LOGO!Power ___________________ Overview Description, device design, 1 ___________________ dimension drawing Power supply LOGO!Power 2 ___________________ Mounting/Disassembly Mounting position, 3 ___________________ installation clearances 4 ___________________ Installation 5 ___________________ Applications Operating Instructions 6 ___________________ Technical data 7 ___________________ EMC 8 ___________________ Ambient conditions 9 ___________________ Safety 10 ___________________ Certifications 11 ___________________ MTBF 12 ___________________ Environment 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 5 V/3 A 5 V/6.3 A 12 V/1.9 A 12 V/4.5 A 15 V/1.9 A 15 V/4 A 24 V/1.3 A 24 V/2.5 A 24 V/4 A 02.2011 C98130-A7560-A999-1-7619 13 ___________________ Accessories 14 ___________________ Service & Support Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed. Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY C98130-A7560-A999-1-7619 Ⓟ 02/2011 Copyright © Siemens AG 2011. Technical data subject to change Overview Description LOGO!Power are powerful power supplies, which - thanks to their flat stepped profile - are extremely flexible for use in a host of applications (for example, in installation distribution boards). The 12 V and 24 V versions are ideal as power supplies for the LOGO! logic modules. The key benefits of the product include: ● Flat LOGO! mechanical design ● Wide-range input for voltages from 85 to 264 V AC and operation with DC voltage ● Adjustable output voltage ● Green LED for "Output voltage OK" ● Ambient temperature -20 °C to +70 °C (derating from +55 °C) ● Constant current under overload conditions for reliable connection of difficult loads ● When you turn on the power supply, a power reserve of 1.5 times rated current is available for typ. 200 ms ● Export benefits thanks to global certifications The following device options are available: Input Output Width 100 - 240 V 1-phase AC 5 V DC / 3 A 54 mm 100 - 240 V 1-phase AC 5 V DC / 6.3 A 72 mm 100 - 240 V 1-phase AC 12 V DC / 1.9 A 54 mm 100 - 240 V 1-phase AC 12 V DC / 4.5 A 72 mm 100 - 240 V 1-phase AC 15 V DC / 1.9 A 54 mm 100 - 240 V 1-phase AC 15 V DC / 4 A 72 mm 100 - 240 V 1-phase AC 24 V DC / 1.3 A 54 mm 100 - 240 V 1-phase AC 24 V DC / 2.5 A 72 mm 100 - 240 V 1-phase AC 24 V DC / 4 A 90 mm LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 3 Overview Safety and warning information WARNING When operating electrical devices, it is inevitable that certain components will carry dangerous voltages. Therefore, failure to handle the units properly can result in death or serious physical injury as well as extensive property damage. Only appropriately qualified personnel may work on or in the vicinity of this equipment. Perfect, safe, and reliable operation of this equipment is dependent on proper transportation, storage, installation and mounting. Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. LOGO!Power 4 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Overview Ordering data LOGO!Power regulated power supply 6EP1311-1SH03 5V/3A 6EP1311-1SH13 5 V / 6.3 A 6EP1321-1SH03 12 V / 1.9 A 6EP1322-1SH03 12 V / 4.5 A 6EP1351-1SH03 15 V / 1.9 A 6EP1352-1SH03 15 V / 4 A 6EP1331-1SH03 24 V / 1.3 A 6EP1332-1SH43 24 V / 2.5 A 6EP1332-1SH52 24 V / 4 A LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 5 Overview LOGO!Power 6 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Table of contents Overview.................................................................................................................................................... 3 1 Description, device design, dimension drawing ......................................................................................... 9 1.1 Device description..........................................................................................................................9 1.2 Connections and terminal designation.........................................................................................10 1.3 Potentiometer...............................................................................................................................10 1.4 Status displays and signaling.......................................................................................................11 1.5 Block diagram ..............................................................................................................................11 1.6 Dimensions and weight................................................................................................................12 2 Mounting/Disassembly............................................................................................................................. 13 3 Mounting position, installation clearances................................................................................................ 15 4 5 6 3.1 Standard mounting position .........................................................................................................15 3.2 Other mounting positions .............................................................................................................15 Installation ............................................................................................................................................... 17 4.1 Line-side connection ....................................................................................................................17 4.2 Output-side connection ................................................................................................................18 Applications ............................................................................................................................................. 19 5.1 Parallel connection to increase power rating ...............................................................................19 5.2 Parallel connection for redundancy .............................................................................................20 5.3 Series connection for increased voltage......................................................................................21 5.4 Protection against short-time voltage dips...................................................................................21 Technical data ......................................................................................................................................... 23 6.1 Input .............................................................................................................................................23 6.2 Output ..........................................................................................................................................25 6.3 Closed-loop control ......................................................................................................................27 6.4 Efficiency and power loss ............................................................................................................27 6.5 Protection and monitoring ............................................................................................................28 7 EMC ........................................................................................................................................................ 29 8 Ambient conditions .................................................................................................................................. 31 9 Safety ...................................................................................................................................................... 33 10 Certifications............................................................................................................................................ 35 11 MTBF....................................................................................................................................................... 37 LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 7 Table of contents 12 Environment ............................................................................................................................................ 39 13 Accessories ............................................................................................................................................. 41 14 Service & Support.................................................................................................................................... 43 LOGO!Power 8 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Description, device design, dimension drawing 1.1 1 Device description LOGO!Power are primary switched-mode power supplies for connection to a 1-phase AC system or to DC systems. An electronically regulated DC voltage that can be set via a potentiometer is available at the output of the device. The output of the device is isolated, no-load proof and short-circuit proof. The LED display indicates the operating status. ① ② ③ ④ ⑤ ⑥ ⑦ Line input DC output Potentiometer Indicator light (output voltage OK) DIN rail slider Natural convection Clearance above/below Figure 1-1 Structure LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 9 Description, device design, dimension drawing 1.2 Connections and terminal designation 1.2 Connections and terminal designation The line input terminals ① can be used to establish the connection to supply voltage. The output terminals ② to be supplied are used to connect the loads (see also Section Installation (Page 17)). Connections and terminal designations ① Supply input L1, N One screw terminal each for 0.5 to 2.5 mm² ② Output + 2 screw terminals for 0.5 mm to 2.5 mm² ② Output – 2 screw terminals for 0.5 mm to 2.5 mm² Figure 1-2 1.3 Terminal data Potentiometer The potentiometer ③ on the front of the device is used to set the output voltage. The output voltage is set to the rated value at the factory and can be set within certain limits; for example, to compensate voltage drops across long supply lines to the connected load. Type Factory setting Setting range 5V 5V 4.6 to 5.4 V 12 V 12 V 10.5 to 12.9 V 15 V 15 V 13.9 to 16.1 V 24 V 24 V 22.2 to 26.4 V WARNING Actuation of the potentiometer is allowed only be means of an insulated screwdriver. Notes on potentiometer operation (such as a screwdriver, torque) refer to Chapter Connections and terminal designation (Page 10), Fig. Terminal data. LOGO!Power 10 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Description, device design, dimension drawing 1.4 Status displays and signaling 1.4 Status displays and signaling Status display Green LED for output voltage OK Signaling 1.5 Figure 1-3 LED ④ lights up green Normal operation, output voltage in setpoint range LED ④ off Supply voltage missing or output voltage is not in setpoint range due to overload Block diagram Block diagram LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 11 Description, device design, dimension drawing 1.6 Dimensions and weight 1.6 Dimensions and weight Figure 1-4 Dimension drawing Dimensions (W × H × D) Weight 54 × 90 × 55 mm Approx. 160 g 72 × 90 × 55 mm Approx. 250 g 90 × 90 × 55 mm Approx. 320 g LOGO!Power 12 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Mounting/Disassembly 2 WARNING The LOGO!Power power supplies are built-in units. They must be installed in a casing or control cabinet to which only qualified personnel have access. The devices can be snapped onto standard mounting rail EN 60715 35x7.5/15 for installation in a control cabinet. Installation To mount the device, position it with the mounting rail guideway at the upper edge of the DIN rail and press down to lock it into place. If this is too difficult, press slider ① at the same time, as described for "Disassembly". Deinstalling To remove, pull up the slider ① using a screwdriver ② and disengage the device at the bottom edge of the DIN rail. Then you can remove the device from the upper edge of the DIN rail. Figure 2-1 Deinstalling WARNING If the device is to be used in a hazardous area (Ex II 3G Ex nA IIC T3) it must be installed in a distributor box with degree of protection IP54 or higher. LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 13 Mounting/Disassembly LOGO!Power 14 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Mounting position, installation clearances 3.1 3 Standard mounting position The device is designed for installation on a standard mounting rail EN 60715 35x7.5/15. The device must be mounted vertically to ensure proper cooling, and with the input terminals and output terminals at the top. A clearance of at least 20 mm should be maintained above and below the device. No space is required at the side. 3.2 Other mounting positions For mounting positions that deviate from the standard mounting position, derating factors (reduction of the output power or the permissible ambient temperature) must be observed in accordance with the following diagrams. Figure 3-1 Mounting position (1) Figure 3-2 Mounting position (2) LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 15 Mounting position, installation clearances 3.2 Other mounting positions Figure 3-3 Mounting position (3) Figure 3-4 Mounting position (4) NOTICE In the case of mounting postilions that deviate from the standard mounting position, reduced mechanical resistance of the devices against vibration and shock must be expected. Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. LOGO!Power 16 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 4 Installation WARNING Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. 4.1 Line-side connection The LOGO!Power power supplies are power packs acc. to safety class II (without protective conductor or equivalent without PE). LOGO!Power are designed for connection to a 1-phase AC supply network (TN or TT system in accordance with VDE 0100 T 300 / IEC 364-3) with rated voltage 1-phase 100-240 V AC, 50/60 Hz or to a power supply with 110-300 V DC . Figure 4-1 Line connection The connection of power supply network is made via the terminals L1 and N (see Fig. 4-1) and must be established in accordance with IEC 60364 and EN 50178. A protective device (miniature circuit breaker or circuit breaker) and a disconnection unit for the power supply must be provided. A residual current circuit-breaker must not be used as the only protective measure against indirect contact; this applies to the entire supply system that is protected by the residual current operated circuit breaker. Line-side protection (IEC 898) to be implemented upstream: ● Circuit breaker characteristic C, from 10 A or ● circuit breaker characteristic B, from 16 A Other country-specific regulations may have to be observed when installing the device. LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 17 Installation 4.2 Output-side connection 4.2 Output-side connection The LOGO!Power power supplies provide an isolated (= non-grounded) SELV (Safety Extra Low Voltage) output voltage at the output. The output of the power supplies is no-load, overload, and short-circuit proof. If overload occurs, the electronic current limitation limits the output current to a maximum value (refer to chapter Technical data, Output (Page 25)). Figure 4-2 Connection of the output voltage The output voltage is connected via the + and - terminals at the output of the power supply (see Fig. 4-2). Make sure that the output cables are dimensioned correctly for the maximum output current rms value and fused accordingly. Note When using LOGO!Power in conjunction with devices of the protection class I (with protective conductor), a connection must be established between "-" and "PE" with at least 1.5 mm². LOGO!Power 18 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 5 Applications 5.1 Parallel connection to increase power rating To enhance performance, two LOGO!Power power supplies of the same type can be galvanically connected in parallel. The following must be observed: ● The cables connected to each power supply at terminals "+" and "-" must have identical lengths and the same cable cross-sections (or the same impedance) up to a common external network junction (terminal strip) if possible. ● The parallel-switched power supplies must be switched on simultaneously with a common switch in the mains supply line (e.g. with the main switch available in control cabinets). ● The output voltages measured in no-load operation for the power supplies that are not yet connected in parallel should not deviate more than a maximum of 0.2 %. This usually corresponds to the factory setting. If the output voltage is changed, you should connect the "-" terminals and then, in no-load operation, measure the voltage difference between the "+" terminals that have not yet been connected. The voltage difference should not exceed 0.2%. Figure 5-1 Parallel connection to increase power rating CAUTION For connection of more than two power supplies in parallel, additional measures must be taken to prevent high backward feeding currents in the event of a secondary device fault. For this purpose, a suitable protective circuit (e.g. decoupling diode) must be installed between each "+" terminal of the power supply and the common connection point. LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 19 Applications 5.2 Parallel connection for redundancy 5.2 Parallel connection for redundancy The parallel switching of several LOGO!Power power supplies for redundancy is required when the demands for reliability of the supply are particularly high. If a component in the redundant supply fails, the power supply for the loads must be fully accommodated by the remaining component. It is therefore important when dimensioning the system to make sure that n+1 redundant switched power supplies can handle the total power requirement of the remaining n power supplies. To prevent loading of the remaining power supplies in the event of a secondary-side error when one power supply fails, the respective "+" terminals of the power supplies must be decoupled via diodes. NOTICE For a high reliability of the supply, it is recommended that the redundant switched power supplies are fused separately on the line-side and, if possible, be connected to different power supply networks. Figure 5-2 Parallel connection for redundancy LOGO!Power 20 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Applications 5.3 Series connection for increased voltage 5.3 Series connection for increased voltage To achieve a higher output voltage, two LOGO!Power power supplies of the same type can be connected in series. In this case, connect the "-" terminal of the first power supply to the "+" terminal of the second power supply. The "+" terminal of the first power supply and the "-" terminal of the second power supply are routed to the load. Depending on grounding point of the secondary output voltage, voltages of +2×UA, ±UA or 2×UAcan be implemented. In the case of asymmetric load distribution, it is not possible to ensure correct functionality. WARNING When two power supplies are connected in series, it is not possible to ensure the permanently permissible SELV voltage of maximum of 60 V DC acc. to EN 60950 in the event of a fault. Figure 5-3 5.4 Series connection Protection against short-time voltage dips During a drop in the primary-side supply voltage, the LOGO!Power power supplies still maintain the output voltage over a short millisecond period (see section Technical data, Input (Page 23)). LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 21 Applications 5.4 Protection against short-time voltage dips LOGO!Power 22 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 6 Technical data 6.1 Input Rated voltage Ve rated 1-phase 100 - 240 V AC wide-range input AC voltage range 85 … 264 V AC Voltage* range DC 110 to 300 V DC Connect/shutdown threshold Typ. 80 V/70 V Overvoltage resistance 2,3 × Ve rated, 1.3 ms Rated line frequency; rated line frequency range 6EP1311-1SH03 Rated current 6EP1311-1SH13 Ie rated at Ve = 230 V 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 50/60 Hz; 47 to 63 Hz 0.20 A 0.43 A 0.29 A 0.67 A 0.35 A 0.70 A 0.36 A 0.69 A 0.99 A Switch-on current limitation (+25 °C) I2t value 6EP1311-1SH03 6EP1311-1SH13 6EP1321-1SH03 6EP1322-1SH03 6EP1351-1SH03 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 < 30 A < 55 A < 30 A < 55 A < 30 A < 55 A < 30 A < 50 A < 30 A 6EP1311-1SH03 0.4 A2s 6EP1311-1SH13 1.2 A2s 6EP1321-1SH03 0.4 A2s 6EP1322-1SH03 1.2 A2s 6EP1351-1SH03 0.4 A2s 6EP1352-1SH03 6EP1331-1SH03 6EP1332-1SH43 6EP1332-1SH52 1.2 A2s 0.4 A2s 1.2 A2s 1.3 A2s Built-in line-side fuse Fuse Required protection in the mains supply conductor Miniature circuit breakers (IEC 898 )characteristic C 10 A or characteristic B 16 A Mains buffering at Ia rated >40 ms (for 187 V) LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 23 Technical data 6.1 Input Figure 6-1 Mains buffering LOGO!Power 24 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Technical data 6.2 Output 6.2 Output Rated voltageVa rated Controlled, isolated DC voltage 5 V DC, 12 V, 15 V or 24 V Total tolerance ±3 % Static line smoothing Approx. ±0.5 % Approx. ±1 % Static load smoothing Residual ripple 12 V, 15 V, 24 V < 200 mVpp Spikes (bandwidth: 20 MHz) 12 V, 15 V, 24 V < 300 mVpp 5 V < 100 mVpp 5 V < 100 mVpp Setting range 5 V 4.6 to 5.4 V 12 V 10.5 to 12.9 V 15 V 13.9 to 16.1 V 24 V 22.2 to 26.4 V Response on activation/deactivation No overshoot of Va (soft start) Startup delay/voltage rise < 1.5 s/< 500 ms (typ. 70 ms/typ. 10 ms) (see the figure below) Rated current Ia rated 6EP1311-1SH03 3 A 6EP1311-1SH13 6.3 A 6EP1321-1SH03 1.9 A 6EP1322-1SH03 4.5 A 6EP1351-1SH03 1.9 A 6EP1352-1SH03 4 A 6EP1331-1SH03 1.3 A 6EP1332-1SH43 2.5 A 6EP1332-1SH52 4 A Current range • Up to +55 °C 0 ... 100% Ia rated • Derating 0 ... 70% Ia rated (at +70 °C) Power reserve When you turn on the power supply 1.5 x Ia rated for typ. 200 ms Parallel switching for enhanced performance Yes, 2 units Output characteristic (see illustration below) LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 25 Technical data 6.2 Output Figure 6-2 Startup delay/voltage rise Figure 6-3 Output characteristic (typical behavior) The device supplies a constant output voltage until the current limit is reached. In the event of an overload, the output current and the output voltage are reduced. The device does not switch off. LOGO!Power 26 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Technical data 6.3 Closed-loop control 6.3 Closed-loop control Dyn. mains compensation (Ve rated ±15 %) <3% Va Dyn. load compensation (Ia: 10/90/10 %) Typ. ±2% Va Load-step settling time 6.4 • 10 to 90 % < 20 ms (typ. 0.2 ms) • 90 to 10 % < 20 ms (typ. 0.2 ms) Efficiency and power loss Efficiency at Va rated, Ia rated (at Ve 230 V) Efficiency at Va rated, Ia rated (at Ve 230 V) No-load power loss (at Ve 230 V) 6EP1311-1SH03 Approx. 77 % 6EP1311-1SH13 Approx. 80 % 6EP1321-1SH03 Approx. 78 % 6EP1322-1SH03 Approx. 84 % 6EP1351-1SH03 Approx. 80 % 6EP1352-1SH03 Approx. 85 % 6EP1331-1SH03 Approx. 83 % 6EP1332-1SH43 Approx. 87 % 6EP1332-1SH52 Approx. 87 % 6EP1311-1SH03 Approx. 4.6 W 6EP1311-1SH13 Approx. 8.1 W 6EP1321-1SH03 Approx. 6.4 W 6EP1322-1SH03 Approx. 10.2 W 6EP1351-1SH03 Approx. 7.1 W 6EP1352-1SH03 Approx. 10.8 W 6EP1331-1SH03 Approx. 6.3 W 6EP1332-1SH43 Approx. 8.7 W 6EP1332-1SH52 Approx. 13.8 W 6EP1311-1SH03 Approx. 1.5 W 6EP1311-1SH13 Approx. 1.5 W 6EP1321-1SH03 Approx. 1.8 W 6EP1322-1SH03 Approx. 1.9 W 6EP1351-1SH03 Approx. 2.1 W 6EP1352-1SH03 Approx. 2.3 W 6EP1331-1SH03 Approx. 2.0 W 6EP1332-1SH43 Approx. 1.8 W 6EP1332-1SH52 Approx. 2.0 W LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 27 Technical data 6.5 Protection and monitoring 6.5 Protection and monitoring Output overvoltage protection Yes, acc. to EN 60950 Current limitation Typ. 110 % … 130 % of Ia rated when you turn on the power supply overload capability with 150 % of Ia rated for typ. 200 ms Short-circuit protection Characteristic curve up to 0 V Sustained short-circuit current rms value 6EP1311-1SH03 Approx. 3.9 A 6EP1311-1SH13 Approx. 8.0 A 6EP1321-1SH03 Approx. 2.3 A 6EP1322-1SH03 Approx. 4.4 A 6EP1351-1SH03 Approx. 2.3 A 6EP1352-1SH03 Approx. 4.4 A 6EP1331-1SH03 Approx. 1.6 A 6EP1332-1SH43 Approx. 3.5 A 6EP1332-1SH52 Approx. 7.2 A Overload/short-circuit indicator - LOGO!Power 28 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 7 EMC EN 61000-6-2 Immunity for industrial environments EN 61000-6-3 Emission for residential areas Electrostatic discharges EN 61000-4-2 6 kV contact, 8 kV air Electromagnetic fields EN 61000-4-3 Generic standards 80 to 1000 MHz 10 V/m 1000 to 2000 MHz 3 V/m 2000 to 2700 MHz 1 V/m High-speed transient disturbance variables (burst) EN 61000-4-4 4 kV on mains connections Power surges EN 61000-4-5 2 kV symmetrically on mains connections 2 kV at DC output 4 kV symmetrically on mains connections 500 V symmetrical/asymmetrical on DC output lines High-frequency fields EN 61000-4-6 10 V; 0.15 to 80 MHz Voltage dips EN 61000-4-11 100 % for 20 ms 60 % for 200 ms 30 % for 500 ms Voltage interruptions EN 61000-4-11 100 % for 5000 ms Emitted interference EN 55022 Class B Harmonic currents EN 61000-3-2 Class A LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 29 EMC LOGO!Power 30 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 8 Ambient conditions Humidity class Climate class 3K3 to EN 60721, no condensation Ambient temperature -20 ... +70 °C with natural convection Derating: • from +55 °C 2 %/K Tested to: Transport/storage temperature • EN 60068-2-1 coldness • EN 60068-2-2 dry heat • EN 60068-2-78 damp heat, constant • EN 60068-2-14 change of temperature -40 ... +85 °C Tests (packed for shipping) according to: Mechanical stressing in operation • EN 60068-2-1 coldness • EN 60068-2-2 dry heat • EN 60068-2-30 damp heat, cyclic Tested to: • • EN 60068-2-6 vibration, test Fc – 7 mm deflection in the range 5 - 9 Hz – 2 G acceleration in the range 9 - 150 Hz EN 60068-2-27 shock, test Ea – Damaging gases Atmospheric pressure Acceleration 150 m/s2, test duration 11 ms Tested to: • EN 60068-2-42 sulfur dioxide: 10 cm3/m3, 4 days • EN 60068-2-43 sulfur dioxide: 1 cm3/m3, 4 days Tested to: • EN 60068-2-13 Operation: • 1080 ... 795 hPa (-1000 to +2000 m) • >2000 m: Derating factor of 5 % / 1000 m Storage: • 1080 ... 660 hPa (-1000 to +3500 m) LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 31 Ambient conditions LOGO!Power 32 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 9 Safety Primary/secondary isolation Yes, SELV output voltage Ua according to EN 60950 and EN 50178 Test voltage Primary/secondary 3 kVAC or corresponding DC value Protection class Class II (without protective conductor) Leakage current < 250 µA Degree of protection (EN 60529) IP20 LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 33 Safety LOGO!Power 34 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 10 Certifications Certifications CE marking Yes (2004/108/EC and 2006/95/EC) UL/cUL approval cULus-listed (UL 508, CSA C22.2 No.107.1), File E197259 cURus (UL60950, CSA C22.2 No. 60950) File E151273 NEC Class2 for types: 6EP1311-1SH03 5 V/3 A 6EP1321-1SH03 12 V/1,9 A 6EP1351-1SH03 15 V/1,9 A 6EP1331-1SH03 24 V/1,3 A 6EP1332-1SH43 24 V/2,5 A CSA approval CLASS 5318 01 - Power Supplies - for Hazardous Locations CLASS 5318 81 - Power Supplies - for Hazardous Locations - Certified to U.S. Standard Class I, Division 2, Groups A,B,C and D, T4 Class I, Zone 2, Ex nA II T4 IP20, AEx nA II T4 IP20 FM Class I, Div. 2, Groups A, B, C, and D; T4 CB scheme IEC 60950-1 Explosion protection ATEX II 3G Ex nA IIC T3 X SEMI F47 compliance 208 V-240 V IEC 61000-4-11 EN 60079-0:2006 and EN 60079-15:2005 Marine approval Germanischer Lloyd (GL) 6EP1352-1SH52: Cert. No.:24184-04HH All other types: Cert. No.:47994-03HH ABS, DNV, BV, LRS in preparation for selected types LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 35 Certifications LOGO!Power 36 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 11 MTBF Mean Time Between Failures In accordance with SN29500: >3500000 h at 40 °C, rated load, 24-h operation LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 37 MTBF LOGO!Power 38 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Environment 12 The device is RoHS-compatible. As a rule, only non-silicon precipitating materials are used. LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 39 Environment LOGO!Power 40 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Accessories 13 No accessories. LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 41 Accessories LOGO!Power 42 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 Service & Support 14 Further information via the home page http://www.siemens.de/sitop/manuals or http://support.automation.siemens.com Phone: +49 (0) 911 895 7222 LOGO!Power Operating Instructions, 02.2011, C98130-A7560-A999-1-7619 43 Service & Support LOGO!Power 44 Operating Instructions, 02.2011, C98130-A7560-A999-1-7619