GAMEWELL-FCI 2400

2400
SYSTEM SENSOR
PHOTOELECTRONIC
SMOKE DETECTOR
DESCRIPTION
The System Sensor 2400 Series photoelectronic smoke detectors are specifically designed to meet the performance requirements of fire detection/alarm systems. These detectors
use state-of-the-art optical sensing chambers. The detectors
are designed to provide open area detection and are compatible with FCI fire alarm control panels. The detectors’ operation and sensitivity can be tested in place. The Model 2400T
unit has the same specifications as the Model 2400, but in addition it features a built-in fixed temperature (135o F) thermal
detection unit.
Each detector has an LED which flashes every ten seconds
indicating that power is being applied to the detector. The
LED lights steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
The 2400 and 2400T detectors include a tamper-resistant
feature that, when used, prevents removal of the detector
without the use of a tool.
Sensitivity testing is performed either by inserting a tool
into the recessed test switch opening or inserting a calibrated
test card according to the test procedures.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and test kit MOD 400R.
·
·
·
·
·
·
·
APPROVALS
·
·
·
FEATURES
Built-in Tamper-resistant Feature
Built-in Test Switch
Built-in Visual Alarm Indicator
Remote LED Option
Compatible with FCI Control Panels
Field Metering of Detector Sensitivity
Removable Insect Screen and Cover
for Field Cleaning
Sealed against Dirt, Insects, and Back
Pressure
Insect-resistant Screening
(.020"/.508mm openings)
Convenient Terminal Strip Wiring
TECHNICAL SPECIFICATIONS
Nominal sensitivity
Operating voltage
Operating current
Operating temperature
Operating humidity
Air velocity
Construction
Diameter
Height
Weight
3.0%/ft. obscuration
8.5 - 35 VDC (24 VDC nominal)
120 uA maximum
32o to 120o F (0o to 49o C)
10% to 93% relative humidity
3,000 fpm max.
Off-white flame-retardant plastic
5.5 inches (14 cm)
3.19 inches (8.0 cm) high,
0.7 lb. (310 gm)
NOTE: Alarm current is limited by control panel initiating device circuit.
ORDERING INFORMATION
Part Number
Model
2400
2400T
Description
Photoelectronic Detector
Photoelectronic Detector w/135o F thermal
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0587/Ver. 1.0
MOUNTING
· On a 4-inch square box with plaster ring
and FCI supplied mounting bracket kit. ÿ
Minimum depth 1.5 inches.
· On a 3.5 or 4-inch octagonal box.
Minimum depth 1.5 inches.
· Directly to ceiling using plastic screw
anchors.
VIEWS SHOWING POSITION OF TEST MAGNET
INSTALLATION
Line up the arrows on the detector with the arrows on
the mounting bracket. Turn the detector clockwise until
the detector clicks into place.
To use the tamper-proof feature, break the smaller tab
at the scribed line in the tamper-proof tab located on the
detector mounting bracket. Install the detector. To remove the detector from the bracket when using the tamper-proof feature, insert the blade of a small
screwdriver into the hole on the side of the base and
push the plastic lever away from the detector head. Turn
the detector counterclockwise for removal. NOTE: The
decorative ring must be removed in order to remove a
head after it has been made tamper-proof.
NOTE: The number of two-wire smoke detectors
which can be accommodated per zone varies with different control panels. Consult the control panel instruction manual to determine the capacity.
Refer to NFPA 72, Chapter 5-3 “Smoke Sensing Fire
Detectors”, for spacing, location of detectors and other
guidelines.
TESTING
Detectors may be tested locally in the following
ways:
· A. Insert a tool into the test opening in the unit.
For the complete procedure, refer to the Installation and Maintenance Instructions furnished
with each detector.
·
B. A test card with one end marked “ALARM”
and the other end marked “NO ALARM” is
furnished with each unit. For the complete
procedure, refer to the Installation and
Maintenance Instructions furnished with each
detector.
WARNING: To prevent detector contamination
during construction, smoke detectors must be
protected from dust and contamination until area
is clean and dust free. See NFPA 72-5-3.7.1.3
· C. Field metering of detector sensitivity may be
performed with the aid of a voltmeter and test
kit MOD 400R. For the complete procedure,
refer to the Installation and Maintenance
Instructions furnished with each detector.
MAINTENANCE
Cleaning programs should be adapted to the individual environment. in conformance with NFPA Standard
72. We recommend, at the least, an annual cleaning of
the unit. The detector screen and cover assembly can be
removed, revealing the sensing chamber. A vacuum
cleaner can be used to remove dust from the screen,
cover and sensing chamber. For the complete procedure, refer to the Installation and Maintenance Instructions furnished with each detector.
WIRING DIAGRAM FOR USE WITH FCI CONTROL PANELS
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control
Instruments, Inc. for their use. Specifications subject to change without notice.
© 2003 All Rights Reserved
2 of 2
9020-0587