ETC PIC01CB23AV0

Monitoring Relays
1-Phase True RMS AC/DC Over and Under Current
Types DIC01, PIC01
DIC01
PIC01
Product Description
DIC01 and PIC01 are precise
TRMS AC/DC over+under,
over+over or under+under
current and voltage (selectable
by DIP-switch) monitoring
relays. DIC01 can perform also
DC plus/minus measurement
by short circuiting pins Z3 and
Y1. The devices can be connected to the MI or MP and
A82 or E82 current transformers.
Both relays have two individual set levels with their own
• TRMS AC/DC over + under, over+over,
under+under current and voltage monitoring relays
• DC process signal plus/minus monitoring relay (DIC01)
• Selection of measuring range by DIP-switches
• Adjustable current and voltage on relative scale
• Adjustable hysteresis on relative scale
• Separately adjustable delay functions (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 1 or 2 x 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DIC01) or plug-in module (PIC01)
• 45 mm Euronorm housing (DIC01)
or 36 mm plug-in module (PIC01)
• LED indication for relay(s), alarm and power supply ON
• Galvanically separated power supply
Ordering Key
time delay. Only for DIC01
each set level can work with a
single SPDT relay.
Owing to the built-in latch
function, the ON-position of
the relay output can be maintained. Inhibit function can be
used to avoid relay operation
when not desired (maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relays.
Housing
Function
Type
Item number
Output
Power supply
Range
DIC 01 D B23 AV0
Type Selection
Mounting
Output
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DIN-rail
Plug-in
2 x SPDT
SPDT
DIC 01 D 724 AV0
PIC 01 C 724 AV0
DIC 01 D B48 AV0
PIC 01 C B48 AV0
DIC 01 D B23 AV0
PIC 01 C B23 AV0
Input Specifications
Input
Current level
Voltage level
DC levels (DIC01 only)
Current ranges
0.5 to 5 mA AC/DC
2 to 20 mA AC/DC
-5 to 5 mA DC
(DIC01
-20 to 20 mA DC
only)
Max. current for 1 s
Voltage ranges
0.1 to 1 V AC/DC
1 to 10 V AC/DC
0.4 to 4 Vp AC
-1 to 1 VDC
(DIC01
-10 to 10 VDC
only)
Max. voltage for 1 s
}
}
DIC01: Terminals Y1, Y2
PIC01: Terminals 6, 7
DIC01: Terminals Y1, Y3
PIC01: Terminals 5, 7
Connecting terminals Z3, Y1
Internal resis.
Max. curr.
50 Ω
35 mA
50 Ω
55 mA
50 Ω
35 mA
50 Ω
55 mA
100 mA
Internal resis.
Max. volt.
> 10 kΩ
7V
> 10 kΩ
20 V
> 10 kΩ
100 V
> 10 kΩ
7V
> 10 kΩ
20 V
100 V
Specifications are subject to change without notice (21.10.00)
CT ranges
MI and MP ranges (0.4 to 4 Vp input)
1-ph.:
3-ph.:
MI 5
MP 3005
MI 20
MP 3020
MI 100
MP 3100
MI 500
MP 3500
A82 ranges (2 to 20 mA input)
A82-10/20 25
A82-10/20 50
A82-10/20 100
A82-10/20 250
A82-10/20 500
E82-20 ranges (2 to 20 mA input)
E82-20 25
E82-20 50
Note:
The input voltage cannot
raise over 300 VAC/DC with
respect to ground (PIC01 only)
AAC rms
Max. curr.
0.5 to 5 A
2 to 20 A
10 to 100 A
50 to 500 A
20 AAC
50 AAC
250 AAC
750 AAC
2.5 to 25 A
5 to 50 A
10 to 100 A
25 to 250 A
50 to 500 A
30 AAC
60 AAC
120 AAC
300 AAC
600 AAC
2.5 to 25 A
5 to 50 A
50 AAC
100 AAC
1
DIC01, PIC01
Input Specifications (cont.)
Output Specifications
Note:
MP 3... current transformers
not suitable for under current
measurements due to the
output signal of the device
(see data sheet)
Contact input
DIC01
PIC01
Disabled
Enabled
Latch disable
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
1 or 2 x SPDT relays
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Supply Specifications
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DIC01)
2, 10 or 11, 10
(PIC01)
724:
B48:
B23:
Overvoltage cat. III
(IEC 60664, IEC 60038)
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
DC supply
2 kV
4 kV
4 kV
AC supply
4 kV
4 kV
4 kV
5 VA
3W
General Specifications
Power ON delay
Reaction time
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
Output relay ON
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 100 ms
< 100 ms
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
1 or 2 x LED(s), yellow
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
Din-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
(EN 60529)
IP 20
3 (DIC01), 2 (PIC01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
45 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 250 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
DIC01 and PIC01 monitor
both AC and DC current and
voltage. DIC01 can also
monitor positive and negative DC voltage connecting
terminals Y1 and Z3.
Example 1
(no contact input - under+over
voltage - 2 x SPDT N.D. relays
(1 x SPDT for PIC01) - TRMS)
DIC01: One relay operates
when the voltage drops below
the under voltage set point
for more than the respective
delay time. It releases when
2
the voltage exceeds the set
level plus the set hysteresis.
The other relay operates
when the voltage exceeds
the over voltage set point for
more than the respective
delay time. It releases when
the voltage drops below the
set level minus hysteresis.
PIC01: The relay operates
when the voltage drops below
the under voltage set level
for more than the respective
set delay time or when it
exceeds the over voltage set
level for more than the relative set delay time. The relay
releases when the voltage
exceeds the under voltage
set level plus hysteresis and
Specifications are subject to change without notice (21.10.00)
DIC01, PIC01
Mode of Operation (cont.)
it drops below the over voltage set level minus hysteresis (the hysteresis is the
same for both set levels).
Example 2
(latch enable active - under+under
current - 2 x SPDT relays (1 x
SPDT for PIC01) - TRMS)
DIC01: Each relay operates
and latches when the current
drops below the respective
set level for more than the respective delay time. Provided
that the current has exceeded
the respective set level plus
hysteresis, each relay releases when the contact input’s
connection is interrupted.
PIC01: The relay operates
when the current drops
below the higher set level for
more than the respective
delay time. Provided that the
current has exceeded the
higher set level plus hysteresis the relay releases when
the contact input’s connections is interrupted.
Note
Different delay times can be
used for appropriate reaction
according to the set points.
Example 3
(inhibit enable active - over+over
current with MI CT - DPDT
relay (SPDT for PIC01) - TRMS)
Provided that the contact
input’s connection is interrupted, the relay operates
when the current flowing in
the MI CT exceeds the lower
set level for more than the
respective delay time. It
releases when the current
drops below the lower set
level minus hysteresis or
voltage drops below the
under voltage set point for
more than the respective
delay time. It releases when
the voltage exceeds the set
level plus the set hysteresis.
The other relay operates
when the voltage exceeds
the over voltage set point for
more than the respective
delay time. It releases when
the voltage drops below the
set level minus hysteresis.
when the contact input’s
pins are connected.
Example 4
(inhibit enable active - over+over
current with A82-10 CT DPDT relay (1 x SPDT for
PIC01) - TRMS
Provided that the contact
input’s connection is interrupted, the relay operates
when the current flowing in
the A82-10 CT exceeds the
lower set level for more than
its delay time. It releases
when the current drops
below the lower set level
minus hysteresis or when the
contact input’s pins are connected.
In this case the spare front
label has to be placed on the
device for proper level
adjustment.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay(s) activation.
Example 5 (DIC01 only)
(no contact input - under+over
voltage - 2 x SPDT N.D. relays
- plus/minus DC
One relay operates when the
Function/Range/Level and Time Delay Setting
Selection of measuring range:
The selection between current
and voltage is automatically
selected through the input
connectors.
TRMS or positive/negative
DC monitoring selectable by
short-circuiting terminals Y1
and Z3 (DIC01 only).
DIP-switch selector (1 to 2)
Selection of function:
DIP-switch selector (3 to 6
and 1 A, 2 A)
3
Relay(s) de-energized in
normal condition.
Relay(s) energized in
normal condition.
4
12
ON
0.5 to 5 mA AC/DC
-5 to 5 mA DC
0.1 to 1 V AC/DC
-1 to 1 VDC
2 to 20 mA AC/DC
-20 to 20 mA DC
0.4 to 4 Vp AC
1 to 10 V AC/DC
-10 to 10 V DC
Power ON delay 1 ± 0.5 s
Power ON delay 6 ± 0.5 s
Set point 1 over voltage/current monitoring relay. The
alarm condition occurs when
voltage/current input is over the
set point value.
Set point 1 under voltage/current monitoring relay. The
alarm condition occurs when
voltage/current input is under
the set point value.
1A
5
Contact input as latch function enable. When the contact
is closed the latch function is
activated. The reset of the latch
condition occurs when the contact is open or by power down.
Contact input as inhibit of
alarm enable. When the contact is closed the relay remains
in normal position even if the
alarm condition occurs.
Specifications are subject to change without notice (21.10.00)
2A
6
ON
Set point 2 over voltage/current monitoring relay. The
alarm condition occurs when
voltage/current input is over the
set point value.
ON
2 x SPDT relays (DIC01)
1 x DPDT relay (PIC01)
Selection of level, time delay
and hysteresis:
Upper knob:
Setting of hysteresis on relative scale: 0 to 30% on set
value.
Centre knobs:
Current level setting on relative scale: 10 to 110% on full
scale.
Lower knobs:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
Set point 2 under voltage/current monitoring relay. The
alarm condition occurs when
voltage/current input is under
the set point value.
3
DIC01, PIC01
Wiring Diagrams
Example 1
L
Z1
PE
Example 1
24 VDC (+)
48/230 VAC 24/115 VAC
Y1
µ
A1
A3
16
L
µ
18 26
2
28
I
U
Y3
Y2
24 VDC (+)
48/230 VAC 24/115 VAC
PE
7
A2
Z3
15
10
6
Latch/inhibit
enable
µ
A1
A3
16
Y3
24 VDC (+)
48/230 VAC 24/115 VAC
L
µ
18 26
2
28
I
U
Y2
PE
A2
Z3
15
7
5
25
Latch/inhibit
enable
10
6
Example 3
µ
A1
A3
16
L
2
28
PE
PE
7
Latch/inhibit
enable
A2
Z3
15
3
5
25
10
6
24 VDC (+)
48/230 VAC 24/115 VAC
Y1
Y2
Example 4
24 VDC (+)
48/230 VAC 24/115 VAC
Latch/inhibit
enable
Z1
A82-10
A1
µ
A3
16
L
µ
18 26
28
2
I
U
A82-10 PE
7
Yellow
Y3
A2
Z3
15
Red
25
N (-)
Black
Example 5
1
N (-)
L
Black
5
µ
11
4
3
I
U
6
10
1
N (-)
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
PE
4
MI...
Y3
Example 4
PE
µ
11
I
U
N (-)
Red
1
24 VDC (+)
48/230 VAC 24/115 VAC
µ
18 26
I
U
Y2
Yellow
3
Latch/inhibit
enable
L
Y1
4
N (-)
24 VDC (+)
48/230 VAC 24/115 VAC
Z1
MI...
µ
11
I
U
N (-)
Example 3
1
Latch/inhibit
enable
L
PE
Example 2
24 VDC (+)
48/230 VAC 24/115 VAC
Z1
Y1
3
N (-)
N (-)
Example 2
4
I
U
5
25
µ
11
Y1
Y2
A1
µ
A3
16
µ
18 26
28
I
U
Y3
Z3
A2
15
25
N (-)
DIC01
4
PIC01
Specifications are subject to change without notice (21.10.00)
DIC01, PIC01
Operation Diagrams
Over+over voltage/current
Over+over voltage/current - Latch
Power Supply
Power Supply
Latch ON
Set Level 1
Hysteresis
Set Level 1
Hysteresis
Set Level 2
Hysteresis
RE1(DIC01)
Set Level 2
1 or 6 s
T1
1 or 6 s
T2
Hysteresis
T1
T2
RE1(DIC01)
1 or 6 s
T1
DPDT(DIC01)/RE(PIC01) 1 or 6 s
RE2(DIC01)
1 or 6 s
T2
Red LED ON
DPDT(DIC01)/RE(PIC01) 1 or 6 s
RE2(DIC01)
T1
T2
Red LED ON
Over+under voltage/current - N.E. relay(s)
Over+under voltage/current - Inhibit - N.E. relay(s)
Power Supply
Power Supply
Inhibit ON
Set Level 1
Hysteresis
Set Level 1
Hysteresis
Set Level 2
Hysteresis
1 or 6 s
RE1(DIC01)
T1
1 or 6 s
DPDT(DIC01)/RE(PIC01)
T
Hysteresis
1 or 6 s
T2
RE2(DIC01)
1 or 6 s
Set Level 2
T1
RE1(DIC01)
T1
1 or 6 s
T
T2
RE2(DIC01)
1 or 6 s
Red LED ON
DPDT(DIC01)/RE(PIC01)
T1
T1
T2
T1
Red LED ON
Under+under voltage/current
Power Supply
Set Level 1
Set Level 2
Hysteresis
Hysteresis
RE1(DIC01)
1 or 6 s
RE2(DIC01)
1 or 6 s
DPDT(DIC01)/RE(PIC01) 1 or 6 s
T1
T1
T2
T
Red LED ON
Specifications are subject to change without notice (21.10.00)
5