction or deterioration of operating characteristics.
•
•
•
•
•
•
•
•
•
Be sure that all lead wires are thick enough according to the
current.
Output terminals T1, T2, and T3 are charged regardless of
whether the Unit is a 2- or 3-element model that is turned on
or off. Do not touch these terminals, otherwise an electric
shock may be received.
To isolate the Unit from the power supply, install an appropriate circuit breaker between the power supply and Unit.
Be sure to turn off the power supply before wiring the Unit.
Terminal L2 and terminal T2 of the 2-element model are internally short-circuited to each other. Therefore, connect terminal L2 to the ground terminal of the power supply. If terminal
L2 is connected to a terminal other than the ground terminal,
cover all the charged terminals, such as heater terminals, for
the prevention of electric shock accidents and ground faults.
•
•
•
•
•
Locations subject to direct sunlight.
Locations subject to ambient operating temperatures outside
the range of --30°C to 80°C.
Locations subject to ambient operating humidity outside the
range of 45% to 85%.
Locations subject to condensation as the result of severe
changes in temperature.
Locations subject to ambient storage temperatures outside
the range of --30°C to 100°C.
Locations subject to corrosive or flammable gases.
Locations subject to dust (especially iron dust) or salts.
Locations subject to shock or vibration.
Locations subject to exposure to water, oil, or chemicals.
G3PB
G3PB
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GCTC12
1/99
Specifications subject to change without notice.
Printed in U.S.A.