Description
The IdentiFlex 602 (IF602SS) with Velociti® is ideally
suited for small- to medium-sized installations at commercial, institutional, and industrial life-safety projects.
The IF602SS can monitor and control up to 396 intelligent
analog addressable input/output points. The interactive
operator’s display uses LED prompting for ease of programming and user operation. The alphanumeric display
and keypad simplify field programming, or download programming from a Windows®-based application.
The IF602SS’s housing will fit between 16" studs for semiflush mounting. Access to system function keys is limited
by a key switch. Multiple levels of password protection prohibit unauthorized use. The circuit boards are mounted on
a removable chassis with pluggable terminal strips for ease
of installation and service.
Operator’s Display
The IF602SS’s operator’s display controls all user access
to the system. The display provides all of the necessary
keys and annunciation points to maintain and monitor the
system. Alarm, supervisory, and trouble conditions are all
indicated on the operator’s display by dedicated LEDs and
an internal sounder. The Acknowledge, Reset, and Signal
Silence keys are located directly below the 4 x 40-character backlit alphanumeric display. All system functions and
operational logic can be programmed from the front panel
in the field. The IF602SS display has four user-programmable function keys.
Analog Addressable Signaling Line Circuits
The IF602SS analog interface module provides Signaling
Line Circuits (SLC), loop circuits that can monitor and control up to 198 analog/addressable devices on each powerlimited loop, for a total of 396 analog points in a dual-loop
system. Loop wiring is polarity sensitive.
g2401ph1.jpg
The IF602SS has all the features of today’s most advanced
life safety systems. The integration of analog and addressable hardwired circuits allows system engineers to customize panels and maximize efficiency for any application.
IF602SS
Features
• One or two Signaling Line Circuits (SLC), up to 396
points
• Velociti protocol 99 detectors, 99 devices per Loop
• Velociti self-programming logic
• Downloadable or front-panel programmable
• Password protected
• Approved for Supervisory Service
• Fully digital SLC protocol
• SmartLink™ peer-to-peer networkable
• 1000-event history log
• Automatic drift compensation
• Coded signaling capability
• Adjustable sensor sensitivity and temperature settings
• Supervisory service
• Style 6 (Class A) or Style 4 (Class B) SLC
• Four Style Y (Class B), or two Style Z (Class A)
notification appliance circuits (NACs)
• Semi-flush mounting (between 16" studs)
• 160-character display
• Optional UDACT
• Built-in strobe and horn synchronization
SmartLink™ is a trademark and Velociti® Series is a registered trademark of
Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
An ISO 9000-2000 Company
SIGNALING
FM
S521
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2490 Rev. A3 page 1 of 3
©2008 Honeywell International Inc. All rights reserved.
Analog Addressable Signaling Line Circuits
(Continued)
Remote Display Network (Continued)
Each SLC loop has a dedicated microprocessor that simultaneously communicates with connected field devices and
the main CPU.
The IF602SS uses Velociti® fully digital communications
protocol to improve the speed and accuracy of event
reporting. The communications protocol provides for alarm
verification per detector, detector adjustability and compensation, adjustable analog heat detector range circuit isolation, and priority interrupts. Priority interrupts allow contacttype devices such as manual fire alarm stations to interrupt
the polling cycle and transmit their addresses at any time
during a polling sequence.
The fully digital protocol allows the IF602SS to operate on
most types of field wiring, greatly expanding its use in retrofit applications. Consult the Supplemental SLC Manual or
Tech Support for specific wiring requirements.
IF602SS Power Supply
The IF602SS power supply is a fully regulated 8 amp. supply that furnishes system operating and signaling power. It
is equipped with a battery charger which maintains the secondary power source. The power supply is monitored by
the main CPU, ensuring that adequate power levels are
available. The power supply design allows for high efficiency while providing precise power output. The battery
charger maintains batteries up to 26 AH. The supply powers four on-board Notification Appliance Circuits (NACs)
(two Class A) with multiple built-in synchronization protocols for System Sensor, Cooper-Wheelock and others.
An alphanumeric display can also be used for remote status and control. The alphanumeric display is designed to
communicate over the serial communications network.
The IF602SS can communicate locally or remotely with a
printer to document system activity.
See the RAN/SAN data sheet (CS-2025) for complete
annunciator details.
Applications
The IF602SS Analog Addressable Control Panel is
designed for new or retrofit small- to mid-sized projects that
require state-of-the-art life-safety systems. The embedded
CPU offers users unrivaled reliability without sacrificing
flexibility or value.
With compatible analog sensors and addressable input and
control interface devices, and its remote status and control
capabilities, the IF602SS provides system engineers with
all the tools necessary to design effective system solutions
for any application.
Architectural/Engineering Specifications
The control panel furnished and installed shall be capable
of supporting 396 addressable devices and two analog
loops. The panel shall utilize a fully digital Signaling Line
Circuit (SLC) protocol. The panel shall contain four onboard Notification Appliance Circuits (NACs) that support
multiple synchronization protocols. The panel shall utilize a
160-character Liquid Crystal Display (LCD) and a 1,000event history log. The panel shall be a Gamewell-FCI
IF602SS with Velociti.
Input (I) / Output (O) Devices
Addressable control output devices are the interface
between analog circuits and building functions. The outputs
are controlled with Control By Event (CBE) software within
the IF602SS, and can be programmed to respond to any
event. The control devices can be used as supervised
remote signaling circuits.
The IF602SS, with Gamewell-FCI’s complete line of 600
Series devices, provides a foundation for system design.
The IF602SS’s RS-232 output expands system monitoring
and control capabilities.
Remote Display and Control
Serial annunciator drivers are available in 16-point increments and are an ideal interface to graphic annunciators.
Switches can be used for Acknowledge, Reset, Signal
Silence, Drill, etc., to customize the remote status control
network.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2490 Rev. A3 page 2 of 3
www.gamewell-fci.com
Ordering Information
Specifications
Model
Common Control:
Standby Current:
Alarm Current:
Input Power:
0.125A
0.171A plus signaling circuit
power, plus 0.002A for master box,
or plus 0.022A for reverse-polarity
120 VAC, 3.0A; or 240 VAC, 1.5A
Auxiliary Output:
S+/S–, A+/A–, 2.0 A maximum
Common Relays:
1.0A @ 30 VDC, or 0.5A @ 250
VAC
Notification appliance circuits:
Circuits:
Output:
Analog SLC:
Standby Current:
Alarm Current:
Four Class B, two Class A.
3.0A maximum@24 VDC per circuit.
Maximum 8.0A total for all circuits.
198
396
0.045A
0.055A
0.045A
0.055A
Panel Dimensions:
Standard Cabinet:
20.0" H x 14.0" W x 4.5" D
XL Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.9 W x 13.97 D cm)
(50.8 H x 35.6 W x 11.4 D cm)
Battery Storage Dimensions:
Standard Cabinet:
6.0" H x 9.0" W x 4.5" D
(15.24 H x 22.86 x 11.43 D cm)
XL Cabinet:
14" H x 22.0" W x 5.5" D
(35.56 H x 55.88 W x 13.97 D cm)
Relative Humidity: 93% non-condensing
Temperature
32°F – 120°F (0°C – 49°C)
Rating:
Description
IF602SS-198R IF602SS Analog Addressable System
with Velociti consisting of the following:
• IF602SS common control
• 8 amp. main power supply
• One (1) analog circuit module
(198 analog addressable points)
• Standard cabinet assembly
(CAB-602R)
Standard Cabinet:
20.0” H x 14.0” W x 4.5” D
(50.8 H x 35.6 W x 11.4 D cm)
IF602SS-198XL 198 point/one SLC IF602SS in extra-large
housing allowing space for battery
storage (Refer to IF602SS-198R model
listed above).
Extra-large Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
IF602SS-396R IF602SS analog addressable system with
Velociti, consisting of the following:
• IF602SS common control.
• 8 amp main power supply.
• Two (2) analog circuits module
(396 analog addressable points).
• Standard cabinet assembly
(CAB-602R).
Standard Cabinet:
20.0” H x 14.0” W x 4.5” D
(50.8 H x 35.56 W x 11.43 D cm)
IF602SS-396XL 396 point/two (2) SLC IF602SS (refer to
IF602SS-396R above) in extra-large
housing, allowing space for battery
storage.
Extra-large Cabinet:
30.0" H x 22.0" W x 5.5" D
(76.2 H x 55.88 W x 13.97 D cm)
52358
IdentiFlex 602SS Analog/Addressable
Fire Alarm Control Panel Installation and
Operation Manual
31077
CTM-602, city-tie/remote signaling
module for 602 Series panels.
31078
ISO-232, RS-232 serial-port isolator
module for 602 Series panels.
31079
CLA-602, Class “A” adapter module for
SLC, 602 Series panels.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2490 Rev. A3 page 3 of 3