OMRON XW2B

Standard-type Connector-Terminal Block Conversion Units
XW2B
CSM_XW2B_DS_E_3_1
Simplifies Connector and terminal
block replacement, and requires less
in-panel wiring.
• Mount to DIN Track or via screws.
• MIL Flat Cable Connectors and Multi-pole, Square
Connectors are standard.
• Terminal blocks available with either M3 or M3.5 screws.
• Connecting Cables for Programmable Controllers
available (sold separately).
Ordering Information
Connectors
Type
Terminal Block
Connector
Terminal block with
M3 screws
Flat Cable
Terminal block with
M3.5 screws
Flat Cable Connectors
*1
Twin-connector
No. of poles
Appearance
Model
20
XW2B-20G4
34
XW2B-34G4
40
XW2B-40G4
50
XW2B-50G4
60
XW2B-60G4
20
XW2B-20G5
34
XW2B-34G5
40
XW2B-40G5
50
XW2B-50G5
60
XW2B-60G5
40
XW2B-40G5-T
20
XW2B-20G5-D
20
XW2B-20Y4
34
XW2B-34Y4
50
XW2B-50Y4
20
XW2B-20Y5
34
XW2B-34Y5
50
XW2B-50Y5
20
XW2B-20X5
34
XW2B-34X5
50
XW2B-50X5
40
XW2B-40F5-P
Terminal block with
M3.5 screws
Daisy Chain
Terminal block with
M3 screws
Multi-pole, Square
Connector
Terminal block with
M3.5 screws
Board I/O
Terminal block with
M3.5 screws
Multi-pole, Square Connector
Plugs
*2
Multi-pole, Square Connector
Plugs
*2
Multi-pole, Square Connector
Plugs
*3
*1. Flat Cable Connectors have one polarity slot.
*2. These Plugs and Sockets are made by Honda Tsushin Kogyo.
*3. These Plugs are made by Fujitsu.
Accessories (Order Separately)
Connecting Cables for Connector-Terminal Block Conversion Units
For details on the Connecting Cable used between XW2B Daisy Chain-type Connectors, refer to the XW2Z datasheet.
1
XW2B
Ratings and Specifications
Type XW2B-@@G@
Flat Cable Units
Item
XW2B-@@Y@
XW2B-40F5-P
Multi-pole, Square-connector Units Board I/O Unit
Rated current
1A
Rated voltage
125 VAC
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
500 VAC for 1 min (leakage current: 1 mA max.)
Ambient operating
temperature
0 to 55°C
Dimensions
(Unit: mm)
Flat Cable Units with a Terminal Block with M3 Screws
XW2B-@@G4
Flat Cable Connector (MIL Plug)
A
3.5
3.5
15.5
29.5
45
Two,
3.5 dia.
5.08
Terminal Block
(45.3)
38.1
Wiring Diagram
Flat Cable
Connector
(mating side)
20.5
2
4
N-2
N
1
3
N-3
N-1
DIN Track lock
Dimensions
Triangular mark
Model
N-3
3
1
N-1
Terminal Block
(terminal side)
2
4
N-2
N
Note: All pins on the Flat Cable Connector correspond
1-to-1 to the terminal of the same number on the
terminal block as shown above.
No. of poles Dimension A (mm) Applicable Connector models *1
XW2B-20G4
20
67.5
XG4A-2031
XW2B-34G4
34
112.5
XG4A-3431
XW2B-40G4
40
135.0
XG4A-4031
XW2B-50G4
50
157.5
XG4A-5031
XW2B-60G4
60
180.0
XG4A-6031
*Flat Cable Connectors have one polarity slot.
Note: Terminal block pitch is 5.08 mm.
Use a wire size between 0.3 and 1.25 mm2 (AWG22 to AWG16).
The wire insertion holes are 1.8 × 2.5 (H × W) mm.
Applicable Connectors
Applicable Connectors (order separately)
Model
Flat Cable Connectors, MIL Sockets with
Strain Reliefs
Discrete-wire IDC Connectors, Double-row Sockets
Connectors *1
Semi-covers *2
XG5S-1001
XW2B-20G4
XG4M-2030-T
XG5M-2032-N
XG5M-2035-N
XW2B-34G4
XG4M-3430-T
XG5M-3432-N
XG5M-3435-N
XG5S-1701
XW2B-40G4
XG4M-4030-T
XG5M-4032-N
XG5M-4035-N
XG5S-2001
XW2B-50G4
XG4M-5030-T
XG5M-5032-N
XG5M-5035-N
XG5S-2501
XW2B-60G4
XG4M-6030-T
XG5M-6032-N
XG5M-6035-N
XG5S-3001
*1. Either the XG5M-@@32-N or the XG5M-@@35-N may be used.
*2. Each Connector requires two Semi-covers.
2
XW2B
Flat Cable Units with a Terminal Block with M3.5 Screws
XW2B-@@G5
Flat Cable Connector (MIL Plug)
3.5
3.5
15.5
29.5
45
Two,
3.5 dia.
7
8.5
7.3
Terminal
Block
7
43.5 (45.3)
Wiring Diagram
Flat Cable
Connector
(mating side)
2
4
1
3
20.5
N-2
N
N-3
N-1
DIN Track lock
Dimensions
Triangular mark
Model
N-3
3
1
N-1
Terminal Block
(terminal side)
2
4
N-2
N
Note: All pins on the Flat Cable Connector correspond
1-to-1 to the terminal of the same number on the
terminal block as shown above.
No. of poles Dimension A (mm)
Applicable Connector models *
XW2B-20G5
20
112.5
XG4A-2031
XW2B-34G5
34
180.0
XG4A-3431
XW2B-40G5
40
202.5
XG4A-4031
XW2B-50G5
50
247.5
XG4A-5031
XW2B-60G5
60
292.5
XG4A-6031
*Flat Cable Connectors have one polarity slot.
Note: Terminal block pitch is 8.5 mm.
Applicable Connectors
Applicable Connectors (order separately)
Model
Flat Cable Connectors, MIL Sockets with
Strain Reliefs
Discrete-wire IDC Connectors, Double-row Sockets
Connectors *1
Semi-covers *2
XW2B-20G5
XG4M-2030-T
XG5M-2032-N
XG5M-2035-N
XG5S-1001
XW2B-34G5
XG4M-3430-T
XG5M-3432-N
XG5M-3435-N
XG5S-1701
XW2B-40G5
XG4M-4030-T
XG5M-4032-N
XG5M-4035-N
XG5S-2001
XW2B-50G5
XG4M-5030-T
XG5M-5032-N
XG5M-5035-N
XG5S-2501
XW2B-60G5
XG4M-6030-T
XG5M-6032-N
XG5M-6035-N
XG5S-3001
*1. Either the XG5M-@@32-N or the XG5M-@@35-N may be used.
*2. Each Connector requires two Semi-covers.
3
XW2B
Twin-connector Units with a Terminal Block with M3.5 Screws
XW2B-40G5-T
Flat Cable Connector (MIL Plug: XG4A-2031 × 2)
3.5
202.5
3.5
15.5
29.5
45
Two,
3.5 dia.
7
8.5
7.3
7
Terminal Block
43.8 (45.3)
2
20.5
Wiring Diagram
DIN Track lock
Flat Cable
Connector
(mating side)
2
4
20
22
38
40
1
3
19
21
37
39
37
39
Triangular
mark
Triangular mark
Terminal Block
(terminal side)
3
1
2
21
19
4
20
38
22
40
Note: All pins on the Flat Cable Connector correspond 1-to-1 to the terminal of
the same number on the terminal block as shown above.
Applicable Connectors
Applicable Connectors (order separately)
Model
XW2B-40G5-T
Flat Cable Connectors, MIL Sockets with
Strain Reliefs
XG4M-2030-T
Discrete-wire IDC Connectors, Double-row Sockets
Connectors *1
Semi-covers *2
XG5M-2032-N
XG5M-2035-N
XG5S-1001
*1. Either the XG5M-@@32-N or the XG5M-@@35-N may be used.
*2. Each Connector requires two Semi-covers.
4
XW2B
Daisy Chain Units with a Terminal Block with M3.5 Screws
XW2B-20G5-D
3.5
Flat Cable Connector (MIL Plug: XG4A-2031 × 2)
135
3.5
15.5
29.5
45
Two,
3.5 dia.
7
7.3
8.5
7
Terminal Block
43.8 (45.3)
2
20.5
Wiring Diagram
DIN Track lock
Flat Cable
Connector
(mating side)
2
20
2
20
1
19
1
19
Triangular mark
Triangular mark
Terminal Block
(terminal side)
19
1
2
20
Note: All pins on the Flat Cable Connector correspond 1-to-1 to the terminal
of the same number on the terminal block as shown above.
Applicable Connectors
Applicable Connectors (order separately)
Model
XW2B-20G5-D
Flat Cable Connectors, MIL Sockets with
Strain Reliefs
XG4M-2030-T
Discrete-wire IDC Connectors, Double-row Sockets
Connectors *1
Semi-covers *2
XG5M-2032-N
XG5M-2035-N
XG5S-1001
*1. Either the XG5M-@@32-N or the XG5M-@@35-N may be used.
*2. Each Connector requires two Semi-covers.
5
XW2B
Multi-pole, Square-connector Plug Units with a Terminal Block with M3 Screws
XW2B-@@Y4
Multi-contact Connector (Plug)
A
3.5
3.5
15.5
29.5
45
Two,
3.5 dia.
Terminal Block
5.08
Wiring Diagram (Example for Terminal
Block with 50 Poles)
2
38.1
20.5
DIN Track lock
2
1
Multi-contact,
Square Connector
(mating side)
16
3
34
48
35
3
1
18
49
50
Dimensions
32
19
33
17
19
17
47
Model
4
16
18
49
48
Applicable Connector
models *
XW2B-20Y4
20
67.5
MR-20RMD2
XW2B-34Y4
34
112.5
MR-34RMD2
XW2B-50Y4
50
157.5
MR-50RMD2
*These Connectors are made by Honda Tsushin Kogyo.
Note: Terminal block pitch is 5.08 mm.
Use a wire size between 0.3 and 1.25 mm2 (AWG22 to AWG16).
The wire insertion holes are 1.8 × 2.5 (H × W) mm.
Terminal Block
(terminal side)
2
No. of poles Dimension A (mm)
50
Note: All pins on the Multi-pole, Square Connector correspond 1-to1 to the terminal of the same number on the terminal block as
shown above.
Applicable Connectors
Model
Applicable Connectors *1
Hood *1
XW2B-20Y4
MR-20F (soldered)
MRP-20F01 (crimped) *2
MR-20FW (wrapped)
MR-20L
XW2B-34Y4
MR-34F (soldered)
MRP-34F01 (crimped) *2
MR-34FW (wrapped)
MR-34L
XW2B-50Y4
MR-50F (soldered)
MRP-50F01 (crimped) *2
MR-50FW (wrapped)
MR-50L
*1. All applicable Connector Hoods are made by Honda Tsushin Kogyo.
*2. Use MRP-F113 or MRP-F103 crimp terminals made by Honda Tsushin Kogyo.
6
XW2B
Multi-pole, Square-connector Plug Units with a Terminal Block with M3.5 Screws
XW2B-@@Y5
Multi-contact, Square Connector (Plug)
3.5
A
3.5
15.5
29.5
45
Two,
3.5 dia.
8.5
7.3
Terminal Block
43.8
2
Wiring Diagram (Example for Terminal
Block with 50 Poles)
20.5
DIN Track lock
Dimensions
2
1
Multi-contact,
Square Connector
(mating side)
16
3
34
18
Model
No. of
poles
Dimension A
(mm)
Applicable Connector
models *
XW2B-20Y5
20
112.5
MR-20RMD2
XW2B-34Y5
34
180.0
MR-34RMD2
XW2B-50Y5
50
247.5
MR-50RMD2
32
19
33
17
48
35
49
50
*These Connectors are made by Honda Tsushin Kogyo.
Note: Terminal block pitch is 8.5 mm.
3
1
19
17
47
49
Terminal Block
(terminal side)
2
4
16
18
48
50
Note: All pins on the Multi-pole, Square Connector correspond
1-to-1 to the terminal of the same number on the terminal
block as shown above.
Applicable Connectors
Model
Applicable Connectors *1
Hood *1
XW2B-20Y5
MR-20F (soldered)
MRP-20F01 (crimped) *2
MR-20FW (wrapped)
MR-20L
XW2B-34Y5
MR-34F (soldered)
MRP-34F01 (crimped) *2
MR-34FW (wrapped)
MR-34L
XW2B-50Y5
MR-50F (soldered)
MRP-50F01 (crimped) *2
MR-50FW (wrapped)
MR-50L
*1. All applicable Connector Hoods are made by Honda Tsushin Kogyo.
*2. Use MRP-F113 or MRP-F103 crimp terminals made by Honda Tsushin Kogyo.
7
XW2B
Multi-pole, Square Connector Socket Units with a Terminal Block with M3.5 Screws
XW2B-@@X5
Multi-contact, Square Connector (Socket)
3.5
A
3.5
15.5
29.5
45
Two,
3.5 dia.
8.5
7.3
Terminal Block
43.8
2
Wiring Diagram (Example for
Terminal Block with 50 Poles)
20.5
DIN Track lock
Dimensions
48
35
34
33
Multi-contact,
Square Connector
(mating side)
50
49
Model
2
1
No. of poles Dimension A (mm)
Applicable Connector models *
32
19
16
3
17
18
XW2B-20X5
20
112.5
MR-20RFD2
XW2B-34X5
34
180.0
MR-34RFD2
XW2B-50X5
50
247.5
MR-50RFD2
*These Connectors are made by Honda Tsushin Kogyo.
Note: Terminal block pitch is 8.5 mm.
3
1
19
17
47
49
Terminal Block
(terminal side)
2
4
16
18
48
50
Note: All pins on the Multi-pole, Square Connector correspond 1to-1 to the terminal of the same number on the terminal
block as shown above.
Applicable Connectors
Model
Applicable Connectors *1
Hood *1
XW2B-20X5
MR-20M (soldered)
MRP-20M01 (crimped) *2
MR-20MW (wrapped)
MR-20L
XW2B-34X5
MR-34M (soldered)
MRP-34M01 (crimped) *2
MR-34MW (wrapped)
MR-34L
XW2B-50X5
MR-50M (soldered)
MRP-50M01 (crimped) *2
MR-50MW (wrapped)
MR-50L
*1. All applicable Connector Hoods are made by Honda Tsushin Kogyo.
*2. Use MRP-F113 or MRP-F103 crimp terminals made by Honda Tsushin Kogyo.
8
XW2B
Board I/O Units with a Terminal Block with M3.5 Screws
XW2B-40F5-P
M2.6
I/O Board Connectors (40-pin Plug)
202.5
3.5
3.5
15.5
29.5
45
Two,
3.5 dia.
7.3
7
8.5
7
Terminal Block
43.8
2
20.5
DIN Track lock
Wiring Diagram
Dimensions
FCN-364P040-AU Plug B
(mating side)
A
1
2
19
20
Model
No. of poles
Applicable Connectors and Circuits *
1
2
19
20
XW2B-40F5-P
40
FCN-364P40-AU (Connector)
FCN-360A1 (Anchor)
*These Connectors and circuits are made by Fujitsu.
Note: Terminal block pitch is 8.5 mm.
Terminal Block
(terminal side)
1
3
2
37
4
39
38
40
Applicable Connectors
Model
Applicable Connectors *1
Hood *1
XW2B-40F5-P
FCN361J040-AU (soldered)
FCN363J040-AAU (crimped)
FCN360C040B
*1. All applicable Connectors and Covers are made by Fujitsu.
*2. Refer to the OMNUC U Series user's manual for details on the Connecting Cable used between the XW2B-40F5-P and the U-series AC Servo Driver.
9
XW2B
Safety Precautions
Precautions for Correct Use
● Wiring
• Always turn OFF the power supply before wiring.
Otherwise, cables or other conductors can short the
terminals and cause the Unit to fail.
• Do not connect or disconnect Connectors with the power
turned ON. Otherwise, it may cause malfunctions.
● Wiring Terminal Blocks
• Direct Wire Connections with a Terminal Block with M3
Screws
1. Use a wire size between 0.3 and 1.25 mm2 (AWG22 to
AWG16).
2. Prepare the end of each wire as shown in the following
diagram.
● Terminal Screw Tightening Torque
• Select a tightening torque from the following table when
connecting wires or crimp terminals to the terminal block.
Tightening torque
N⋅m
Terminal Block
With M3 screws
0.40
With M3.5 screws
0.59
● Mounting Units to and Removing Units from DIN Track
• For terminal blocks with M3 screws, use a flat-heat
screwdriver like the one shown in the following diagram.
2.9- to 3.5-mm blade
6 mm
Screw slot width: 0.7
3. The wire insertion holes are 1.8 × 2.5 (H × W) mm on the
terminal block with M3 screws.
• Direct Wire Connections with a Terminal Block with M3.5
Screws
Round
Forked
3.7 mm dia.
3.7 mm 6.8 mm max.
6.8 mm max.
Applicable crimp terminals
AWG22 to AWG16
(0.30 to 1.25 mm2)
2-3.5
AWG16 to AWG14
(1.25 to 2.0 mm2)
1.25Y-3.5
AWG22 to AWG16
(0.30 to 1.25 mm2)
2Y-3.5
AWG16 to AWG14
(1.25 to 2.0 mm2)
Forked
mounted side-to-side on DIN Track. The flanges for
mounting screws are located on each side at the bottom of
the XW2B.
• Secure both ends of the XW2B with End Plates.
• When removing the Unit from a DIN Track, insert a flat-head
screwdriver into the slider and pull the lock out.
Applicable wires
1.25-3.5
Round
• XW2B Connector-Terminal Block Conversion Units can be
(With a Terminal Block with M3 Screws)
Round rod
Blade
Dia.
W
t = 0.75
Applicable crimp terminals
Rod
Blade
Applicable wires
TC-05
Dia. = 1
AWG22 to AWG18
(0.30 to 0.75 mm2)
TC-1.25S
Dia. = 1.5
AWG22 to AWG16
(0.30 to 1.25 mm2)
BT1.25-9-1
BT1.25-10-1
W = 2.2
AWG22 to AWG16
(0.30 to 1.25 mm2)
Note: Round rod and blade crimp terminals are made by Nichifu.