Timers Multifunction Types DMB01, PMB01 DMB 01 • Time range 0.1 s to 100 h • 7 knob selectable functions: Op delay on operate In interval Io interval on trigger open Id double interval Dr delay on release R symmetrical recycler ON first Rb symmetrical recycler OFF first • Knob selection of time range • Knob-adjustable time setting • Automatic or manual start • Repeatability: ≤ 0.2% • Output: 8 A SPDT or 8 A DPDT relay • For mounting on DIN-rail in accordance with DIN/EN 50 022 or Plug-in • 22.5 mm Euronorm or 36 mm Plug-in module housing • Combined AC and DC power supply • LED indication for relay status and power supply ON PMB 01 Product Description Ordering Key Multi-voltage timer with 7 knob selectable functions and 7 knob selectable time ranges within 0.1s and Housing Function Type Item number Output Power supply 100h. For mounting on DINrail (DMB01) or Plug-in (PMB01). DMB 01 C M24 Type Selection Mounting Output Housing Supply: 24 VDC and 24 to 240 VAC DIN-rail SPDT DPDT SPDT DPDT D-Housing DMB 01 C M24 P-Housing PMB 01 C M24 Plug-in DMB 01 D M24 PMB 01 D M24 Time Specifications Time ranges Knob Selectable Setting accuracy Repeatability Time variation Within rated power supply Within ambient temperature Reset Manual reset of time and/or relay Pulse duration Power supply interruption Automatic start Supply: 24 to 240 VAC/DC Output Specifications 0.1 to to 1 6 to 60 to 0.1 to 1 to 10 to ≤ 5% ≤ 0.2% 1s 10 s 60 s 600 s 1h 10 h 100h ≤ 0.05%/V ≤ 0.2%/ºC Close the trigger contact between pins A1 and Y1 or 2 and 5 ≥ 100 ms ≥ 200 ms Connect pins A1 and Y1 or 2 and 5 Specifications are subject to change without notice (15.12.05) Output Rated insulation voltage Contact Ratings (AgSnO2) Resistive loads AC 1 DC 12 Small inductive loads AC 15 DC 13 Mechanical life Electrical life SPDT or DPDT relay 250 VAC (rms) µ 8 A @ 250 VAC 5 A @ 24 VDC 2.5 A @ 250 VAC 2.5 A @ 24 VDC ≥ 30 x 106 operations ≥ 105 operations (at 8 A, 250 V, cos ϕ = 1) < 7200 operations/h Operating frequency Dielectric strength 2 kVAC (rms) Dielectric voltage Rated impulse withstand volt. 4 kV (1.2/50 µs) 1 DMB01, PMB01 Supply Specifications General Specifications Power supply Rated operational voltage through terminals: (DMB01C) A1, A2 (PMB01C) 2, 10 Power ON delay Indication for Power supply ON Output relays ON (DMB01D) A1, A2 (PMB01D) 2, 10 Voltage interruption Rated operational power AC supply DC supply Overvoltage cat. III (IEC 60664, IEC 60038) 24 VDC ±15% and 24 to 240 VAC +10%/-15%, 45 to 65 Hz 24 to 240 VAC/DC +10%/-15%, 45 to 65 Hz ≤ 10 ms 4 VA 1.5 W Function and Time Setting Upper knob: Setting of function: Op - delay on operate In - interval Io - interval on trigger open Id - double interval Dr - delay on release R - symmetrical recycler (ON first) Rb - symmetrical recycler (OFF first) Centre knob: Time setting on relative scale: 1 to 10 with respect to the chosen range. Environment Degree of protection Pollution degree Operating temperature Storage temperature Housing dimensions DIN-rail version Plug-in version Weight Screw terminals Tightening torque Approvals Lower knob: Setting of time range. CE Marking EMC Immunity Emission Timer Specifications keeps ON and a new time period starts. the relay operates again for the set delay period. If the trigger contact is opened before the end of the first time period the second one begins; if the trigger contact is closed before the end of the second time period the relay keeps ON and the first time period begins again. ≤ 100 ms LED, green LED, yellow (flashing when timing) (EN 60529) IP 20 3 (DMB01), 2 (PMB01) (IEC 60664) -20 to 60°C, R.H. < 95% -30 to 80°C, R.H. < 95% 22.5 x 80 x 99.5 mm 36 x 80 x 94 mm Approx. 130 g Max. 0.5 Nm according to IEC EN 60947 UL, CSA RINA (DMB01 only) Yes Electromagnetic Compatibility According to EN 61000-6-2 According to EN 61000-6-3 According to EN 61812-1 Mode of Operation Function Op Delay on operate The time period begins as soon as the trigger contact is closed. At the end of the set delay time the relay operates and doesn't release until the trigger contact is closed again or the power supply is disconnected. If the trigger contact is closed before the end of the delay time, the device resets and a new time period starts. Function In Interval The relay operates and the time period begins as soon as the trigger contact is closed. The relay releases at the end of this period or when the power supply is disconnected. The relay operates again when the trigger contact is closed again. If the trigger contact is closed before the end of the delay time, the relay 2 Function Io Interval on trigger open The relay operates and the time period begins as soon as the trigger contact is opened. At the end of the set delay or when the power supply is disconnected the relay releases. The relay operates again when the trigger contact is opened again. If the trigger contact is opened before the end of the delay time the relay keeps ON and a new time period begins. Function Id Double interval The relay operates and the time period begins as soon as the trigger contact is closed. The relay releases at the end of this period or when the power supply is disconnected. When the trigger contact is opened Function Dr Delay on release The relay operates as soon as the trigger contact is closed. The time period begins when the trigger contact is opened. The relay releases at the end of the set delay time or when the power supply is disconnected. The relay operates again when the input contact is closed again. If it is closed before the end of the delay time the relay keeps ON, a new time period begins as soon as the contact is opened again. Function R Symmetrical recycler, ONtime period first The relay operates and the time period begins as soon as the input contact is closed. After the set delay period the relay releases for the same time period. This sequence continues with equal ON- and OFF-time periods until the power supply is interrupted. Function Rb Symmetrical recycler, OFF-time period first The time period begins as soon as the input contact is closed. The relay is OFF during the set delay period, after this time it operates for the same time period. This sequence continues with equal OFF- and ON-time periods until power supply is interrupted. Specifications are subject to change without notice (15.12.05) DMB01, PMB01 Mode of Operation (cont.) ger contact without damaging the device (see wiring diagram). Additional Load It's possible to wire an additional load (i.e. a relay) between pins Y1 and A2, or 5 and 10, driven by the trig- Incorrect knobs Fast blinking Yellow LED working mode Timing: Slow blinking Relay ON: See operation diagrams position: Wiring Diagrams DMB 01 PMB 01 L(+) L(+) m A1 S m 18 26 16 m 28 2 S Y1 4 m 3 8 9 5 A2 10 25 15 11 1 PMB01C... PMB01D... PMB01D... DMB01C... DMB01D... DMB01D... N(-) N(-) Operation Diagrams Function Op - Delay on operate - Manual start Function In - Interval - Manual start Power supply Power supply Trigger input Trigger input T T T Relay ON ON T Relay ON ON OFF OFF LED LED Function Op - Delay on operate - Automatic start Power supply Function In - Interval - Automatic start Power supply T T T Relay ON ON T Relay ON ON OFF OFF LED LED Function Io - Interval on trigger open Function Id - Double interval Power supply Power supply Trigger input Trigger input T T Relay ON ON T OFF OFF LED Specifications are subject to change without notice (15.12.05) T Relay ON ON LED 3 DMB01, PMB01 Operation Diagrams (cont.) Function Dr - Delay on release Function R - Symmetrical recycler (ON first) Power supply Power supply Trigger input Trigger input T T Relay ON ON T T T Relay ON ON OFF OFF LED LED Function Rb - Symmetrical recycler (OFF first) Power supply Trigger input T T T T Relay ON ON OFF LED Dimensions Plug-in DIN-rail 94 80 63 28.5 4 90 36 63 99.5 83.5 80 22.5 28.5 Specifications are subject to change without notice (15.12.05)