SIEMENS 6EP1322

LOGO!Power
___________________
Overview
Description, device design,
1
___________________
dimension drawing
Power supply
LOGO!Power
2
___________________
Mounting/Disassembly
Mounting position,
3
___________________
installation clearances
4
___________________
Installation
5
___________________
Applications
Operating Instructions
6
___________________
Technical data
7
___________________
EMC
8
___________________
Ambient conditions
9
___________________
Safety
10
___________________
Certifications
11
___________________
MTBF
12
___________________
Environment
6EP1311-1SH03
6EP1311-1SH13
6EP1321-1SH03
6EP1322-1SH03
6EP1351-1SH03
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
5 V/3 A
5 V/6.3 A
12 V/1.9 A
12 V/4.5 A
15 V/1.9 A
15 V/4 A
24 V/1.3 A
24 V/2.5 A
24 V/4 A
02.2011
C98130-A7560-A999-1-7619
13
___________________
Accessories
14
___________________
Service & Support
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and
safety instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
C98130-A7560-A999-1-7619
Ⓟ 02/2011
Copyright © Siemens AG 2011.
Technical data subject to change
Overview
Description
LOGO!Power are powerful power supplies, which - thanks to their flat stepped profile - are
extremely flexible for use in a host of applications (for example, in installation distribution
boards). The 12 V and 24 V versions are ideal as power supplies for the LOGO! logic
modules.
The key benefits of the product include:
● Flat LOGO! mechanical design
● Wide-range input for voltages from 85 to 264 V AC and operation with DC voltage
● Adjustable output voltage
● Green LED for "Output voltage OK"
● Ambient temperature -20 °C to +70 °C (derating from +55 °C)
● Constant current under overload conditions for reliable connection of difficult loads
● When you turn on the power supply, a power reserve of 1.5 times rated current is
available for typ. 200 ms
● Export benefits thanks to global certifications
The following device options are available:
Input
Output
Width
100 - 240 V 1-phase AC
5 V DC / 3 A
54 mm
100 - 240 V 1-phase AC
5 V DC / 6.3 A
72 mm
100 - 240 V 1-phase AC
12 V DC / 1.9 A
54 mm
100 - 240 V 1-phase AC
12 V DC / 4.5 A
72 mm
100 - 240 V 1-phase AC
15 V DC / 1.9 A
54 mm
100 - 240 V 1-phase AC
15 V DC / 4 A
72 mm
100 - 240 V 1-phase AC
24 V DC / 1.3 A
54 mm
100 - 240 V 1-phase AC
24 V DC / 2.5 A
72 mm
100 - 240 V 1-phase AC
24 V DC / 4 A
90 mm
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
3
Overview
Safety and warning information
WARNING
When operating electrical devices, it is inevitable that certain components will carry
dangerous voltages.
Therefore, failure to handle the units properly can result in death or serious physical injury
as well as extensive property damage.
Only appropriately qualified personnel may work on or in the vicinity of this equipment.
Perfect, safe, and reliable operation of this equipment is dependent on proper
transportation, storage, installation and mounting.
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again.
If this instruction is not observed, touching live parts can result in death or serious injury.
Disposal guidelines
Packaging and packaging aids can and should always be recycled.
The product itself may not be disposed of as domestic refuse.
LOGO!Power
4
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Overview
Ordering data
LOGO!Power
regulated power supply
6EP1311-1SH03
5V/3A
6EP1311-1SH13
5 V / 6.3 A
6EP1321-1SH03
12 V / 1.9 A
6EP1322-1SH03
12 V / 4.5 A
6EP1351-1SH03
15 V / 1.9 A
6EP1352-1SH03
15 V / 4 A
6EP1331-1SH03
24 V / 1.3 A
6EP1332-1SH43
24 V / 2.5 A
6EP1332-1SH52
24 V / 4 A
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
5
Overview
LOGO!Power
6
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Table of contents
Overview.................................................................................................................................................... 3
1
Description, device design, dimension drawing ......................................................................................... 9
1.1
Device description..........................................................................................................................9
1.2
Connections and terminal designation.........................................................................................10
1.3
Potentiometer...............................................................................................................................10
1.4
Status displays and signaling.......................................................................................................11
1.5
Block diagram ..............................................................................................................................11
1.6
Dimensions and weight................................................................................................................12
2
Mounting/Disassembly............................................................................................................................. 13
3
Mounting position, installation clearances................................................................................................ 15
4
5
6
3.1
Standard mounting position .........................................................................................................15
3.2
Other mounting positions .............................................................................................................15
Installation ............................................................................................................................................... 17
4.1
Line-side connection ....................................................................................................................17
4.2
Output-side connection ................................................................................................................18
Applications ............................................................................................................................................. 19
5.1
Parallel connection to increase power rating ...............................................................................19
5.2
Parallel connection for redundancy .............................................................................................20
5.3
Series connection for increased voltage......................................................................................21
5.4
Protection against short-time voltage dips...................................................................................21
Technical data ......................................................................................................................................... 23
6.1
Input .............................................................................................................................................23
6.2
Output ..........................................................................................................................................25
6.3
Closed-loop control ......................................................................................................................27
6.4
Efficiency and power loss ............................................................................................................27
6.5
Protection and monitoring ............................................................................................................28
7
EMC ........................................................................................................................................................ 29
8
Ambient conditions .................................................................................................................................. 31
9
Safety ...................................................................................................................................................... 33
10
Certifications............................................................................................................................................ 35
11
MTBF....................................................................................................................................................... 37
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
7
Table of contents
12
Environment ............................................................................................................................................ 39
13
Accessories ............................................................................................................................................. 41
14
Service & Support.................................................................................................................................... 43
LOGO!Power
8
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Description, device design, dimension drawing
1.1
1
Device description
LOGO!Power are primary switched-mode power supplies for connection to a 1-phase AC
system or to DC systems. An electronically regulated DC voltage that can be set via a
potentiometer is available at the output of the device. The output of the device is isolated,
no-load proof and short-circuit proof. The LED display indicates the operating status.
①
②
③
④
⑤
⑥
⑦
Line input
DC output
Potentiometer
Indicator light (output voltage OK)
DIN rail slider
Natural convection
Clearance above/below
Figure 1-1
Structure
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
9
Description, device design, dimension drawing
1.2 Connections and terminal designation
1.2
Connections and terminal designation
The line input terminals ① can be used to establish the connection to supply voltage. The
output terminals ② to be supplied are used to connect the loads (see also Section
Installation (Page 17)).
Connections and terminal designations
① Supply input L1, N
One screw terminal each for 0.5 to 2.5 mm²
② Output +
2 screw terminals for 0.5 mm to 2.5 mm²
② Output –
2 screw terminals for 0.5 mm to 2.5 mm²
Figure 1-2
1.3
Terminal data
Potentiometer
The potentiometer ③ on the front of the device is used to set the output voltage. The output
voltage is set to the rated value at the factory and can be set within certain limits; for
example, to compensate voltage drops across long supply lines to the connected load.
Type
Factory setting
Setting range
5V
5V
4.6 to 5.4 V
12 V
12 V
10.5 to 12.9 V
15 V
15 V
13.9 to 16.1 V
24 V
24 V
22.2 to 26.4 V
WARNING
Actuation of the potentiometer is allowed only be means of an insulated screwdriver.
Notes on potentiometer operation (such as a screwdriver, torque) refer to Chapter
Connections and terminal designation (Page 10), Fig. Terminal data.
LOGO!Power
10
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Description, device design, dimension drawing
1.4 Status displays and signaling
1.4
Status displays and signaling
Status display
Green LED for output voltage OK
Signaling
1.5
Figure 1-3
LED ④ lights up green
Normal operation, output
voltage in setpoint range
LED ④ off
Supply voltage missing or
output voltage is not in
setpoint range due to
overload
Block diagram
Block diagram
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
11
Description, device design, dimension drawing
1.6 Dimensions and weight
1.6
Dimensions and weight
Figure 1-4
Dimension drawing
Dimensions (W × H × D)
Weight
54 × 90 × 55 mm
Approx. 160 g
72 × 90 × 55 mm
Approx. 250 g
90 × 90 × 55 mm
Approx. 320 g
LOGO!Power
12
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Mounting/Disassembly
2
WARNING
The LOGO!Power power supplies are built-in units. They must be installed in a casing or
control cabinet to which only qualified personnel have access.
The devices can be snapped onto standard mounting rail EN 60715 35x7.5/15 for installation
in a control cabinet.
Installation
To mount the device, position it with the mounting rail guideway at the upper edge of the DIN
rail and press down to lock it into place. If this is too difficult, press slider ① at the same
time, as described for "Disassembly".
Deinstalling
To remove, pull up the slider ① using a screwdriver ② and disengage the device at the
bottom edge of the DIN rail. Then you can remove the device from the upper edge of the DIN
rail.
Figure 2-1
Deinstalling
WARNING
If the device is to be used in a hazardous area (Ex II 3G Ex nA IIC T3) it must be installed
in a distributor box with degree of protection IP54 or higher.
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
13
Mounting/Disassembly
LOGO!Power
14
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Mounting position, installation clearances
3.1
3
Standard mounting position
The device is designed for installation on a standard mounting rail EN 60715 35x7.5/15. The
device must be mounted vertically to ensure proper cooling, and with the input terminals and
output terminals at the top.
A clearance of at least 20 mm should be maintained above and below the device. No space
is required at the side.
3.2
Other mounting positions
For mounting positions that deviate from the standard mounting position, derating factors
(reduction of the output power or the permissible ambient temperature) must be observed in
accordance with the following diagrams.
Figure 3-1
Mounting position (1)
Figure 3-2
Mounting position (2)
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
15
Mounting position, installation clearances
3.2 Other mounting positions
Figure 3-3
Mounting position (3)
Figure 3-4
Mounting position (4)
NOTICE
In the case of mounting postilions that deviate from the standard mounting position,
reduced mechanical resistance of the devices against vibration and shock must be
expected. Particularly when installing on a vertically fastened standard mounting rail,
additional measures may be required, e.g. to prevent the device from slipping on the
standard mounting rail.
LOGO!Power
16
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
4
Installation
WARNING
Before installation or maintenance work can begin, the system's main switch must be
switched off and measures taken to prevent it being switched on again. If this instruction is
not observed, touching live parts can result in death or serious injury.
4.1
Line-side connection
The LOGO!Power power supplies are power packs acc. to safety class II (without protective
conductor or equivalent without PE). LOGO!Power are designed for connection to a 1-phase
AC supply network (TN or TT system in accordance with VDE 0100 T 300 / IEC 364-3) with
rated voltage 1-phase 100-240 V AC, 50/60 Hz or to a power supply with 110-300 V DC .
Figure 4-1
Line connection
The connection of power supply network is made via the terminals L1 and N (see Fig. 4-1)
and must be established in accordance with IEC 60364 and EN 50178. A protective device
(miniature circuit breaker or circuit breaker) and a disconnection unit for the power supply
must be provided. A residual current circuit-breaker must not be used as the only protective
measure against indirect contact; this applies to the entire supply system that is protected by
the residual current operated circuit breaker.
Line-side protection (IEC 898) to be implemented upstream:
● Circuit breaker characteristic C, from 10 A or
● circuit breaker characteristic B, from 16 A
Other country-specific regulations may have to be observed when installing the device.
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
17
Installation
4.2 Output-side connection
4.2
Output-side connection
The LOGO!Power power supplies provide an isolated (= non-grounded) SELV (Safety Extra
Low Voltage) output voltage at the output. The output of the power supplies is no-load,
overload, and short-circuit proof. If overload occurs, the electronic current limitation limits the
output current to a maximum value (refer to chapter Technical data, Output (Page 25)).
Figure 4-2
Connection of the output voltage
The output voltage is connected via the + and - terminals at the output of the power supply
(see Fig. 4-2). Make sure that the output cables are dimensioned correctly for the maximum
output current rms value and fused accordingly.
Note
When using LOGO!Power in conjunction with devices of the protection class I (with
protective conductor), a connection must be established between "-" and "PE" with at least
1.5 mm².
LOGO!Power
18
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
5
Applications
5.1
Parallel connection to increase power rating
To enhance performance, two LOGO!Power power supplies of the same type can be
galvanically connected in parallel.
The following must be observed:
● The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external network junction (terminal strip) if possible.
● The parallel-switched power supplies must be switched on simultaneously with a
common switch in the mains supply line (e.g. with the main switch available in control
cabinets).
● The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 0.2 %. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 0.2%.
Figure 5-1
Parallel connection to increase power rating
CAUTION
For connection of more than two power supplies in parallel, additional measures must be
taken to prevent high backward feeding currents in the event of a secondary device fault.
For this purpose, a suitable protective circuit (e.g. decoupling diode) must be installed
between each "+" terminal of the power supply and the common connection point.
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
19
Applications
5.2 Parallel connection for redundancy
5.2
Parallel connection for redundancy
The parallel switching of several LOGO!Power power supplies for redundancy is required
when the demands for reliability of the supply are particularly high.
If a component in the redundant supply fails, the power supply for the loads must be fully
accommodated by the remaining component. It is therefore important when dimensioning the
system to make sure that n+1 redundant switched power supplies can handle the total power
requirement of the remaining n power supplies.
To prevent loading of the remaining power supplies in the event of a secondary-side error
when one power supply fails, the respective "+" terminals of the power supplies must be
decoupled via diodes.
NOTICE
For a high reliability of the supply, it is recommended that the redundant switched power
supplies are fused separately on the line-side and, if possible, be connected to different
power supply networks.
Figure 5-2
Parallel connection for redundancy
LOGO!Power
20
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Applications
5.3 Series connection for increased voltage
5.3
Series connection for increased voltage
To achieve a higher output voltage, two LOGO!Power power supplies of the same type can
be connected in series. In this case, connect the "-" terminal of the first power supply to the
"+" terminal of the second power supply. The "+" terminal of the first power supply and the "-"
terminal of the second power supply are routed to the load.
Depending on grounding point of the secondary output voltage, voltages of +2×UA, ±UA or 2×UAcan be implemented.
In the case of asymmetric load distribution, it is not possible to ensure correct functionality.
WARNING
When two power supplies are connected in series, it is not possible to ensure the
permanently permissible SELV voltage of maximum of 60 V DC acc. to EN 60950 in the
event of a fault.
Figure 5-3
5.4
Series connection
Protection against short-time voltage dips
During a drop in the primary-side supply voltage, the LOGO!Power power supplies still
maintain the output voltage over a short millisecond period (see section Technical data, Input
(Page 23)).
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
21
Applications
5.4 Protection against short-time voltage dips
LOGO!Power
22
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
6
Technical data
6.1
Input
Rated voltage Ve rated
1-phase 100 - 240 V AC wide-range input
AC voltage range
85 … 264 V AC
Voltage* range DC
110 to 300 V DC
Connect/shutdown threshold
Typ. 80 V/70 V
Overvoltage resistance
2,3 × Ve rated, 1.3 ms
Rated line frequency; rated line frequency range
6EP1311-1SH03
Rated current
6EP1311-1SH13
Ie rated at Ve = 230 V
6EP1321-1SH03
6EP1322-1SH03
6EP1351-1SH03
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
50/60 Hz; 47 to 63 Hz
0.20 A
0.43 A
0.29 A
0.67 A
0.35 A
0.70 A
0.36 A
0.69 A
0.99 A
Switch-on current limitation
(+25 °C)
I2t value
6EP1311-1SH03
6EP1311-1SH13
6EP1321-1SH03
6EP1322-1SH03
6EP1351-1SH03
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
< 30 A
< 55 A
< 30 A
< 55 A
< 30 A
< 55 A
< 30 A
< 50 A
< 30 A
6EP1311-1SH03 0.4 A2s
6EP1311-1SH13 1.2 A2s
6EP1321-1SH03 0.4 A2s
6EP1322-1SH03 1.2 A2s
6EP1351-1SH03 0.4 A2s
6EP1352-1SH03
6EP1331-1SH03
6EP1332-1SH43
6EP1332-1SH52
1.2 A2s
0.4 A2s
1.2 A2s
1.3 A2s
Built-in line-side fuse
Fuse
Required protection in the mains supply
conductor
Miniature circuit breakers (IEC 898
)characteristic C 10 A
or characteristic B 16 A
Mains buffering at Ia rated
>40 ms (for 187 V)
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
23
Technical data
6.1 Input
Figure 6-1
Mains buffering
LOGO!Power
24
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Technical data
6.2 Output
6.2
Output
Rated voltageVa rated
Controlled, isolated DC voltage
5 V DC, 12 V, 15 V or 24 V
Total tolerance
±3 %
Static line smoothing
Approx. ±0.5 %
Approx. ±1 %
Static load smoothing
Residual ripple
12 V, 15 V, 24 V < 200 mVpp
Spikes (bandwidth: 20 MHz)
12 V, 15 V, 24 V < 300 mVpp
5 V < 100 mVpp
5 V < 100 mVpp
Setting range
5 V 4.6 to 5.4 V
12 V 10.5 to 12.9 V
15 V 13.9 to 16.1 V
24 V 22.2 to 26.4 V
Response on activation/deactivation
No overshoot of Va (soft start)
Startup delay/voltage rise
< 1.5 s/< 500 ms (typ. 70 ms/typ. 10
ms) (see the figure below)
Rated current Ia rated
6EP1311-1SH03 3 A
6EP1311-1SH13 6.3 A
6EP1321-1SH03 1.9 A
6EP1322-1SH03 4.5 A
6EP1351-1SH03 1.9 A
6EP1352-1SH03 4 A
6EP1331-1SH03 1.3 A
6EP1332-1SH43 2.5 A
6EP1332-1SH52 4 A
Current range
•
Up to +55 °C
0 ... 100% Ia rated
•
Derating
0 ... 70% Ia rated (at +70 °C)
Power reserve
When you turn on the power supply 1.5 x Ia rated
for typ. 200 ms
Parallel switching for enhanced performance
Yes, 2 units
Output characteristic
(see illustration below)
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
25
Technical data
6.2 Output
Figure 6-2
Startup delay/voltage rise
Figure 6-3
Output characteristic (typical behavior)
The device supplies a constant output voltage until the current limit is reached. In the event
of an overload, the output current and the output voltage are reduced. The device does not
switch off.
LOGO!Power
26
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Technical data
6.3 Closed-loop control
6.3
Closed-loop control
Dyn. mains compensation (Ve rated ±15 %)
<3% Va
Dyn. load compensation (Ia: 10/90/10 %)
Typ. ±2% Va
Load-step settling time
6.4
•
10 to 90 %
< 20 ms (typ. 0.2 ms)
•
90 to 10 %
< 20 ms (typ. 0.2 ms)
Efficiency and power loss
Efficiency at
Va rated, Ia rated
(at Ve 230 V)
Efficiency at Va rated, Ia
rated
(at Ve 230 V)
No-load power loss
(at Ve 230 V)
6EP1311-1SH03
Approx. 77 %
6EP1311-1SH13
Approx. 80 %
6EP1321-1SH03
Approx. 78 %
6EP1322-1SH03
Approx. 84 %
6EP1351-1SH03
Approx. 80 %
6EP1352-1SH03
Approx. 85 %
6EP1331-1SH03
Approx. 83 %
6EP1332-1SH43
Approx. 87 %
6EP1332-1SH52
Approx. 87 %
6EP1311-1SH03
Approx. 4.6 W
6EP1311-1SH13
Approx. 8.1 W
6EP1321-1SH03
Approx. 6.4 W
6EP1322-1SH03
Approx. 10.2 W
6EP1351-1SH03
Approx. 7.1 W
6EP1352-1SH03
Approx. 10.8 W
6EP1331-1SH03
Approx. 6.3 W
6EP1332-1SH43
Approx. 8.7 W
6EP1332-1SH52
Approx. 13.8 W
6EP1311-1SH03
Approx. 1.5 W
6EP1311-1SH13
Approx. 1.5 W
6EP1321-1SH03
Approx. 1.8 W
6EP1322-1SH03
Approx. 1.9 W
6EP1351-1SH03
Approx. 2.1 W
6EP1352-1SH03
Approx. 2.3 W
6EP1331-1SH03
Approx. 2.0 W
6EP1332-1SH43
Approx. 1.8 W
6EP1332-1SH52
Approx. 2.0 W
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
27
Technical data
6.5 Protection and monitoring
6.5
Protection and monitoring
Output overvoltage protection
Yes, acc. to EN 60950
Current limitation
Typ. 110 % … 130 % of Ia rated when you turn
on the power supply overload capability with 150
% of Ia rated for typ. 200 ms
Short-circuit protection
Characteristic curve up to 0 V
Sustained short-circuit current
rms value
6EP1311-1SH03 Approx. 3.9 A
6EP1311-1SH13 Approx. 8.0 A
6EP1321-1SH03 Approx. 2.3 A
6EP1322-1SH03 Approx. 4.4 A
6EP1351-1SH03 Approx. 2.3 A
6EP1352-1SH03 Approx. 4.4 A
6EP1331-1SH03 Approx. 1.6 A
6EP1332-1SH43 Approx. 3.5 A
6EP1332-1SH52 Approx. 7.2 A
Overload/short-circuit indicator
-
LOGO!Power
28
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
7
EMC
EN 61000-6-2
Immunity for industrial environments
EN 61000-6-3
Emission for residential areas
Electrostatic discharges
EN 61000-4-2
6 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
Generic standards
80 to 1000 MHz 10 V/m
1000 to 2000 MHz 3 V/m
2000 to 2700 MHz 1 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4
4 kV on mains connections
Power surges
EN 61000-4-5
2 kV symmetrically on mains connections
2 kV at DC output
4 kV symmetrically on mains connections
500 V symmetrical/asymmetrical on DC
output lines
High-frequency fields
EN 61000-4-6
10 V; 0.15 to 80 MHz
Voltage dips
EN 61000-4-11
100 % for 20 ms
60 % for 200 ms
30 % for 500 ms
Voltage interruptions
EN 61000-4-11
100 % for 5000 ms
Emitted interference
EN 55022
Class B
Harmonic currents
EN 61000-3-2
Class A
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
29
EMC
LOGO!Power
30
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
8
Ambient conditions
Humidity class
Climate class 3K3 to EN 60721, no condensation
Ambient temperature
-20 ... +70 °C with natural convection
Derating:
• from +55 °C 2 %/K
Tested to:
Transport/storage temperature
•
EN 60068-2-1 coldness
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 damp heat, constant
•
EN 60068-2-14 change of temperature
-40 ... +85 °C
Tests (packed for shipping) according to:
Mechanical stressing in operation
•
EN 60068-2-1 coldness
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 damp heat, cyclic
Tested to:
•
•
EN 60068-2-6 vibration, test Fc
–
7 mm deflection in the range 5 - 9 Hz
–
2 G acceleration in the range 9 - 150 Hz
EN 60068-2-27 shock, test Ea
–
Damaging gases
Atmospheric pressure
Acceleration 150 m/s2, test duration 11 ms
Tested to:
•
EN 60068-2-42 sulfur dioxide: 10 cm3/m3, 4 days
•
EN 60068-2-43 sulfur dioxide: 1 cm3/m3, 4 days
Tested to:
• EN 60068-2-13
Operation:
•
1080 ... 795 hPa (-1000 to +2000 m)
• >2000 m: Derating factor of 5 % / 1000 m
Storage:
•
1080 ... 660 hPa (-1000 to +3500 m)
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
31
Ambient conditions
LOGO!Power
32
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
9
Safety
Primary/secondary isolation
Yes, SELV output voltage Ua according to EN
60950 and EN 50178
Test voltage
Primary/secondary 3 kVAC or corresponding DC
value
Protection class
Class II (without protective conductor)
Leakage current
< 250 µA
Degree of protection (EN 60529)
IP20
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
33
Safety
LOGO!Power
34
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
10
Certifications
Certifications
CE marking
Yes (2004/108/EC and 2006/95/EC)
UL/cUL approval
cULus-listed (UL 508, CSA C22.2 No.107.1), File
E197259
cURus (UL60950, CSA C22.2 No. 60950) File
E151273
NEC Class2 for types:
6EP1311-1SH03 5 V/3 A
6EP1321-1SH03 12 V/1,9 A
6EP1351-1SH03 15 V/1,9 A
6EP1331-1SH03 24 V/1,3 A
6EP1332-1SH43 24 V/2,5 A
CSA approval
CLASS 5318 01 - Power Supplies - for
Hazardous Locations
CLASS 5318 81 - Power Supplies - for
Hazardous Locations - Certified to U.S. Standard
Class I, Division 2, Groups A,B,C and D, T4
Class I, Zone 2, Ex nA II T4 IP20, AEx nA II T4
IP20
FM
Class I, Div. 2, Groups A, B, C, and D; T4
CB scheme
IEC 60950-1
Explosion protection
ATEX II 3G Ex nA IIC T3 X
SEMI F47 compliance 208 V-240 V
IEC 61000-4-11
EN 60079-0:2006 and EN 60079-15:2005
Marine approval
Germanischer Lloyd (GL)
6EP1352-1SH52: Cert. No.:24184-04HH
All other types: Cert. No.:47994-03HH
ABS, DNV, BV, LRS in preparation for selected
types
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
35
Certifications
LOGO!Power
36
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
11
MTBF
Mean Time Between Failures
In accordance with SN29500: >3500000 h at
40 °C, rated load, 24-h operation
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
37
MTBF
LOGO!Power
38
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Environment
12
The device is RoHS-compatible.
As a rule, only non-silicon precipitating materials are used.
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
39
Environment
LOGO!Power
40
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Accessories
13
No accessories.
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
41
Accessories
LOGO!Power
42
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
Service & Support
14
Further information via the home page
http://www.siemens.de/sitop/manuals or
http://support.automation.siemens.com
Phone: +49 (0) 911 895 7222
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
43
Service & Support
LOGO!Power
44
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619