MA-COM 3100

Catalog 1308242
Issued 3-03 (PDF Rev. 3-04)
PRODUCTS UNLIMITED
Model 98 - 3100 series
Definite Purpose Contactor
3-pole, 20-40 FLA
AC Coil
File E75492
File EN60947-4-1:1991
IEC 947-4-1
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Features
Environmental Data
• 3-pole contactors.
• Industry-standard mounting plate.
• Optional interlock/auxiliary switches available.
• Manual test button is standard.
• Coil dust cover helps keep dust and dirt away from magnet and coil area.
• Double E magnet system provides optimal performance.
Temperature Range: Storage and Operating: -40°C – +65°C.
Flammability: UL 94-HB housing.
Mechanical Data
Contact Termination:
20, 25, 30 FLA Models
Type: #10-32 Screw with quad 0.250” (6.35 mm) quick connects.
Wire Size: 16-8 AWG (Stranding must be split for 8 AWG wire.)
Tightening Torque: 25 in.-lbs.
40 FLA Models
Type: Box Lug with dual 0.250” (6.35 mm) quick connects.
Wire Size: 14-4 Cu/Al AWG
Tightening Torque: 40 in.-lbs.
Coil Termination: Dual 0.250” (6.35 mm) quick connects, standard.
A 0.250” quick connect and a #6-32 screw, optional.
Arc Cover: Optional on 20-30 FLA models, standard on 40 FLA models.
Weight: 16 oz. (455 g) approximately
Contact Data @ 25°C
Arrangements: 3 Form X (3PST-NO-DM).
Maximum Ratings: See Contact Ratings Table.
Material: Silver Cadmium Oxide.
Coil Data @ 25°C
Voltage: 24 - 480 VAC, 50/60 Hz. See Coil Data Table below.
Insulation Class: UL Class B (130°C).
Duty Cycle: Continuous.
Contact Ratings
Full
Load
Amps
Number
of
Poles
20
3
25
Line
Voltage
240/277
480
600
Locked
Rotor
Amps
120
100
80
Resistive
Amps
Rating
30
30
30
3
240/277
480
600
150
125
100
35
35
35
30
3
240/277
480
600
180
150
120
40
40
40
40
3
240/277
480
600
240
200
160
50
50
50
Nominal Coil Voltage
Maximum Pickup Volts
Drop-Out Volts Range
Nominal Inrush VA @ 50 Hz
Nominal Inrush VA @ 60 Hz
Nominal Sealed VA @ 50 Hz
Nominal Sealed VA @ 60 Hz
Nominal DC Resistance - Ohms
24
18
6 -15
60
53
6.0
5
7
Voltage
110/120
200/240
480/600
110/120
200/208
240/277
480
600
110/120
200/208
240/277
480
600
110/120
200/208
240/277
480
600
Maximum Horsepower
Single
Phase
1.5
3
2
5
2
5
3
7.5
-
Three
Phase
7.5
7.5
7.5
10
15
20
10
10
15
20
10
10
20
25
Coil Data
Dimensions are shown for
832 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
120
88
20 - 70
60
53
6.0
5
180
208/240
177
40 - 140
60
53
6.0
5
720
Specifications and availability
subject to change.
277
220
65 - 185
60
53
6.0
5
950
480
384
150 - 270
65
53
6.0
5
3100
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Catalog 1308242
Issued 3-03 (PDF Rev. 3-04)
PRODUCTS UNLIMITED
Ordering Information
Typical Part No.
B
3100
-
30
Q
9
999
1. Series:
3100 = 3-pole, 20-40 FLA contactor
2.Packaging:
Y = Individual Pack
- = Bulk Pack
A-ZZZ = Customer specific information (assigned by factory)
3.Pole Configuration:
30 = 3 Form X (3PST-NO-DM)
4.Coil Voltage (50/60 Hz.):
Q = 24VAC
U = 208/240VAC H = 480VAC
J = 120VAC, molded
M = 277VAC, molded
T = 120VAC V = 277VAC
I = 24VAC, molded K = 208/240VAC, molded W = 480VAC, molded
5.Contact Ratings (Inductive):
7 = 20 FLA
8 = 25 FLA
9 = 30 FLA
10 = 40 FLA
6.Customer ID Suffix:
999 = Standard Model
000-998 = Factory assigned customer ID
7. Option Code:
Leave Blank = No customer-specific options
A - ZZ = Factory assigned customer-specific options.
Standard part numbers listed below are more likely to be available from stock.
3100-30Q9999CY
3100-30T9999CY
3100-30U9999CY
3100-30Q10999CG
3100-30T10999CG
3100-30U10999CG
Termination Options
Outline Dimensions
2.97
1.78 (75.44) 1.19
(45.21)
(30.23)
3.00
(76.2)
2.00
(50.8)
.250 TYP.
(6.35)
.253
(6.43)
3.25
(82.55)
.203 TYP.
(5.156)
.455 DIA.
(11.56)
3.39
(86.1)
2.0 MAX.
(50.8)
3.75
(95.25)
.125
.203 TYP.
(3.175)
(5.156)
2.375 TYP.
(60.325)
Shown with Optional Auxiliary Switches
Standard on
Special on
20, 25, 30, 35 FLA 20, 25, 30, 35 FLA
#10-32 Combination
#10-32 Sems
Phillips, Slotted &
Screw
5/16 Hex Head
with Pressure
#12 Washer
Plate
Standard
on 40 FLA
Lug accepts 14-4
Cu/Al AWG
ORDERING NOTE: “Standard” terminals need not be specified
in the “Ordering Information” chart above. “Special” terminals
are offered on a special order basis. Special order items may be
subject to extended leadtimes and significant minimum order
quantities. Your Tyco Electronics sales engineer must consult
with the factory before providing price and availability
information regarding items with these options.
Auxiliary Switches
Various interlock / auxiliary switches are available for the Model 98 contactor.
All auxiliary switches for the Model 98 are snap-on design, no tools required.
Equipped with 0.250” (6.35) Quick Connect Terminals
Factory Modifications
Contact Config.
NO
NC
Single unit interlock
1
0
configurations listed.
0
1
Maximum of two.
1
1
(One on each side.)
2
0
0
2
See footnote (1) for ratings.
2
2
SPDT Circuit
1
1
(Either one or two
2
2
switches per side.)
2
2
See footnote (2) for ratings.
4
4
SPDT Dry Circuit
1
1
0.1 amp max.
2
2
Gold Flashed Contacts
4
4
Description
ONE SPDT
SWITCH
PER SIDE
TWO SPDT
SWITCHES
PER SIDE
1 N/O / 1 N/C
Field Added Kits
Kit Catalog
Number of
Number
Kits Required
98220-303
1
98220-331
1
98220-332
1
98220-303
2
98220-331
2
98220-332
2
98220-337
1
98220-338
1
98220-337
2
98220-338
2
98220-341
1
98220-340
1
98220-340
2
Equipped with #6-32 Screw Terminals & Saddle Clamps
Footnotes: Ratings of Auxiliary Interlocks / Switches
(1) Contact Rating Single Circuit NO or NC and two circuit NO/NC:
120V 240V 480V 600V
Amperes - Break
3.0
1.5
0.75
0.6
Amperes - Make
30
15
7.5
6
Amperes - Continuous
10
10
10
10
(2) Contact Rating SPDT (337):
10A, 1/3 HP, 125 or 250 VAC
1/2A, 125 VDC; 1/4A, 250 VDC:
4A 120 VAC on Lamp Load
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Factory Modifications
Contact Config.
NO
NC
Single unit interlock
1
0
configurations listed.
0
1
Maximum of two.
1
1
(One on each side.)
2
0
0
2
See footnote (1) for ratings.
2
2
Description
Specifications and availability
subject to change.
Field Added Kits
Kit Catalog
Number of
Number
Kits Required
98220-303
1
98220-331
1
98220-332
1
98220-303
2
98220-331
2
98220-332
2
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
833