MACOM WUVT

Voltage Sensitive Relays
WILMAR™ Protective Relays – WUVT/WOVT Series
Function: 27/59
• ANSI/IEEE C37.90-1978
TERMINAL STRIPS
#6 - 32 SCREWS
• UL file No. E58048
• CSA file No. LR61158
Undervoltage Models - The relay is energized at
normal voltage, N.C. contacts will open and N.O.
contacts will close. The relay will de-energize when
the voltage drops and remains below the U/V set
point for the duration of the set time delay.
3.0
Overvoltage Models - The relay is de-energized at
normal voltages, N.C. contacts are closed and N.O.
contacts are open. The relay will energize, when the
voltage rises and remains above the O/V set point for
the duration of the set time delay.
3
4
1 /8
1 /2
5 /8
4
3
1 /2
4
1 /4
/ DIA.
4 MTG. HOLES
Single Phase
Three Phase
13 64"
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
Part Number
WUVT/WOVT
Nominal Voltage ...............................
100 VAC to 575 VAC
Phase ................................................
Single or Three
Line Frequency .................................
50-400 Hz
Pick-up to Drop-out Differential ......
1% typical
Drop-out Point (u/v models) ...........
70-100% of nominal voltage, screwdriver adjustable
Pick-Up Point (o/v models) .............
100-125% of nominal voltage, screwdriver adjustable
Output Contacts ...............................
One set N.O, One set N.C.
Contact Ratings ................................
5 amp resistive at 120 VAC or 28 VDC
Operating Temperature Range ........
-40°C to +70°C
Power Consumption ........................
3 VA maximum
Time Delay ........................................
0.5 to 20 seconds, screwdriver adjustable
Voltage Reset ...................................
The reset is automatic when voltage returns to normal.
Notes:
1. Remove black screws for access to the voltage and time delay adjustment potentiometer.
2. Clockwise rotation of the voltage adjust potentiometer will raise the voltage trip point.
3. Clockwise rotation of the time adjust potentiometer will increase the time delay (Pick-up
time for O/V models, drop-out time for U/V models).
4. The adjustments are single turn potentiometers, use a small screwdriver and do not force
beyond the limit stops.
5. On U/V models, when the voltage falls to approximately 33% of nominal or below, the relay
will drop out in 0.150 to 0 .300 seconds, regardless of the time delay setting.
PART NUMBER SELECTION
Sample Part No.
WUVT-1-120
Type:
WUVT - Undervoltage
WOVT- Overvoltage
No. Phases
1 = Single
3 = Three (line to line)
Line Voltage VAC
100
240
115
380
120
416
150
440
200
460
208
480
220
525
230
575
Options:
Blank - Standard
A = 2 Form A Contacts
B = 2 Form B Contacts
H = 125VDC 3A Contacts
P = Transient Protection
Transient Protection - All voltage relays will withstand
momentary voltage surges of twice the nominal rated
input voltage (standard).
Option "P" provides additional transient protection
which complies with the requirements of ANSI/IEEE
C37.90-1978
Consult factory for additional models.