GAMEWELL-FCI IF610

600 Series
IdentiFlex 610
Analog Addressable Control Panel
Description
The IF610 can monitor and control up to 504 analog
addressable input/output points. Analog circuits are backed
up by Gamewell-FCI’s Default Alarm Mode for added security. The 1,000-event history log furnishes a complete
record of system activities. The interactive operator’s display uses LED prompting for ease of programming and
user operation. The alphanumeric display and keypad simplify field programming, or program from a PC using
Gamewell-FCI’s Smart Program II programmer.
The IF610’s cabinet will fit between studs for semi-flush
mounting. The compact design and key-activated deadfront construction enables secure routine maintenance of
the system. Access to system function keys is limited by a
key switch. Multiple levels of password protection prevent
unauthorized use. The circuit boards are mounted on a
removable chassis, and are designed with pluggable terminal strips for ease of installation and service.
Operator’s Display
The IF610’s operator’s display provides all user access to
the system. The display has all the necessary keys and
annunciation points to maintain and monitor the system.
Alarm, supervisory, and trouble conditions are indicated on
the operator’s display by dedicated LEDs and an internal
sounder. The Acknowledge, Reset, and Signal Silence
keys are located directly below the 4-line by 40-character
backlit alphanumeric display. All system functions and
operational logic can be programmed directly from the front
panel.
GF-2001ph.jpg
The IdentiFlex 610 (IF610) is suited for small- to mediumsized installations of commercial, institutional, and industrial life-safety applications. The IF610 offers all the features of today’s most advanced life safety systems. The
integration of analog and addressable hardwired circuits
allows system engineers to customize panels and maximize efficiency for a given application. The IF610 can be
networked with up to 256 other 600 Series panels using
Gamewell-FCI’s SmartLink™ peer-to-peer network.
IF610
Features
• One to four Signaling Line Circuits (SLC), up to 504
points.
• Polarity-insensitive SLC circuit wiring (XP95 protocol).
• SmartStart™ self-programming logic.
• Programmable by PC or front panel.
• Password protected.
• Approved for Suppressant Releasing and Supervisory
Service.
• Fully digital SLC protocol.
• SmartLink™ networkable.
• 1000-event history log.
• Automatic drift compensation.
• Coded signaling capability.
• Adjustable sensor sensitivity and temperature settings.
• Day/night sensitivity setting.
• Supervisory service.
• Style 6 (Class A) or Style 4 (Class B) SLC.
• Two Style Y (Class B), or two Style Z (Class A)
notification appliance circuits (NACs).
• Semi-flush mounting (between 16" studs).
• 160-character display.
• Optional integrated voice evacuation.
• Optional UDACT.
• Agent Releasing service.
SmartStart™ and SmartLink™ are trademarks of Honeywell International Inc.
An ISO 9000-2000 Com pany
SIGN AL IN G
FM
S521
APPRO VED
M EA
Approved
132-95-E
City of
Chicago
7165-1288:144 Approved
7170-1288:146 High Rise
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2001 Rev. A page 1 of 3
Analog Addressable Signaling Line Circuits
Remote Display and Control
The IF610 analog interface module provides one to four
Signaling Line Circuits (SLC), circuits that can monitor and
control up to 126 analog/addressable devices on each
power-limited circuit, for a total of 504 analog points in a
four-SLC system. Circuit wiring is not polarity sensitive.
System designers and engineers can add serial annunciators to display system activity and control. Serial annunciator drivers are available in 16-point increments and are an
ideal interface to graphic annunciators. Switches can be
used for Acknowledge, Reset, Signal Silence, Drill, etc., to
customize the remote status control network. An alphanumeric display can also be used for remote status and control. The alphanumeric display will communicate over the
serial communications network.
Each SLC has a dedicated microprocessor that simultaneously communicates with connected field devices and
the main CPU.
The IF610 uses XP95 fully digital communications protocol
for superior speed and accuracy of event reporting. This
protocol provides alarm verification per detector, detector
adjustability and compensation, adjustable analog heat
detector range (131°F to 194°F, 55°C to 90°C), circuit isolation, and priority interrupts. Priority interrupts allow contacttype devices such as manual fire alarm stations to interrupt
the polling cycle and transmit their addresses at any time.
With this fully digital protocol, the IF610 will operate on
most types of field wiring, greatly expanding its use in retrofit applications. Consult Gamewell-FCI Technical Support
for specific wiring requirements.
IF610 Power Supply
The IF610 power supply is a fully regulated 6 amp supply
that furnishes system operating and signaling power. It is
equipped with a battery charger which maintains the secondary power source. The power supply is monitored by
the main CPU, ensuring that adequate power is available.
The power supply design allows for high efficiency while
providing precise power output. The battery charger maintains batteries up to 26 AH. The supply powers two (2) onboard NACs (Class A or B).
I/O Devices
Addressable control output devices are the interface
between analog circuits and building functions. The outputs
are controlled by Control By Event (CBE) software within
the IF610, and can be programmed to respond to any
event. The control devices can also be used as supervised
remote signaling circuits.
The IF610’s RS-232 output expands system monitoring
and control capabilities.
The IF610 can communicate locally or remotely with a
printer to document system activity. See the RAN/SAN data
sheets (CS-2025 and CS-2027) for the complete
annunicator details.
Applications
The IF610 Analog Addressable Control Panel is designed
for new or retrofit small- to mid-sized projects that require
state-of-the-art life-safety systems. The embedded CPU
offers users unrivaled reliability.
With compatible analog sensors and addressable input and
control interface devices, and its remote status and control
capabilities, the IF610 provides system engineers with all
the tools necessary to design effective system solutions.
The IF610 can also control bulk fire-suppressant materials
releasing. The IF610 is capable of releasing the following
NFPA types of suppressant: 13 Sprinkler, 15 Water Spray,
11 Low-Expansion Foam, 16 Water Foam, 17 Dry Chemical, and 2001 Clean Agent.
Architectural/Engineering Specifications
The control panel furnished and installed shall be capable
of supporting 504 addressable devices and four (4) analog
SLCs. The panel shall use a fully digital Signaling Line Circuit (SLC) protocol. The panel shall contain two (2) Notification Appliance Circuits (NACs) that support multiple
synchronization protocols. The panel shall use a 160-character Liquid Crystal Display (LCD) and a 1,000-event history log. The panel shall be a Gamewell-FCI IF610.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2001 Rev. A page 2 of 3
Specifications
Ordering Information (Continued)
Common Control
Standby Current:
Alarm Current:
Model
Description
IF610-126XL 126 point/one SLC IF610 in extra-large
housing allowing space for battery storage.
(Refer to the IF610-126)
30.0” H x 22.0” W x 5.5” D
(76.2 H x 55.88 W x 13.97 D cm)
AAM610-252 Upgrades the IF610-126 to an IF610-252
System. Replaces the single analog circuit
card with a two-circuit card to provide a
total of 252 analog addressable points.
IF610-252
IF610 analog addressable system consisting of the following:
• IF610 common control that includes:
- Main CPU
- IF610 front display with LCD
alphanumeric display
- Bus Driver Module
- Common system relays
- Ribbon cables
• 6 amp main power supply
• Two (2) analog circuits module
(252 analog addressable points)
• Standard cabinet assembly
30.0” H x 22.0” W x 5.5” D
(76.2 H x 55.88 W x 13.97 D cm)
AAM610-504 Upgrades the IF610-252 or IF610-126 to an
IF610-504 system. Replaces the singleand/or two circuit analog card with a fourcircuit card to provide a total of 504 analog
addressable points.
IF610-504
IF610 analog addressable system consisting of the following:
• IF610 common control that includes:
- Main CPU
- IF610 front display with LCD alpha
numeric display
- Bus Driver Module
- Common system relays
- Ribbon cables
• 6 amp main power supply
• Four (4) analog circuits module
(504 analog addressable points)
• Standard cabinet assembly
20.0” H x 14.0” W x 4.5” D
(50.8 H x 35.56 W x 11.43 D cm)
IF610-504XL 504 point/four SLC IF610 in extra-large
housing, allowing space for battery storage
(Refer to the above IF610-504)
30.0” H x 22.0” W x 5.5” D
(76.2 H x 55.88 W x 13.97 D cm)
Input Power:
Auxiliary Output:
S+/S–, A+/A–:
Signaling Circuits:
Analog SLCs
IF610-126 points:
IF610-252 points:
IF610-504 points:
0.125A.
0.171A plus NAC power, plus
0.002A for master box, or plus
0.022A for reverse-polarity
120 VAC, 2.0A
24 VDC, 2.0A combined maximum
Common Relays:
1.0A @ 30 VDC, or 0.5A @ 250 VAC
24 VDC nominal @ 2.0A per circuit
Standby current 0.045A,
alarm current 0.045A
Standby current 0.055A,
alarm current 0.055A
Standby current 0.075A,
alarm current 0.075A
Panel Dimensions:
Standard Cabinet:
20.0” H x 14.0” W x 4.5”
(50.8 H x 35.56 W x 11.43 D cm)
XL Cabinet:
30.0” H x 22.0 W x 5.5” D
(76.2 H x 55.88 W x 13.97 D cm)
Battery Storage Dimensions:
8.0" H x 14.25" W x 6.0" D
(20.3 H x 36. W x 15.2 D cm)
Standard Cabinet: 6.0” H x 9.0” W x 4.5” D
(15.5 H x 22.86 W x 11.43 D cm)
XL Cabinet:
14” H x 22.0” W x 5.5” D
(35.56 H x 55.88 W x 13.97 D cm)
Relative Humidity: 93% non-condensing
Temperature Rating: 32° – 120°F (0° – 49°C)
Ordering Information
Model
IF610-126
Description
IdentiFlex 610 base analog/addressable
system consisting of the following:
• IF610 common control that includes:
- Main CPU
- IF610 front display with LCD
alphanumeric display
- Bus Driver Module
- Common system relays
- Ribbon cables
• 6 amp main power supply
• One (1) analog circuit module
(126 analog addressable points)
• Standard cabinet assembly
20.0” H x 14.0” W x 4.5” D
(50.8 H x 35.56 W x 11.43 D cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2001 Rev. A page 3 of 3