Series Reversing Relay/
Synchronization Module
Model
RRS-MOD
RRS-MOD
Reversing relay/synchronization module
for i3 series sounder models
Product Overview
Compatible with 2- and 4-wire i3 detectors equipped with a sounder
System Sensor’s RRS-MOD reversing relay/synchronization module enhances the
operation of 2- and 4- wire i3 series detectors equipped with a sounder.
Activates all i3 sounders on a loop when
one alarms
Installation ease. The RRS-MOD includes a Velcro attachment for easy installa-
i3
Synchronizes all sounders on the loop
for a clear alarm signal
Can be used with bell/alarm, alarm relay,
or NAC outputs
Includes a field-selectable switch to
accommodate both coded and continuous alarm signals
Allows i3 detector silencing from the
panel or keypad
Operates on 12- and 24-volt systems
Quick-connect harness and color coded
wires facilitate connections
tion into the fire alarm control panel cabinet. A quick-connect harness and
color-coded wires simplify connections.
Intelligence. The RRS-MOD’s design is flexible to accommodate virtually any
application. The RRS-MOD is compatible with both 2- and 4-wire i3 series
detectors operating over 12V and 24V systems. The module can be used with
either bell/alarm, alarm relay, or NAC outputs, and its field-selectable switch
accommodates both coded and continuous alarm signals.
Instant inspection. To meet fire alarm requirements, the RRS-MOD activates all
i3 sounders on a loop when one alarms. Additionally, the RRS-MOD synchronizes the output of the i3 sounders, regardless of whether the panel’s alarm signal is continuous or coded, to ensure a clear alarm signal.
Architect/Engineer Specifications
Reversing relay/synchronization module
shall be a System Sensor i3 Series model
number RRS-MOD, listed to Underwriters
Laboratories as a smoke detector accessory.
The module shall allow all 2-wire and 4wire i3 Series detectors equipped with a
sounder on a loop to sound when one
alarms. The module shall provide a switch
to toggle between coded mode and continuous mode. When in coded mode, the module shall synchronize the i3 sounders on the
loop to mirror the input signal. When in
continuous mode, the module shall synchronize the i3 sounders on the loop to the
ANSI S3.41 temporal coded pattern. In
either coded or continuous modes, the
RRS-MOD module shall permit sounders
to be silenced at the panel. The RRS-MOD
module shall operate between 8.5 and 35
VDC, and shall provide 18 AWG stranded,
tinned conductors connected to a quickconnect harness.
Avg. Operating Current
Relay Contact Rating
25mA
2 A @ 35 VDC
Electrical Specifications
Operating Voltage
Nominal:
12 / 24 V
Min.:
Max.:
8.5 V
35 V
Physical Specifications
Operating Temperature Rangez
Operating Humidity Range
Wire Connections
32°F–131°F (0°C–55°C)
5% to 85% non-condensing
18 AWG stranded, tinned, 16″ long
Dimensions
Height:
2.5 inches (63 mm)
Width:
2.5 inches (63 mm)
Depth:
1 inch (25 mm)
2-Wire System Triggered from Alarm/Bell Circuit:
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
EOL
BROWN
OUT+
2–WIRE +
INITIATING
DEVICE
–
CIRCUIT
YELLOW
IN+
ORANGE
IN–
WHITE
OUT–
1 + IN
1 + IN
2 + OUT
2 + OUT
3 - IN/OUT
3 - IN/OUT
4 RA+
4 RA+
5 RA-
5 RA-
+
+
RED
PWR+
–
BLACK
PWR–
AUX POWER
+
–
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
S0101-00
2-Wire System Triggered from Alarm Relay Contact:
UL LISTED
ALARM
CONTROL
PANEL
ALARM
RELAY
(NO Contact)
NOTE:
These diagrams represent
two common wiring methods.
Refer to the RRS-MOD
installation manual for additional wiring configurations.
PURPLE
T+
EOL
BROWN
OUT+
2–WIRE +
INITIATING
DEVICE
–
CIRCUIT
YELLOW
IN+
ORANGE
IN–
WHITE
OUT–
1 + IN
1 + IN
2 + OUT
2 + OUT
3 - IN/OUT
3 - IN/OUT
4 RA+
4 RA+
5 RA-
5 RA-
+
+
RED
PWR+
–
BLACK
PWR–
AUX POWER
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
+
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
S0103-00
Ordering Information
Model
Description
RRS-MOD
Reversing relay/synchronization module for i3 series smoke detectors
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
Documents-on-Demand
800/736-7672 x3
www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.524.6253
Fx: 86.29.524.6259
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor Europe
Ph: 44.1403.276500
Fx: 44.1403.276501
System Sensor in Singapore
Ph: 65.6273.2230
Fx: 65.6273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
©2002 System Sensor. The company reserves the right to change product specifications without notice.