ETC H479166230

Current and Voltage Controls
1-Phase Max. and Min. Current Control
Type H 479
• AC current metering relay
• Measuring range: 0.5 - 500 AAC with 1-phase
current metering transformer, type MI...
• Upper and lower current limits separately adjustable
• Output: 8 A DPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• H4-housing
• LED-indication for power supply and output ON
• AC power supply
Product Description
1-phase AC current metering
relay. For mounting on DINrail. Adjustment of upper and
lower current values possible.
Ordering Key
Often used where a reaction
has to be taken e.g. when a
motor exceeds the set value.
Housing
Type
Output
Power supply
H 479 166 230
Type Selection
Plug
Output
Supply: 24 VAC
Supply: 115 VAC
Supply: 230 VAC
Screw
terminals
DPDT
H 479 166 024
H 479 166 115
H 479 166 230
Input Specifications
Output Specifications
Input
Terminals 7 & 8
Output
Rated insulation voltage
Overvoltage cat. III (IEC 60664)
nom. voltage: 0.4-4 Vp max.
20 V from current transformer MI ...
Impedance
9.9 kΩ
Measuring ranges
Range
Max. current
Types of current transformers AAC rms rms
MI 5
0.5 - 5
20 AAC
MI 20
2 - 20
50
MI 100
10 - 100
250 AAC
MI 500
50 - 500
700 AAC
Supply Specifications
Power supply AC types
Rated operational voltage
Through term. 21 & 22 024
115
230
Voltage interruption
Dielectric voltage
Rated impulse withstand volt.
Rated operational power
Overvoltage cat. III (IEC 60664)
(IEC 60038)
24 VAC ± 15%, 45 to 65 Hz
115 VAC ± 15%, 45 to 65 Hz
230 VAC ± 15%, 45 to 65 Hz
≤ 40 ms
2 kVAC (rms) (supply/elect.)
4 kV (1.2/50 µs) (line/neutral,
line/line), no direct connection to electronics
2.5 VA
Specifications are subject to change without notice (26.10.99)
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
DPDT relay
250 VAC (rms)
(cont./elect., cont./cont.)
µ (micro gap)
8 A/250 VAC (2000 VA)
0.4 A/250 VDC (100 W)
4 A/25 VDC (100 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations
(at max. load)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms) (cont./elect.)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
1
H 479
General Specifications
Reaction time
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
τ = 0.2 s, worst case reaction
time may be up to 5 x τ
LED, green
LED, red
(IEC 60947-1)
IP 20 B/front IP 40 D (IEC 60529)
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
300 g
Mode of Operation
The relay operates when the
current is within set points
(including hysteresis) and releases when the measured
current drops below/exceeds
the set points (under and over
current monitoring).
If the lower set point is set
above the upper set point,
the output relay releases and
cannot be activated before
the lower set point is set lower
than the upper set point.
Wiring Diagram
µ
Power supply
H 479
Range Setting
Range setting
Right potentiometer:
Upper limit adjustable from
10 to 100% of max. value of
4 Vp.
PE = Term. 8
Accessories
Hysteresis
Approx. 1% of set point values.
Current metering transformers
MI 5, MI 20, MI 100, MI 500.
For further information refer
to "Current Metering Transformers".
Left potentiometer:
Lower limit adjustable from 8
to 98% of max. value of 4 Vp.
Operation Diagram
Power supply
Upper limit
Hysteresis
Hysteresis
Lower limit
Relay ON
2