OMRON H3DKFACDC24240

New Product News
Solid-state Timers
H3DK
DIN Track-mounted, 22.5-mm-width
Standard Timer Series
LR
• A wide AC/DC power supply range (24 to 240 VAC/DC).*1
• All sub-series include models with 12-VDC power supply.*1
• G-type Models (H3DK-G) now include model with 240 to 440VAC power supply.
• UL*2, CSA*3, and CCC certification and EN 61812-1 compliance.
CE Marking.
• EMC (EN 61812-1) compliance for application in heavy industrial, residential, commercial, or light industrial environments.
• Finger-safe terminal block and captive screws according to EN 50274.
*1. Except for the H3DK-H.
*2. Except for the H3DK-GE.
*3. Scheduled to obtain certification in April 2012.
Model Number Structure
■ The Entire H3DK Series
H3DK Series
H3DK-M/-S Multi-range,
Multi-mode Timers
H3DK-F
Twin Timers
Page 2
■ Eight-mode Timer
H3DK-M1/M2
● Operating Modes
A: ON Delay
B: Flicker OFF Start
B2: Flicker ON Start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
■ Four-mode Timer
H3DK-S1/S2
● Operating Modes
A: ON Delay
B2: Flicker ON Start
E: Interval
J: One-shot Output
H3DK-G
Star-delta Timers
Page 11
● Operating Modes
Flicker-OFF Start/
Flicker-ON Start
H3DK-H Power
OFF-delay Timers
Page 15
● Operating Modes
Star-delta Timer
Page 21
● Operating Modes
Power OFF-delay
Timer
■ Model Number Legend (Not all models that can be represented with the model number legend can necessarily be produced.)
H3DK-@@@@
1 2 3 4
1. Type
Symbol
M
S
F
G
H
2. Control Output
Meaning
Eight-mode Timer
Four-mode Timer
Twin Timer
Star-delta Timer
Power OFF-delay Timer
Symbol
1
2
Meaning
SPDT
DPDT
* M- and S-type models only.
3. Supply Voltage
Symbol
Blank
A
B
C *1
D *1
E *1
Meaning
24 to 240 VAC/DC
12 VDC
24 to 48 VAC/DC
100 to 120 VAC
200 to 240 VAC
240 to 440 VAC *2
4. Time Ranges (H-type
Models Only)
Symbol
S
L
Meaning
0.1 to 1.2 s or 1 to 12 s
1 to 12 s or 10 to 120 s
*1 H-type models only.
*2 G-type models only.
1
New Product News
Multi-range, Multi-mode Timer
H3DK-M/H3DK-S
LR
• Multiple time ranges and operating modes let you cover a wide
range of applications.
• The time-limit DPDT output contacts can be changed to time-limit
SPDT and instantaneous SPDT output contacts using a switch.
• Sequence checks are easily performed by setting an instantaneous output to 0.
• Start signal control for the H3DK-M.
Ordering Information
■ List of Models
Supply voltage
Control output
24 to 240 VAC/DC
12 VDC
Eight-mode Timer
Four-mode Timer
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch.
Model
H3DK-M2
H3DK-S2
Contact output, SPDT (time-limit SPDT)
Model
H3DK-M1
H3DK-S1
Contact output, DPDT (time-limit DPDT, or time-limit
SPDT + instantaneous SPDT)
Changed using a switch.
Model
H3DK-M2A
H3DK-S2A
Contact output, SPDT (time-limit SPDT)
Model
H3DK-M1A
H3DK-S1A
■ Accessories (Order Separately)
Item
Specification
Model
50 cm (l) x 7.3 mm (t)
Mounting Track
PFP-50N
1 m (l) x 7.3 mm (t)
PFP-100N
1 m (l) x 16 mm (t)
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
■ Model Structure
Model
H3DK-M2
H3DK-M1
H3DK-S2
H3DK-S1
2
Operating modes
A: ON Delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF Delay
D: Signal OFF Delay
E: Interval
G: Signal ON/OFF Delay
J: One-shot Output
A: ON Delay
B2: Flicker ON start
E: Interval
J: One-shot Output
Terminal block
Input type
Output type
Mounting method
Safety standards
Accessories
Relay, DPDT
Voltage input
9 terminals
Relay, SPDT
Relay, DPDT
--6 terminals
Relay, SPDT
cURus (UL 508
CSA C22.2 No. 14)
DIN Track mounting EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
User label
H3DK-M/H3DK-S
Specifications
■ Time Ranges
Time range setting
Set time range
0.1 s
1s
10 s
1 min
10 min
1h
10 h
100 h
0.1 to 1.2 s
1 to 12 s
10 to 120 s
1 to 12 min
10 to 120 min
1 to 12 h
10 to 120 h
100 to 1,200 h
Scale numbers
12
■ Ratings
Power supply voltage *1
• 24 to 240 VAC/DC, 50/60 Hz *2
• 12 VDC *2
Allowable voltage fluctuation
range
• 24 to 240 VAC/DC: 85% to 110% of rated voltage
• 12 VDC: 90% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
10% of rated voltage
• 24 to 240 VAC/DC
High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC
• 12 VDC
High level: 10.8 to 13.2 VDC, Low level: 0 to 1.2 VDC
Voltage input
Power consumption
H3DK-M2/-S2
*3 H3DK-M1/-S1
H3DK-M2A/-S2A
H3DK-M1A/-S1A
At 240 VAC: 6.6 VA max. *4
At 240 VAC: 4.5 VA max. *4
*1.
*2.
*3.
*4.
*5.
At 12 VDC: 0.9 W max.
At 12 VDC: 0.6 W max.
Control output
Contact output, 5 A at 250 VAC with resistive load (cosφ = 1),
5 A at 30 VDC with resistive load *4, *5
Ambient operating temperature
−20 to 55°C (with no icing)
Storage temperature
−40 to 70°C (with no icing)
Ambient operating humidity
25% to 85%
*6.
When using a 24-VDC power supply voltage, there will
be an inrush current of approximately 0.25 A. Allow for
this inrush current when turning ON and OFF the
power supply to the Timer with device with a solidstate output, such as a sensor.
DC ripple: 20% max.
The power consumption is for mode A after the Timer
times out.
For the H3DK-M@, the maximum power consumption
is given, including the current consumed by the input
circuit.
Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
The control output ratings are for one H3DK operating
alone. If you operate two or more Timers side by side,
refer to Installation Pitch and Output Switching Capacity (Reference Values) on the next page.
125 VDC: 0.15 A max. with resistive load, 125 VDC:
0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference
value)
3
H3DK-M/H3DK-S
■ Characteristics
● Installation Pitch and Output
Switching Capacity (Reference Values)
Setting error
±10% of FS ±0.05 s max.*
Minimum input signal
width
50 ms* (start input)
Influence of voltage
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
Impulse withstand voltage
24 to 240 VAC/VDC: 3 kV between power terminals, 4.5 kV between currentcarrying metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV between power terminals, 1.5 kV between current-carrying metal
parts and exposed non-current-carrying metal parts
Noise immunity
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Vibration
resistance Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Life expectancy
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Malfunction 100 m/s2 3 times each in 6 directions
Electrical
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection
IP30 (Terminal block: IP20)
Weight
Approx. 120 g
■ Applicable standards
EMC
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
(EMI)
Radiated Emissions:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuations and Flicker:
(EMS)
ESD Immunity:
EN61812-1
EN 55011 class B
EN 55011 class B
EN 61000-3-2
EN61000-3-3
EN61812-1
EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:
EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:
EN 61000-4-5: 2 kV common mode,
1 kV differential mode
■ I/O
Item
Model
Input
Start
Output
Control
output
H3DK-M1/-M2
Functions to start timing.
H3DK-S1/-S2
There is no start input.
The output is turned ON/OFF according to the operating mode when the value
that is set on the dial is reached. *
* If the INST/TIME switch on the front of the Timer is set to INST on the H3DK-M2/-S2, relay R2 will
operate as instantaneous contacts and will turn ON/OFF in synchronization with the power supply.
4
80
70
60
d = 50 mm
d = 10 mm
50
d = 5 mm
40
30
d=0 A
20
10
0
1
2
3
4
5
6
Load current (A)
Testing Method
Tested Timer: H3DK-M/-S
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
* With the H3DK-M@, if the voltage exceeds 26.4 VAC/DC in mode C, D, or G, the OFF trigger signal characteristics are as follows:
Accuracy of operating time: ±1% ±50 ms max.
+100 ms
Setting error: ±10% −50 ms
max.
Minimum input signal width: 100 ms
Safety standards
The relation between the installation pitch
and the load current is shown in the following graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the temperature inside the Timer will increase, reducing
the life expectancy of internal parts.
Ambient temperature (°C)
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)*
Maximum ambient operating
temperature in specifications
Accuracy of operating
time
Test
timer
1
DIN Track
Test
timer
2
Test
timer
3
Test
timer
4
Timer installation pitch: d
Test
timer
5
H3DK-M/H3DK-S
Connections
■Block Diagrams
H3DK-M1/-M2
Time setting
detection circuit
AC (DC) input
ROM
Time specification
switches
RAM
Operating mode
switch
Clock
Power supply circuit
Output circuit
One-chip microcomputer
Input circuit
Start input
Indicator circuit
Power
indicator
Output
indicator
H3DK-S1/-S2
AC (DC) input
Time specification
switches
Time setting
detection circuit
ROM
RAM
Power supply circuit
Operating
mode switch
Clock
Output circuit
One-chip microcomputer
Indicator circuit
Power
indicator
Output
indicator
5
H3DK-M/H3DK-S
■ Terminal Arrangement
H3DK-M1
A1
H3DK-M2
15
A1
15
H3DK-S1
25/21
A1
H3DK-S2
15
A1
15
25/21
*
*
R1
R1
R2
R1
R1
R2
15
15
25/21
15
15
25/21
18
16
18
B1
18
16
16 28/24 26/22
28/24 26/22
Start
18
A2
16
B1
18
16
18
28/24 26/22
Start
18
A2
See note 3.
16
18
A2
See note 3.
A1
B1
(DIN notation)
15
A1
B1
15
A1
A2
A2
A2
16 18
A2
See note 3.
(DIN notation)
(21)
25
16
See note 3.
Note 1: The time-limit contact symbol for previous models of Timers was
. The time-limit contact symbol for the H3DK is
used because the H3DK supports multiple operating modes.
Note 2: *The relay R2 can be set to either instantaneous or time-limit contacts using the switch on the front of the Timer.
Note 3: The power supply terminals do not have polarity.
(DIN notation)
16 28/24 26/22
. A different symbol is
(DIN notation)
15
A1
A2
16 18
16 18 26 28
(22) (24)
15
(21)
25
16 18 26 28
(22) (24)
■ Input Connections
The start input of the H3DK-M1/-M2 is a voltage input.
PNP Transistor Input
NPN Transistor Input
Relay Input
Voltage Input Signal Levels
Sensor
24 VDC
Sensor (sensor
power supply)
(+)
24
VDC (−)
24 VDC
(sensor
power supply)
Timer
A1 (+)
B1
Start
A2 (−)
Operates when PNP transistor turns ON.
24
VDC
Timer
Timer
A1 (−)
A1
B1
Start
B1
Start
A2 (+)
A2
(−)
(+)
Operates when NPN transistor turns ON.
Transistor
input
Operates when relay turns ON.
Consider the minimum load
of the relay. (See signal
levels on the right.)
Relay
input
6
1. Transistor ON
• Residual voltage: 1 V max.
Voltage between terminals B1
and A2 must be equal to or
higher than the rated high level
voltage (20.4 VDC min.).
2. Transistor OFF
• Leakage current: 0.01 mA max.
Voltage between terminals B1
and A2 must be equal to or
below the rated low level voltage
(2.4 VDC min.).
Use relays that can adequately
switch 0.1 mA at the imposed
voltage.
When the relay is ON or OFF, the
voltage between terminals B1 and
A2 must be within the following
ranges:
• 24 to 240 VAC/DC
When relay is ON: 20.4 to 264
VAC/DC
When relay is OFF: 0 to 2.4 V
• 12 VDC
When relay is ON: 10.8 to 13.2 V
When relay is OFF: 0 to 1.2 V
H3DK-M/H3DK-S
Nomenclature
H3DK-M2
H3DK-S2
Front View
Bottom View
User label
attachment location
Terminal Block
(See notes 1 and 2.)
Time range switch
Output indicator (orange)
(Lit while Timer gives output.)
Main dial (for
setting the time)
Note 1. Use solid wire (2.5 mm2 max.) or ferrules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
Using Solid Wire
(2.5 mm2 Max.)
Operation/power indicator (green)
(Lit while the power is ON.)
Using Ferrule with
Insulative Sleeve
8 mm max.
Operating mode switch
8 mm max.
Recommended Ferrules
Phoenix Contact
• AI@@@ Series
• AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
INIT/TIME switch for relay R2
(Default setting is for time-limit
output.)*
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
H3DK-M1
H3DK-S1
Front View
User label attachment
location
User label attachment
location
Time range switch*
Time range switch
Output indicator (orange)
(Lit while Timer gives output.)
Front View
Main dial
(for setting the time)
Output indicator (orange)
(Lit while Timer gives output.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operation/power indicator (green)
(Lit while the power is ON.)
Operating mode switch
Operating mode switch*
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
Main dial
(for setting the time)
*If the switch is left between settings, proper operation may not be possible.
Make sure that the switch is set properly.
Note: The default settings are for 0.1 s in mode A.
7
H3DK-M/H3DK-S
Dimensions
(Unit: mm)
■ Timers
H3DK-M
H3DK-S
100
88.2
22.5
22.5
22.5
69.1
4
79 65.6 52
H3DK-M2
H3DK-S2
89.4
H3DK-M1
H3DK-S1
H3DK-M2
H3DK-S2
H3DK-M1
H3DK-S1
■ Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
■ Basic Operation
● Setting Switches
• Each switch has a snap mechanism that secures the switch at given positions. Set the switch to one of these positions.
Do not set it midway between two positions. Malfunction could result from an improper setting.
Setting the Operating Mode
● Setting the Operating Mode
The H3DK-M can be set to any of eight
operating modes. The H3DK-S can be
set to any of four operating modes. Turn
the operating mode switch with a flatblade or Phillips screwdriver. The H3DKM can be set to any of eight modes; the
H3DK-S, to any of four modes.
Setting the INIT/TIME Switch
● Switching Relay R2 between
Instantaneous and Time-limit
Contacts (H3DK-M2/-S2 Only)
The INIT/TIME switch can be used to
switch relay R2 between instantaneous
and time-limit operation.
Setting the Time Range
● Setting the Time Range
The time range switch can be used to set
the time range. Turn the switch with a
flat-blade or Phillips screwdriver.
Time range
switch
Operating
mode switch
8
INIT/TIME
switch
H3DK-M/H3DK-S
■ Timing Charts
• There is no start input with the H3DK-S. Timer operation starts when the power is turned ON.
• There is no instantaneous output with the H3DK-@1.
A: ON Delay
t−a
t
Basic Operation
t
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
**
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
B: Flicker OFF Start
t
t−a
t
t
t
t
t−a
Basic Operation
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
**
Timing
Timing
Timing
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
B2: Flicker ON start
t
t−a
t
t
t
t
Basic Operation
t−a
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
**
Timing
Timing
Timing
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is ignored while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
C: Signal ON/ OFF Delay
t
t
t
t−a
t
t−a
Basic Operation
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Instantaneous contacts: NC
(21 and 22)
Power
*
Start input
Timing
Timing
Timing
Output
Timing
* The start input is valid while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
Note 1.The reset time is 0.1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the set time. “t−a” is a time that is less that the set time.
9
H3DK-M/H3DK-S
D: Signal OFF delay
t−a
t
t−a
t−a
t
Basic Operation
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* The start input is valid while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
E: Interval
t
t
t−a
t−a
Basic Operation
t
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
**
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* For power ON-delay operation, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
G: Signal ON/ OFF Delay
t
t
t
t−a
t−a
t
Basic Operation
Power (A1 and A2)
Start (B1 and A1)
Power
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
*
Start input
Timing
Timing
Timing
Timing
Output
Instantaneous contacts: NC
(21 and 22)
* The start input is valid while the Timer is in
operation.
Instantaneous contacts: NO
(21 and 24)
Power indicator
J: One-shot Output (ON delay)
t
t
t−a
t−a
t
Basic Operation
Power (A1 and A2)
Start (B1 and A1)
Time-limit contacts: NC
15 and 16 (25 and 26)
Time-limit contacts: NO
(output indicator)
15 and 18 (25 and 28)
Power
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
1 s±0.6 s
(fixed)
Instantaneous contacts: NC
(21 and 22)
Instantaneous contacts: NO
(21 and 24)
Power indicator
Note 1.The reset time is 0.1 s min. Make sure the signal input time is 0.05 s or longer.
Note 2.“t” is the set time. “t−a” is a time that is less that the set time.
10
*
Start input
**
Timing
Output
1 s±0.6 s
(fixed)
* To start with the power supply, connect start input
terminals B1 and A1. The Timer starts operating
as soon as the power turns ON.
** The start input is valid while the Timer is in
operation.
New Product News
Twin Timer
H3DK-F
LR
• Switch between flicker-OFF or flicker-ON start mode.
• Independent ON time and OFF time settings.
• Eight time ranges from 0.1 s to 1,200 h.
Ordering Information
■ List of Models
Operating
modes
Flicker OFF
start/flicker ON
start
Supply voltage
Control output
H3DK-F
24 to 240 VAC/DC
Contact output: SPDT
Model
H3DK-F
12 VDC
Contact output: SPDT
Model
H3DK-FA
■ Accessories (Order Separately)
Item
Specification
Model
50 cm (l) x 7.3 mm (t)
Mounting Track
PFP-50N
1 m (l) x 7.3 mm (t)
PFP-100N
1 m (l) x 16 mm (t)
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
■ Model Structure
Model
H3DK-F
Operating modes
Terminal block
Flicker OFF start/flicker ON
start
6 terminals
Output type
Mounting method
Safety standards
cURus
(UL508
CSA C22.2 No. 14)
DIN Track mounting
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
Relay, SPDT
Accessories
User label
Specifications
■ Time Ranges
Time range setting
Set time range
0.1 s
1s
10 s
1 min
10 min
1h
10 h
100 h
0.1 to 1.2 s
1 to 12 s
10 to 120 s
1 to 12 min
10 to 120 min
1 to 12 h
10 to 120 h
100 to 1,200 h
Scale numbers
12
■ Ratings
Power supply voltage *1
• 24 to 240 VAC/DC, 50/60 Hz *2
• 12 VDC *2
Allowable voltage fluctuation range
• 24 to 240 VAC/DC: 85% to 110% of rated voltage
• 12 VDC: 90% to 110% of rated voltage
Power reset
Minimum power-OFF time: 0.1 s
Reset voltage
Power consumption
10% of rated voltage
H3DK-F
At 240 VAC: 4.5VA max. *3
H3DK-FA
At 12 VDC: 0.6 W max.
Control output
Contact output (SPDT): 5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 24 VDC with resistive load *3, *4
Ambient operating temperature
−20 to 55°C (with no icing)
Storage temperature
−40 to 70°C (with no icing)
Ambient operating humidity
25% to 85%
11
H3DK-F
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity
(Reference Values) on the next page.
*5. 125 VDC: 0.15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference value)
■ Characteristics
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
Setting error
±10% of FS ±0.05 s max.
Influence of voltage
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
Impulse withstand voltage
24 to 240 VAC/VDC: 3 kV between power terminals, 4.5 kV between currentcarrying metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV between power terminals, 1.5 kV between current-carrying metal
parts and exposed non-current-carrying metal parts
Noise immunity
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
Life expectancy
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Malfunction 100 m/s2 3 times each in 6 directions
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
IP30 (Terminal block: IP20)
Weight
Approx. 110 g
EMC
(EMI)
Radiated Emissions:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuations and Flicker:
(EMS)
ESD Immunity:
EN61812-1
EN 55011 class B
EN 55011 class B
EN 61000-3-2
EN61000-3-3
EN61812-1
EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:
EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:
EN 61000-4-5: 2 kV common mode,
1 kV differential mode
■ I/O
Output
12
None
Control output
60
d = 50 mm
d = 10 mm
50
d = 5 mm
30
d = 0 mm
20
10
0
1
2
3
4
5
Output is turned ON/OFF according to the time set on the ON
time setting dial and OFF time setting dial.
6
Load current (A)
Tested Timer: H3DK-F
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
Input
70
Testing Method
■ Applicable standards
Safety standards
80
Maximum ambient operating
temperature in specifications
Shock resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Degree of protection
The relation between the installation pitch
and the load current is shown in the following graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the temperature inside the Timer will increase, reducing the life expectancy of internal parts.
40
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Vibration
resistance Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Electrical
● Installation Pitch and Output
Switching Capacity (Reference
Values)
Ambient temperature (°C)
Accuracy of operating
time
Test
timer
1
DIN Track
Test
timer
2
Test
timer
3
Test
timer
4
Timer installation pitch: d
Test
timer
5
H3DK-F
Connections
■ Block Diagrams
■ Terminal Arrangement
H3DK-F
H3DK-F
A1
ON
OFF
indicator indicator
ON/OFF time setting
detection circuit
ON/OFF start switch
15
R1
15
AC (DC)
input
Time
specification
switches
Indicator
circuit
18
ROM
RAM
16
Clock
One-chip microcomputer
Power supply
circuit
Output circuit
18
16
A2
(DIN notation)
A1
A2
15
16 18
Note: The power supply terminals do not have polarity.
Nomenclature
H3DK-F
Front View
Bottom View
Note 1. Use solid wire (2.5 mm2 max.) or ferrules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
User label
attachment location
ON time range switch
ON output
indicator (orange)
ON time setting dial
(Sets the ON time.)
OFF output
indicator (green)
OFF time setting dial
(Sets the OFF time.)
OFF time range switch
ON/OFF start switch
(Default setting is for
an OFF start.)
Using Solid Wire
(2.5 mm2 Max.)
Using Ferrule with
Insulative Sleeve
Terminal Block
(See notes 1 and 2.)
8 mm max.
8 mm max.
Recommended Ferrules
Phoenix Contact
• AI@@@ Series
• AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
13
H3DK-F
Dimensions
(Unit: mm)
■ Timers
H3DK-F
100
88.2
22.5
69.1
4
79 65.6 52
89.4
■ Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
■ Basic Operation
Setting the Time Ranges
Setting the ON/OFF Start Switch
Setting the Times
● Setting the Time Ranges
● Setting an ON Start or OFF Start
● Setting the Times
Use the ON time range switch to set the
ON time range and the OFF time range
switch to set the OFF time range. Turn
the switches with a flat-blade or Phillips
screwdriver.
The ON/OFF start switch can be used to
switch between ON-start and OFF-start
operation.
Use the ON time setting dial and the
OFF time setting dial to set the ON time
and OFF time.
ON time setting dial
ON time range
switch
ON/OFF start
switch
OFF time setting dial
OFF time range
switch
■ Timing Charts
Flicker OFF start
Flicker ON start
0.1 s min.
0.1 s min.
Power (A1 and A2) ON
OFF
ON indicator (15 and 18) ON
OFF
tOFF
tON
tOFF
tON
Power (A1 and A2) ON
OFF
tOFF
tOFF
ON indicator (15 and 18) ON
OFF
tON
tOFF
tON
tOFF
tON
tON
OFF indicator (15 and 16) ON
OFF
OFF indicator (15 and 16) ON
OFF
Output (15 and 18) ON
OFF
Output (15 and 18) ON
OFF
tON: ON set time
tOFF: OFF set time
tON: ON set time
tOFF: OFF set time
Note 1. The reset time is 0.1 s min.
Note 2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer.
14
New Product News
Star-delta Timer
H3DK-G
LR
• Set two time ranges between 1 and 120 s with one Timer.
• Models with 240 to 440-VAC power supply added to series.
Ordering Information
■ List of Models
Operating modes
Supply voltage
Control output
H3DK-G
24 to 240 VAC/DC
Star-delta Timer
Model
H3DK-G
Contact outputs
Model
Delta circuit: SPDT, Star circuit: SPDT
Model
12 VDC
240 to 440 VAC
H3DK-GA
H3DK-GE
■ Accessories (Order Separately)
Item
Specification
Model
50 cm (l) x 7.3 mm (t)
Mounting Track
PFP-50N
1 m (l) x 7.3 mm (t)
PFP-100N
1 m (l) x 16 mm (t)
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
■ Model Structure
Model
Terminal block
H3DK-G
9 terminals
Operating/resetting method
Time-limit operation/selfresetting
Output type
Time-limit (relay)
Star circuit: SPDT
Delta circuit: SPDT
Mounting method
Safety standards
cURus*1
(UL 508
CSA C22.2 No. 14)
DIN Track mounting
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
Accessories
User label
*1. Except for the H3DK-GE.
Specifications
■ Time Ranges
Time range setting
Star set time (t1) range
Star-Delta transfer time (t2)
t1x1
t1x10
1 to 12 s
10 to 120 s
Select from 0.05, 0.1, 0.25, or 0.5 s.
■ Ratings
H3DK-G, -GA
• 24 to 240 VAC/DC, 50/60 Hz *2
• 12 VDC *2
Power supply voltage *1
Allowable voltage fluctuation range
Power reset
80 % to 110% of rated voltage
Minimum power-OFF time: 0.5 s
Reset voltage
Power consumption
• 24 to 240 VAC/DC: 85% to 110% of rated voltage
• 12 VDC: 90% to 110% of rated voltage
H3DK-GE
• 240 to 440 VAC (50/60 Hz) *6
10% of rated voltage
H3DK-G
At 240 VAC: 6.6 VA max. *3
H3DK-GA
At 12 VDC: 0.9 W max.
Control output
Contact output (Time-limit output: relay, Star output:
SPDT, Delta output: SPDT):
5 A at 250 VAC with resistive load (cosφ = 1)
5 A at 24 VDC with resistive load *3, *4
Ambient operating temperature
−20 to 55°C (with no icing)
Storage temperature
−40 to 70°C (with no icing)
Ambient operating humidity
25% to 85%
At 440 VAC: 34 VA max.
Ith 2 A
AC-15
AC-15
AC-15
120 VAC: 1.5 A
240 VAC: 1 A
440 VAC: 0.3 A
15
H3DK-G
*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this inrush current when turning ON and OFF the
power supply to the Timer with device with a solid-state output, such as a sensor.
*2. DC ripple: 20% max.
*3. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*4. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity
(Reference Values) on the next page.
*5. 125 VDC: 0.15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference value)
*6. For the H3DK-GE, approx. 6 A of inrush current will flow when the power supply is turned ON. When selecting the device connected to the Timer, allow leeway in
the current ratings.
■ Characteristics
±1% of FS max.
Setting error
±10% of FS ±0.05 s max.
Transfer time
Total error ± (25% of transfer time + 5 ms) max.
Influence of voltage
±0.5% of FS max.
Influence of temperature
±2% of FS max.
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
Between current-carrying metal parts
and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and
operating circuit: 2,000 VAC 50/60 Hz
for 1 min.
Between contacts not located next to
each other: 1,000 VAC 50/60 Hz for
1 min.
Impulse withstand voltage
H3DK-G: 24 to 240 VAC/VDC: 3 kV
between power terminals, 4.5 kV
between current-carrying metal
parts and exposed non-currentcarrying metal parts
H3DK-GA: 12 VDC: 1 kV between
power terminals, 1.5 kV between
current-carrying metal parts and
exposed non-current-carrying
metal parts
Between current-carrying metal parts
and exposed non-current-carrying metal
parts: 2,500 VAC 50/60 Hz for 1 min.
Between control output terminals and
operating circuit: 2,500 VAC 50/60 Hz
for 1 min.
Between contacts not located next to
each other: 1,000 VAC 50/60 Hz for
1 min.
---
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV*
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
*
16
80
70
60
Destruction 1,000 m/s2 3 times each in 6 directions
d = 5 mm
30
d = 0 mm
20
10
0
Mechanical
10 million operations min. (under no
load at 1,800 operations/h)
Electrical
100,000 operations min.
100,000 operations min. (5 A at 250
(0.3 A at 440 VAC, resistive load at
VAC, resistive load at 360 operations/h)
1,800 operations/h)
Weight
Approx. 120 g
Except for the H3DK-GE
2
3
4
5
Tested Timer: H3DK-G
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Test
timer
2
Test
timer
3
Test
timer
4
10 million operations min.
(under no load at 1,800 operations/h)
DIN Track
IP30 (Terminal block: IP20)
1
6
Load current (A)
Test
timer
1
Malfunction 100 m/s2 3 times each in 6 directions
Degree of protection
d = 50 mm
d = 10 mm
50
Testing Method
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Vibration
resistance Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Life expectancy
The relation between the installation pitch
and the load current is shown in the following graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the temperature inside the Timer will increase, reducing the life expectancy of internal parts.
40
Noise immunity
Shock resistance
● Installation Pitch and Output
Switching Capacity (Reference
Values)
Maximum ambient operating
temperature in specifications
Accuracy of operating
time
H3DK-GE
Ambient temperature (°C)
H3DK-G, -GA
Timer installation pitch: d
Test
timer
5
H3DK-G
■ Applicable standards
Safety standards
cURus: UL 508/CSA C22.2 No. 14 *1
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III *2
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2 *1
(EMI)
Radiated Emissions:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuations and Flicker:
(EMS)
ESD Immunity:
EN61812-1
EN 55011 class B
EN 55011 class B
EN 61000-3-2 *1
EN61000-3-3 *1
EN61812-1
EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3:
10 V/m (80 MHz to 1 GHz)
Burst Immunity:
EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:
EN 61000-4-5: 2 kV common mode,
1 kV differential mode
EMC
*1. This standard is not applicable to the H3DK-GE.
*2. This standard is not applicable if the output is used with a rating that exceeds 250 VAC.
■ I/O
Input
None
Output
Control output
The star output is turned OFF when the dial set value is reached and the
delta output is turned ON after the preset transfer time elapses.
Connections
■ Block Diagrams
■ Terminal Arrangement
H3DK-G
H3DK-G
AC (DC) input
Star-delta
transfer time
switch
Star time
setting
switch
A1
15
25
Delta
Star
contacts contacts
Power supply
circuit
Star output
ROM
RAM
Clock
R1
R2
15
25
Output
circuit
Delta output
One-chip microcomputer
Indicator circuit
18
16 28
28
26
18
16
26
A2
(DIN notation)
Star output ON Delta output ON
indicator
indicator
A1
A2
15
25
16 18 26 28
Note: The power supply terminals do not have polarity.
17
H3DK-G
Nomenclature
H3DK-G
Front View
Bottom View
Note 1. Use solid wire (2.5 mm2 max.) or ferrules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
User label
attachment location
Terminal block
(See notes 1 and 2.)
Star operation
indicator (green)
Main dial
(Sets the star time.)
Using Solid Wire
(2.5 mm2 Max.)
Using Ferrule with
Insulative Sleeve
Delta operation
indicator (orange)
8 mm max.
Star-delta transfer time
switch
H3DK-GE
Front View
Bottom View
User label
attachment location
Star operation
indicator (green)
Terminal block
(See notes 1 and 2.)
Main dial
(Sets the star time.)
Delta operation
indicator (orange)
Star-delta transfer time
switch
18
8 mm max.
Recommended Ferrules
Phoenix Contact
• AI@@@ Series
• AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
Note 3. Always keep the front cover mounted
when using the Timer.
Front cover
(See note 3.)
H3DK-G
Dimensions
(Unit: mm)
■ Timers
H3DK-G
100
88.2
22.5
69.1
4
79 65.6 52
89.4
H3DK-GE
102
88.2
26
22.5
69.1
89.4
79
65.6
55
4
■ Track Mounting Products (Sold Separately)
Refer to page 28 for details.
19
H3DK-G
Operating Procedures
■ Basic Operation
Setting the Time Ranges
Setting the Time
● Setting the Delta Time Range and the Star-delta Transfer
Time (t2)
● Setting the Time
The start time is set with the main dial.
Star Time (t1) Range
Set the star-delta transfer time.
For ×1 (1 to 12 s), use side (A) (labeled “t1×1”).
For ×10 (10 to 120 s), use side (B) (labeled “t10×1”).
(See following diagram.)
(A)
Star-delta transfer
time setting (t2)
Switches the start
time (t1) range.
(B)
0.5s
0.25s
0.1s
0.05s
0.5s
0.25s
0.1s
0.05s
t2
t1x1
Main dial
t2
t1x10
■ Timing Chart
0.5 s min.
Power (A1 and A2)
ON
OFF
Star contacts (15 and 18)
ON
OFF
Delta contacts (25 and 26)
ON
OFF
Star operation indicator
ON
OFF
t1
t2
Delta operation indicator ON
OFF
t1: Star time setting
t2: Transfer time
Note: “t1” is the start set time. “t2” is the transfer time.
20
New Product News
Power OFF-delay Timer
H3DK-H
• Set two time ranges with each Timer, from 0.1 to 12 seconds for
the S Series and from 1.0 to 120 seconds for the L Series.
Ordering Information
■ List of Models
H3DK-H
Operating modes
Power OFF Delay
Supply voltage
S Series
(time range: 0.1 to 12 s)
Control output
L Series
(time range: 1.0 to 120 s)
100 to 120 VAC
Contact output: SPDT
Model
H3DK-HCS
H3DK-HCL
200 to 240 VAC
Contact output: SPDT
Model
H3DK-HDS
H3DK-HDL
24 to 48 VAC/DC
Contact output: SPDT
Model
H3DK-HBS
H3DK-HBL
■ Accessories (Order Separately)
Item
Specification
Model
50 cm (l) x 7.3 mm (t)
Mounting Track
PFP-50N
1 m (l) x 7.3 mm (t)
PFP-100N
1 m (l) x 16 mm (t)
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
■ Model Structure
Model
Terminal block
H3DK-H
Operating/resetting method
Output type
Instantaneous operation/
time-limit reset
6 terminals
Relay, SPDT
Mounting method
Safety standards
cURus
(UL 508
CSA C22.2 No. 14)
DIN Track mounting
EN 61812-1
IEC 60664-1 4 kV/2
EN 50274
Accessories
User label
Specifications
■ Time Ranges
S Series
Time range setting
Set time range
L Series
x0.1
x1
x1
x10
0.1 to 1.2 s
1 to 12 s
1 to 12 s
10 to 120 s
Power ON time
0.1 s min.
Scale numbers
0.3 s min.
12
■ Ratings
• 100 to 120 VAC, 50/60 Hz
• 200 to 240 VAC, 50/60 Hz
• 24 to 48 VAC/DC, 50/60 Hz
Supply voltage
Allowable voltage fluctuation range
Power consumption
*1
85% to 110% of rated voltage
H3DK-HCS/-HCL
At 120 VAC: 11.7 VA max.
H3DK-HDS/-HDL
At 240 VAC: 29.5 VA max.
H3DK-HBS/-HBL
At 48 VAC: 1.2 VA max.
*2
Control output
Contact output, 5 A at 250 VAC with resistive load (cosφ = 1), 5 A at 30 VDC with
resistive load *2
Ambient operating temperature
−20 to 55°C (with no icing)
Storage temperature
−40 to 70°C (with no icing)
Ambient operating humidity
25% to 85%
21
H3DK-H
*1. DC ripple: 20% max. (A single-phase, full-wave rectifying power supply can be connected.)
*2. Refer to DC Power Consumptions (Reference Information) on page 27 for DC power consumptions.
*3. The control output ratings are for one H3DK operating alone.
If you operate two or more Timers side by side, refer to Installation Pitch and Output Switching Capacity (Reference Values) on the next page.
■ Characteristics
Setting error
±10% of FS ±0.05 s max.
Influence of voltage
±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature
±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance
100 MΩ min. at 500 VDC
Dielectric strength
Between current-carrying metal parts and exposed non-current-carrying metal
parts: 2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for
1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for
1 min.
Impulse withstand voltage
Between power supply terminals: 1 kV for 24-VAC/DC and 48-VAC/DC models,
3 kV for all other models.
Between current-carrying metal parts and exposed non-current-carrying metal
parts): 1.5 kV for 24-VAC/DC and 48-VAC/DC models, 4.5 kV for all other
models.
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs,
1-ns rise): ±1.5 kV (between power supply terminals)
Noise immunity
Static immunity
Malfunction: 4 kV, Destruction: 8 kV
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Vibration
resistance Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Life expectancy
Mechanical 10 million operations min. (under no load at 1,200 operations/h)
Malfunction 100 m/s2 3 times each in 6 directions
Electrical
IP30 (Terminal block: IP20)
Weight
Approx. 120 g
80
70
60
d = 50 mm
d = 10 mm
50
d = 5 mm
40
30
d = 0 mm
20
10
0
1
2
3
4
Tested Timer: H3DK-H
Applied voltage: 240 VAC
Installation pitch: 0, 5, 10, and 50 mm
Safety standards
cURus: UL 508/CSA C22.2 No. 14
EN 50274: Finger protection, back-of-hand proof
EN 61812-1: Pollution degree 2, Overvoltage category III
CCC: Pollution degree 2, Overvoltage category II, section DB14048.5-2008 part 5-1
LR: Test Specification No. 1-2002 Category ENV 1.2
EMC
(EMI)EN61812-1
Radiated Emissions:EN 55011 class B
Emission AC Mains:EN 55011 class B
Harmonic Current:EN 61000-3-2
Voltage Fluctuations and Flicker:EN61000-3-3
(EMS)EN61812-1
ESD Immunity:EN 61000-4-2: 6 kV contact discharge,
8 kV air discharge
Radiated Radio-Frequency Electromagnetic Field Immunity (AM Radio Waves):
EN 61000-4-3: 10 V/m (80 MHz to 1 GHz)
Burst Immunity:EN 61000-4-4: 2 kV power line,
1 kV I/O signal line
Surge Immunity:EN 61000-4-5: 2 kV common mode,
1 kV differential mode
■ I/O
Input
None
Control output
5
The Timer operates as soon as the Timer is turned ON. The
Timer starts timing when the power is turned OFF and the output
is turned OFF when the time set on the dial elapses.
6
Load current (A)
Testing Method
■ Applicable standards
22
The relation between the installation pitch
and the load current is shown in the following graph. (Except for the H3DK-GE)
If Timer is used under load conditions that
exceed the specified values, the temperature inside the Timer will increase, reducing the life expectancy of internal parts.
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
Degree of protection
Output
● Installation Pitch and Output
Switching Capacity (Reference
Values)
Ambient temperature (°C)
±1% of FS max. (±1% ±10 ms max. at 1.2-s range)
Maximum ambient operating
temperature in specifications
Accuracy of operating
time
Test
timer
1
DIN Track
Test
timer
2
Test
timer
3
Test
timer
4
Timer installation pitch: d
Test
timer
5
H3DK-H
Connections
■ Block Diagrams
■ Terminal Arrangement
H3DK-H
H3DK-H
A1
AC (DC) input
Indicator circuit
15
Time specification
switches
R1
15
Power supply
circuit
Oscillation circuit
Counting circuit
Output circuit
Power
interruption
detection circuit
18
18
16
16
A2
(DIN notation)
A1
A2
15
16 18
Note 1: The above figure shows the terminal arrangement for a 24 to 48-VAC/DC model.
Models with 100 to 120-VAC or 200 to
240-VAC power input do not have a DC
input.
Note 2: The power supply terminals do not have
polarity.
Nomenclature
H3DK-H
Bottom View
Front View
Note 1. Use solid wire (2.5 mm2 max.) or ferrules with insulative sleeves to connect
to the terminals.
To maintain the withstand voltage after
connecting the terminals, insert no
more than 8 mm of exposed conductor
into the terminal.
User label
attachment location
Time range switch
(S Series: ×0.1 or
×1, L Series: ×1 or
×10)
Power indicator
(green) (Lit while
the power is ON.)
Using Solid Wire
(2.5 mm2 Max.)
Main dial
(for setting the time)
Using Ferrule with
Insulative Sleeve
Terminal block
(See notes 1 and 2.)
8 mm max.
8 mm max.
Recommended Ferrules
Phoenix Contact
• AI@@@ Series
• AI-TWIN@@@ Series
Note 2. Screw Tightening Torque
Recommended torque: 0.49 N·m
Maximum torque: 0.98 N·m
23
H3DK-H
Dimensions
(Unit: mm)
■ Timers
H3DK-H
100
88.2
22.5
69.1
4
79 65.6 52
89.4
■ Track Mounting Products (Sold Separately)
Refer to page 28 for details.
Operating Procedures
■ Basic Operation
Setting the Time Ranges
Setting the Time
● Setting the Time Ranges
● Setting the Time
The scale multiplier can be changed with the timer range switch.
It can be changed between ×0.1 s and ×1 s for an S-series Timer
and between ×1 s and ×10 s for an L-series Timer.
The operation time is set with the main dial.
Main dial
Time range
switch
■ Timing Charts
Rt
t
ON
Power (A1 and A2)
OFF
Output relay: NO (15 and 18)
ON
OFF
Indicator ON
OFF
t: Set time
Rt: Minimum power-ON time
S Series: 0.1 s min.
L Series: 0.3 s min.
(The output may never turn ON if the power is not ON for at least this time.)
24
Rt
t
H3DK
Safety Precautions
● Refer to Safety Precautions for All Timers.
Note: The following is common for all H3DK models.
Caution
Switching arcs or relay heating may cause fire or
explosion. Do not use the Timer in the presence of
inflammable or explosive gases.
The H3DK Series uses a transformerless power
supply system. An electrical shock may occur if
an input terminal is touched while power is being
supplied.
The inrush current will depend on the type of load
and may influence the contact switching frequency and number of operations. Check both the
rated current and the inrush current, and allow
leeway in the circuit design.
The life of the output relay largely depends on the
switching current and other switch conditions.
Consider the actual application conditions and do
not exceed the rated load or electrical life. If the
output relay is used beyond its service life, the contacts
may fuse or burning may occur. Also, never exceed the
rated load current. When using a heater, also place a thermal switch in the load circuit.
Do not remove the external case.
Minor electric shock, fire, or equipment failure
may sometimes occur. Do not disassemble, modify, or repair the Timer or touch any internal parts.
Precautions for Safe Use
• Use ferrules to wire the H3DK. If stranded wires are used, wire
scraps may enter the Timer, possibly shorting the circuits.
• Rapid changes in temperature or high humidity may cause
condensation in Timer circuits, possibly resulting in malfunction or damage to components. Check the application environment.
• Store the Timer within the rated ranges given for the Timer
model you are using. If the Timer is stored below −20°C, allow
it to warm up for three hours at room temperature before turning ON the power supply.
• Use the Timer within the ambient operating temperature and
ambient operating humidity ranges given for the Timer model
you are using.
• Use the Time within the characteristics for water and oil exposure given for the Timer model you are using.
• Do not use the Timer in locations subject to excessive dust,
corrosive gas, or direct sunlight.
• Do not use the Timer in locations subject to vibration and
shock. Long-term exposure may damage the Timer due to
stress.
• Separate the Timer from any sources of excessive static electricity, such as forming materials and pipes carrying power or
liquid materials.
• Maintain the variations in the power supply voltage to within
the specified allowable range.
• If a voltage that exceeds the rating is applied, internal components may be destroyed.
• Wire all terminals correctly.
• Use only the specified wires for wiring.
Applicable wire gauge: AWG18 to AWG22
• Install and clearly label a switch or circuit breaker so that the
operator can quickly turn OFF the power supply.
• If the Timer is left in the timed out condition for a long period of
time at high temperatures, internal components (such as electrolytic capacitors) may deteriorate quickly.
• The exterior of the Timer may be damaged by organic solvents
(such as thinners or benzene), strong alkali, or strong acids.
• For Timers with AC power input, use a commercial power supply for the power supply voltage. Although some inverters give
50/60 Hz as the output frequency, do not use an inverter output as the power supply for a Timer. Doing so may result in
smoking or burning due to internal temperature increases in
the Timer.
• Use the same type of wiring for all Timer wiring.
• When disposing of the Timer, observe all local ordinances as
they apply.
• The Timer may not operate properly in locations that are subject to sulfide gas, such as in sewers or incinerators. Products
that are suitable for operation in sulfide gas are not available
for OMRON Timers or general control devices. Seal the Timer
to isolate it from sulfide gas. If the Timer cannot be sealed,
OMRON can make special products with resistance to sulfide
gas for some Timers. Ask your OMRON representative for
details.
• Confirm that the power and output indicators are operating
normally. Depending on the operating environment, the indicators and plastic parts may deteriorate faster than expected,
causing the indicators to fail. Periodically perform inspections
and replacements.
25
H3DK
Precautions for Correct Use
● Changing Switch Settings
Do not change the time unit, time scale, operating mode, or INIT/
TIME switch while the Timer is in operation. Doing so may result
in malfunction. Turn OFF the power supply before changing the
setting of any switch.
● Mounting and Dismounting
• Although there are no particular mounting restrictions, the
Timer should be mounted as horizontally as possible.
• When mounting the Timer on a mounting Track, loosen the
two hooks, press the Timer onto the Track, and then insert the
hooks.
Hook
● Relationship between Input and Power Supply Circuits (H3DK-M1/-M2)
B1
AC/DC
power supply
Input circuit
A1
Power supply circuit
A2
• The input circuit and the power supply circuit are configured
independently. The input circuit can be turned ON and OFF
without considering the ON/OFF state of the power supply.
A voltage equivalent to the power supply voltage is also
applied to the input circuit.
• If a relay or transistor is connected to two or more Timers, the
input terminals of those Timers must be wired properly so that
they will not be different in phase or the terminals will be shortcircuited to one another. Always use the same power supply
phases.
Contact or transistor for
external input signal
Hook
• When removing the Timer, pull out the two hooks, and then
remove the Timer from the Track
A1
B1
Hook
H3DK
Power
A2
A1
B1
Hook
30 mm min.
A2
• It will be easier to mount and dismount the Timer if a distance
of 30 mm or more is provided between the bottom of the Timer
and other equipment.
Contact or transistor for
external input signal
A1
● Power Supply
B1
• The power supply can be connected to the power input terminals without considering polarity.
• A DC power supply can be connected if its ripple factor is 20%
or less and the average voltage is within the allowable voltage
fluctuation range of the Timer.
• For the power supply of the input device, use an isolating
transformer in which the primary and secondary windings are
mutually isolated and the secondary winding is not grounded.
(H3DK-M1 and H3DK-M2 only)
H3DK
Power
Rectifier circuit
A2
Circuit
Isolation transformer is required.
• The H3DK-H has a large inrush current. Provide sufficient
power supply capacity.
If the power supply capacity is too small, there may be delays
in turning ON the output.
26
H3DK
Power
A2
A1
B1
H3DK
A2
● Environment
A1
B1
Start
input
H3DK
• When using the Timer in an area with excessive electronic
noise, separate the Timer and input device as far as possible
from the noise sources. It is also recommended to shield the
input signal wiring to prevent electronic interference.
• The external impulse voltage entering across the power supply
terminals has been checked against a ±1.2×50 µs standard
waveform according to JEC-210, Impulse Voltage/Current
Test, of The Institute of Electrical Engineers of Japan. Surge
or noise superimposed on the power supply may damage
internal components or cause them to malfunction. We recommend that you check the circuit waveform and use surge
absorbers. The effects on components depend on the type of
surge and noise that are generated. Always perform testing
with the actual equipment.
H3DK
● Wiring
The H3DK-H acts like a high-impedance circuit. Therefore, the
Timer may not reset if it is influenced by inductive voltage. To
eliminate inductive voltage, the wires connected to the Timer
must be as short as possible and should not be installed parallel
to power lines. If the Timer is influenced by inductive voltage that
is 30% or more of the rated voltage, connect a CR filter with a
capacitance of approximately 0.1 µF and a resistance of approximately 120 Ω or a bleeder resistor between the power supply
terminals.
If there is any residual voltage due to current leakage, connect a
bleeder resistor between the power supply terminals.
•
•
● Operating Frequency
• The H3DK-H may malfunction if it is used as shown below. Do
not use the H3DK-H in these ways.
Timer Repeatedly Times Out in Cycles of 3 s or Less
3s
or less
3s
or less
•
•
Power
•
Output
In the above case, use the H3DK-M2/-M1 in D mode (signal
OFF delay).
● DC Power Consumptions (Reference Information)
H3DK-M2/-S2
At 24 VDC: 1.2 W max.
H3DK-M1/-S1
At 24 VDC: 1.1 W max.
H3DK-F
At 24 VDC: 1.1 W max.
H3DK-G
At 24 VDC: 1.2 W max.
H3DK-HBS/-HBL
At 24 VDC: 1.2 W max.
•
•
•
•
● Other Precautions
• If the Timer is mounted on a control panel, dismount the Timer
from the control panel before carrying out a voltage withstand
test between the electric circuits and non-current-carrying
EN/IEC Standard Compliance
• Refer to the datasheet for the H3DK for cable selection and
other conditions for compliance with EMC standards.
• The power supply terminals and input terminals are not isolated. There is basic insulation between the power supply terminals and output terminals.
• If double or reinforced insulation is required, use the double or
reinforced insulation defined in IEC 60664 that is suitable for
the maximum applied voltage for the clearance, solid insulation, and other factors.
•
metal parts of the Timer. (Otherwise, the internal circuits of the
Timer may be damaged.)
The H3DK-H uses a latching relay for the output. Shock, such
as dropping the H3DK-H during shipment or handling, can
cause the output contacts to reverse to the neutral position.
Check the output status with a tester before using the H3DKH.
The life expectancy of the control output contacts is greatly
affected by switching conditions. Always confirm operation
using the actual conditions and equipment before using the
Timer and make sure that the number of switching operations
presents no problems in performance. If Timer application is
continued after performance has deteriorated, insulation failure between circuits, burning of the control output relay, or
other problem will eventually occur.
If the power supply voltage is gradually increased, a power
reset may occur or the Timer may time out. Use a switch,
relay, or other device with contacts to apply the power supply
voltage all at once.
Make sure that residual voltage or inductive voltage is not
applied after the power turns OFF.
Error in the operation time of the Timer is given as a percentage of the full-scale time. The absolute value of the error will
not change even if the set time is changed. Therefore, always
use the Timer with the set time set as close as possible to the
full-scale value of the set time range.
When switching a microload, check the specified minimum
load given for the Timer model you are using.
When setting the operating time, do not turn the dial beyond
the scale range.
If better accuracy is required in the set time, adjust the dial
while measuring the operation time.
If the Timer is reset immediately after timing out, make sure
that the circuit configuration allows sufficient resetting time.
Errors will occur in the sequence if there is not sufficient resetting time.
When directly switching a DC load, the switching capacity will
be lower than when switching an AC load.
Precautions for Compliance with UL Standards
and CSA Standards
Notice to Users of the H3DK in the USA and Canada
Please use the following installation information instead of the
general information in this document in order to use the product
under certified conditions of UL and CSA when the product is
installed in the USA or Canada. These conditions are required by
NFPA 70, National Electrical Code in the USA and the Canadian
Electrical Code, Part I in Canada and may vary from information
given in this document.
• Use an isolated source for power input for the H3DK-@A.
Use an isolated source with external overcurrent protection of
16 A maximum for the source and input. (The input is applicable to the H3DK-M only.)
• Environment
Surrounding Air Temperature: 55°C
• Power Supply: The inputs are non-isolated (applicable to
H3DK-M only).
The same power supply as the main power source must be
used for that for input.
• Pollution Degree
Pollution degree II
27
H3DK
Track Mounting Products (Sold Separately)
DIN Track
PFP-100N
PFP-50N
(Unit: mm)
7.3±0.15
4.5
35±0.3
15
25
10
25
25
1,000 (500)*
10
25
27±0.15
15 (5)*
1
*Dimensions in parentheses are for the PFP-50N.
DIN Track
PFP-100N2
16
4.5
35±0.3 27
15
End Plate
PFP-M
25
10
25
25
1,000
25
10
15
M4x8
panhead
screw
50
1.8
1
35.5 35.3
1.8
11.5
10
1.3
4.8
M4 screw
and washer
Spacer
PFP-S
16
12
5
34.8
44.3
16.5
Note 1: Order the above products in multiples of 10.
Note 2: The Tracks conform to DIN standards.
28
29.2
1
10
6.2
24
1.5
Warranty and Application Considerations
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or
other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER
ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET
THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2010 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
Printed in Japan
CSM_3_1_0212
Cat. No. L118-E1-02
0910