ETC DUA01C724500V

Monitoring Relays
1-Phase AC/DC Over Voltage - AC Over Current
Types DUA01, PUA01
DUA01
• AC/DC over voltage monitoring relay
• Selection of measuring range by DIP-switches
• Measuring ranges: 2 to 20 VAC/DC, 5 to 50 VAC/DC,
20 to 200 VAC/DC, 50 to 500 VAC/DC, 0.4 to 4 Vp AC
• Adjustable voltage limit on relative scale
• Adjustable hysteresis
• Programmable latching at set level
• Output: 8 A SPDT relay normally de-energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DUA01) or plug-in module (PUA01)
• 22.5 mm Euronorm housing (DUA01) or
36 mm plug-in module (PUA01)
• LED indication for relay and power supply ON
• Galvanically separated power supply
PUA01
Product Description
DUA01 and PUA01 are precise AC/DC over voltage
monitoring relays. They can
also be used as 1-phase or 3phase over current monitoring
relays when connected with
MI or MP current transformers.
Ordering Key
Owing to the built-in latch
function, the ON-position of
the relay output can be maintained.
The red LED indicates the
alarm status.
Housing
Function
Type
Item number
Output
Power supply
Range
DUA 01 C B23 500V
Type Selection
Mounting
Output
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DIN-rail
Plug-in
SPDT
SPDT
DUA 01 C 724 500V
PUA 01 C 724 500V
DUA 01 C B48 500V
PUA 01 C B48 500V
DUA 01 C B23 500V
PUA 01 C B23 500V
Input Specifications
Input (voltage level)
Measuring ranges
Direct
Selectable by DIP-switches
2 to 20 VAC/DC
5 to 50 VAC/DC
20 to 200 VAC/DC
50 to 500 VAC/DC
0.4 to 4 Vp AC
MI and MP CT ranges
1-ph.:
3-ph.:
MI 5
MP 3005
MI 20
MP 3020
MI 100
MP 3100
MI 500
MP 3500
Note:
The input voltage cannot
raise over 300 VAC/DC with
respect to ground (PUA01 only)
Contact input
DUA01
PUA01
Disabled
Enabled
Latch disable
Output Specifications
DUA01: Terminals Y1, Y2
PUA01: Terminals 5, 7
Int. resist.
Max. volt.
> 500 kΩ
600 V
> 500 kΩ
600 V
> 500 kΩ
600 V
> 500 kΩ
600 V
> 500 kΩ
600 V
Max. voltage for 1 s: 1000 V
AAC rms
Max. curr.
0.5 to 5 A
2 to 20 A
10 to 100 A
50 to 500 A
20 AAC
50 AAC
250 AAC
750 AAC
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
Specifications are subject to change without notice (21.10.00)
1
DUA01, PUA01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DUA01)
2, 10 or 11, 10
(PUA01)
724:
B48:
Reaction time
Alarm ON delay
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
Overvoltage cat. III
(IEC 60664, IEC 60038)
Alarm OFF delay
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
AC supply
2 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 VA
2W
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
< 100 ms
(voltage rising from
-20% to +20% set value)
< 300 ms
(voltage decreasing from
+20% to -20% set value)
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full-scale
LED, green
LED, red
(EN 60529)
IP 20
3 (DUA01), 2 (PUA01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 150 g
CE-Marking
Max. 0.5 Nm
acc. to IEC 60947
Yes
Example 2 (MI CT)
(no connection between terminals Z1, Y1 or 8, 9)
(no connection between terminals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates when the
current flowing through the
CT exceeds the set level. It
releases when the current
drops min. 4% below the set
level (see hysteresis) or when
power supply is interrupted.
The relay operates when the
maximum current flowing
through the CT exceeds the
set level. It releases when
the maximum current drops
min. 4% below the set level
(see hysteresis) or when
power supply is interrupted.
Mode of Operation
DUA01 and PUA01 monitor
both AC and DC over voltage.
When connected with MI or
MP
current
transformer
(using the 0.4 - 4 Vp range)
they can monitor 1-phase or
3-phase AC currents up to
500 A.
Example 1
(connection between terminals Z1, Y1 or 8, 9 - latch
function enabled)
The relay operates and latches
in operating position when
the measured value exceeds
the set level. Provided that
the voltage has dropped
min. 4% below the set point
(see hysteresis), the relay
releases when the interconnection between terminals
Z1, Y1 or 8, 9 is interrupted
or the power supply is interrupted as well.
Example 3 (MP CT)
Range - Level Setting
Selection of measuring
range:
DIP-switch selector (1 to 4)
1 234
ON
2
2 to 20 VAC/DC
5 to 50 VAC/DC
20 to 200 VAC/DC
50 to 500 VAC/DC
0.4 to 4 Vp AC
Centre knob:
Setting of voltage on relative
scale: from 10 to 110% of the
full-scale value.
Hysteresis:
Approx. 4% of set value, it
can be extended by inserting
a resistor between terminals
Z1, Y1 or 8, 9.
Approx. resistor values:
10%:
180 kΩ
25%:
47 kΩ
50%:
22 kΩ
75%:
15 kΩ
Latch: < 500 Ω
Specifications are subject to change without notice (21.10.00)
DUA01, PUA01
Operation Diagrams
Power supply
Power supply
Latch ON
Set level
Set level
Hysteresis
Hysteresis
Relay ON
Relay ON
Wiring Diagrams
Example 1
Example 1
Latch/Hysteresis 24 VDC (+)
48/230 VAC 24/115 VAC
adjustment
µ
L
Z1
PE
Ð
~
Y1
+
~
Y2
24 VDC (+)
48/230 VAC 24/115 VAC
Latch/Hysteresis
adjustment
A1
A3
14
9
U
PE
A2
µ
L
12
11
N (-)
Ð
~
7
+
~
5
2
8
4
11
3
U
10
1
N (-)
Example 2
Example 2
24 VDC (+)
48/230 VAC 24/115 VAC
Hysteresis
adjustment
µ
L
Z1
PE
~
Y1
~
Y2
A1
24 VDC (+)
48/230 VAC 24/115 VAC
Hysteresis
adjustment
A3
12
9
U
PE
A2
µ
L
14
11
~
7
~
5
8
2
11
4
3
U
10
N (-)
1
N (-)
Example 3
Example 3
24 VDC (+)
48/230 VAC 24/115 VAC
Hysteresis
adjustment
µ
L
Z1
PE
~
Y1
~
Y2
A1
24 VDC (+)
48/230 VAC 24/115 VAC
Hysteresis
adjustment
A3
12
9
PE
U
A2
µ
L
14
11
N (-)
DUA01
Specifications are subject to change without notice (21.10.00)
~
7
~
5
8
2
11
4
3
U
10
1
N (-)
PUA01
3