XMC0 Series DEFINITE PURPOSE

XMC0 Series
DEFINITE PURPOSE CONTACTORS
DESCRIPTION
American Zettlers XMC0 series of Definite Purpose Contactors are electromechanical switching devices designed ideally for the HVAC industry. The
most common applications of our contactors are found in refrigeration, air
conditioning and heating. Other applications include elevators, food service
equipment, cranes, hoists, welding machines, power supplies, vending
machines, lighting, pumps and compressors. XMC0 contactors are built to
the ARI 780/790 standard in our ISO 9001 manufacturing facility for high performance and great reliability. XMC0 is available in various pole configurations and load ratings up to 90 amps.
FEATURES
• A variety of termination options for specific application requirements
• Universal mounting plate: Easy replacement of competitor's contactors
• Heavy-duty contacts ensure long electrical life
• EE lamination (magnetic assembly) provides optimum performance
while reducing power consumption
• Performance unaffected by position mounting
• Dust-free internal construction
• SCCR (short circuit current rating) 100kA, 600VAC
• Class F Coil Insulation
• Offer complete line of auxilary contacts and micro switches
• Mechanical Interlock device offered - 2P, 2P/3P, and 3P
• UL, CUR file no. E222994
• Meets ARI 780/790 Guidelines
7/22/15
XMC0 Series
PART NUMBERING SYSTEM
XMC0 - 25 3 • E B B C - H 0 0 F G - XXXX
*
Full Load Amp
25
32
40
50
63
75
90
25 FLA
32 FLA
40 FLA
50 FLA
63 FLA
75 FLA
90 FLA
Custom Special Code
* N suffix - No coil cover
Power Terminals
Number of Poles
7
1
2
3
3A
1&2 Poles: Quad Terminals
3 Pole: Dual Terminals
D 1&2 Poles: Dual Terminals
G Without Any Terminals
3 Pole: Dual Terminals on the side
Q near coil terminals.
Quad Terminals on opposite side
1 Pole - Compact
1 Pole + 1 Shunt - Compact
2 Pole - Compact
3 Pole - Standard
2 Pole - Standard (3 Pole Frame)
Nil
Coil Voltage
D
E
F
I
L
N
U
50Hz
12 VAC
24 VAC
110-120 VAC
208-220 VAC
380-415 VAC
550-600 VAC
60Hz
12 VAC
24 VAC
110-120 VAC
208-240 VAC
277 VAC
440-480 VAC
550-600 VAC
Coil Terminals
1 & 2 Pole: Dual Terminals w/o screws
3 Pole: Single Terminal w/ screw
F 3 Pole: Dual Terminals w/ screws
Nil
Auxiliary Contacts & Microswitch
Right Side
Left Side
*550-600V coil not available in 50A or greater models.
Mounting Plate
A Plastic Base
B Metal Plate
Metal Plate with
C
DIN Rail mounting *
Cover
A Long Cover
B Short Cover
* Available for 50 &63 Amp versions
only
Terminal with Quick Connects
B Sems Clamp
C Slotted & Hex Head Washer
D Box Lug
Box Lug (Line)
E
Slotted & Hex Head Washer (Load)
Box Lug (Load)
F
Slotted & Hex Head Washer (Line)
Contact Material
Nil* AgSnO2
H
AgCdO
*Contact option available in 40A
version only. All other amperages
use AgCdO
0
1
3
4
5
6
1P
3P
4P
5P
6P
L
L1
L2
R
R1
R2
AUXILARY CONTACTS
None (Standard)
1NC+1NO, pressure plate screws w/ QC
1NC, pressure plate screws w/ QC
1NO, pressure plate screws w/ QC
2NC, pressure plate screws w/ QC
2NO, pressure plate screws w/ QC
1NC+1NO, pressure plate screws
1NC, pressure plate screws
1NO, pressure plate screws
2NC, pressure plate screws
2NO, pressure plate screws
MICROSWITCH
Left 2 SPDT
Left SPDT Postion 1
Left SPDT Postion 2
Right 2 SPDT
Right SPDT Postion 1
Right SPDT Postion 2
7/22/15
XMC0 Series
DEFINITE PURPOSE CONTACTORS
GENERAL DATA
Rated insulation voltage
Di-electric strength
Designs/conforms to
Agency approvals
Operating position
Operating altitude
Ambient temperature
Shock resistance
(1/2 ~ wave) = 11ms
Vibration resistance (5-300Hz)
Weight
Torque
QC Wiring
690 Vrms
2500Vrms (coil to contact & contact to contact)
IEC 60947-4-1, GB14048.4, EN60947-4, ARI780 / 790
UL,CUR file E220475
Vertical and Horizontal mounting recommended
2000 meters without derating
Operating: -25°C to 70°C *
Storage -40°C to 70°C
Contact Open: 6g ; Contact Closed: 15g
Contact Open: 2g ; Contact Closed: 4g
20-40A: 230-420g, 50/63A: 650g, 75/90A: 1550g
Screws 25 lb-in/Lugs 40 lb-in for 20-40FLA types
Screws 45 lb-in/Lugs 50 lb-in for 50-63FLA types
Screws 50 lb-in/Lugs 60 lb-in for 75-90FLA types
Screws 8 lb-in for Auxiliary Contact Blocks
Coil Screws 8 lb-in for 3-pole 30-40FLA and 12 lb-in for
50-90FLA types
Main Screws 12 lb-in/Auxiliary Screws 8 lb-in/
Coil Screws 8 lb-in for small frame types
The female connector should meet IEC 60760, necessary
to ensure the reliability of connection between female
connectors and QC terminals
* The overall combined temperature must not exceed the coil insulation max temperature of 155C.
ELECTRICAL
Rated Operating Voltage
Make Capacity (230V, cos Ø=0.45)
Break Capacity (230V, cos Ø=0.45)
Switching Frequency
Electrical Endurance
Mechanical Endurance
SCCR (UL508)
12-600VAC max
12 x FLA
10 x FLA
360 operations/hour
250,000
1,000,000
100kA, 600VAC
AUXILIARY CONTACT BLOCK DATA
MICROSWITCH BLOCK DATA
Conventional Thermal Current (A)
10
Rated Insulation Voltage (V)
690
A600 (AC-15)
230/380V
3/1.9
N600(DC-13)
110/230V
2.2/1.1
Rated
Operational
Current
(A)
Max. Rating
22A at 250 VAC. General use, 6K cycles
7/22/15
XMC0 Series
DEFINITE PURPOSE CONTACTORS
ELECTRICAL RATINGS
Size
Full Load Resistive
Amps Load Amps
(FLA)
(RLA)
Compact
Standard
Locked Rotor Amps (LRA)
240VAC
480VAC
600VAC
Pole Form
Order Number
1P
1P+1shunt
2P
1P
1P+1shunt
2P
1P
1P+1shunt
2P
2P
3P
2P
3P
2P
3P
XMC0-257
XMC0-251
XMC0-252
XMC0-327
XMC0-321
XMC0-322
XMC0-407
XMC0-401
XMC0-402
XMC0-253A
XMC0-253
XMC0-323A
XMC0-323
XMC0-403A
XMC0-403
200
3P
XMC0-503
300
240
3P
XMC0-633
450
375
300
3P
XMC0-753
540
450
360
3P
XMC0-903
25
32
150
125
100
32
40
180
150
120
40
50
240
200
160
25
32
150
125
100
32
40
180
150
120
40
50
240
200
160
50
63
300
250
63
80
360
75
95
90
120
COIL DATA
Pole Form
1 pole, 1 pole + 1 shunt
2 pole
3 pole, 2 pole standard (3A)
3 pole -503 & 633
3 pole -753 & 903
Inrush
Sealed
VA
VA
50Hz 60Hz 50Hz 60Hz
33
31
8
6
33
31
8
6
72.5 65
13
10
114 110 19
14
295 282 44
33
Sealed
(W)
3.5
4
5
7
12
Pickup
Voltage
Dropout
Voltage
< 0.8 Us* > 0.2 Us*
*Us = nominal coil voltage. VA data at nominal coil voltage, ambient temperature 25C.
7/22/15
XMC0 Series
DEFINITE PURPOSE CONTACTORS
DIMENSIONS
Figure 1 - 1 Pole Contactor (metal base, 25-40FLA)
52
59
41
4 5 0 .5
3 8 0 .5
16
81
27
5.2
0.5
Figure 2 - 1 Pole + Shunt Contactor (metal base, 25-40FLA)
7/22/15
XMC0 Series
DEFINITE PURPOSE CONTACTORS
81
4 5 0 .5
3 8 0 .5
16
27
5 .2
4 1 0.5
59
50
Figure 3 - 2 Pole Contactor (metal base, 25-40FLA)
5 0. 4
3 8 0 .5
7 9. 5
92 .5
0 .5
5 .2
8 2 0 .5
78
5 .2
61
0.5
5.2
Figure 4 - 3 Pole Contactor (metal base, 25-40FLA)
7/22/15
XMC0 Series
80
8 2 .5
1 0 2 .6
0 .5
5 .2
5 .2
DEFINITE PURPOSE CONTACTORS
3 8 0 .5
73
84
5 7 0 .5
5 .2
5.
2
12 7
1 1 2 .5 0 . 5
1 1 7 . 5 0 .5
5.2
Figure 5 - 3 Pole Contactor (metal base, 50-63FLA)
89
1 1 3 .5
6 3 0 .5
7 3 0.5
Figure 6 - 3 Pole Contactor (metal base, 75-90FLA)
7/22/15
XMC0 Series
MICROSWITCH
AUXILIARY CONTACT
Position 1
Position 2
INTERLOCKS
Ordering Information:
In XMC0 Part Number, replace “Number of Poles” selection with J22 (2 2P), J23 (1 2P & 1 3P), J32 (1 3P & 1 2P), or J33 (2 3P). Interlock
Pole Order is left to right for 2P or 3P.
25-40A C03J0
50-63A C03J1
75-90A C03J2
Interlock Block Fastener (2X)
7/22/15