MAGNETROL 910-A1A0-006

Echotel®
Model 910
Installation and Operating Manual
Ultrasonic
Level
Switch
Read this Manual Before Installing
This manual provides information on the Echotel Model
910 Ultrasonic Liquid Level Switches. It is important that
all instructions are read carefully and followed in
sequence. Detailed instructions are included in the
Installation section of this manual.
Conventions Used in this Manual
Certain conventions are used in this manual to convey
specific types of information. General technical material,
support data, and safety information are presented in
narrative form. The following styles are used for notes,
cautions, and warnings.
NOTES
Notes contain information that augments or clarifies
an operating step. Notes do not normally contain
actions. They follow the procedural steps to which
they refer.
Cautions
Cautions alert the technician to special conditions that
could injure personnel, damage equipment, or reduce
a component’s mechanical integrity. Cautions are also
used to alert the technician to unsafe practices or the
need for special protective equipment or specific materials. In this manual, a caution box indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
WARNINGS
Warnings identify potentially dangerous situations or
serious hazards. In this manual, a warning indicates an
imminently hazardous situation which, if not avoided,
could result in serious injury or death.
Safety Messages
The Echotel Model 910 is designed for use in Category II,
Pollution Degree 2 installations. Follow all standard
industry procedures for servicing electrical and computer
equipment when working with or around high voltage.
Always shut off the power supply before touching any
components. Although high voltage is not present in this
system, it may be present in other systems.
Electrical components are sensitive to electrostatic
discharge. To prevent equipment damage, observe
safety procedures when working with electrostatic
sensitive components.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) This device must accept any interference
received, including interference that may cause undesired operation.
WARNING! Explosion hazard. Do not connect or
disconnect equipment unless power has been switched off
or the area is known to be non-hazardous.
Low Voltage Directive
For use in Category II installations. If equipment is used
in a manner not specified by manufacturer, protection
provided by equipment may be impaired.
Notice of Trademark, Copyright, and Limitations
Magnetrol & Magnetrol logotype and Echotel are registered trademarks of Magnetrol International.
Copyright © 2011 Magnetrol International, Incorporated.
All rights reserved.
Performance specifications are effective with date of issue
and are subject to change without notice. Magnetrol
reserves the right to make changes to the product
described in this manual at any time without notice.
Magnetrol makes no warranty with respect to the accuracy of the information in this manual.
Warranty
All Magnetrol Model 910 Level Switches are
warranted free of defects in materials or workmanship for
two full years from the date of original factory
shipment.
If returned within the warranty period; and, upon
factory inspection of the control, the cause of the claim is
determined to be covered under the warranty; then,
Magnetrol will repair or replace the control at
no cost to the purchaser (or owner) other than
transportation.
Magnetrol shall not be liable for misapplication, labor
claims, direct or consequential damage or expense arising
from the installation or use of equipment.
There are no other warranties expressed or implied,
except special written warranties covering some
Magnetrol products.
Quality Assurance
The quality assurance system in place at Magnetrol guarantees the highest level of quality throughout the company. Magnetrol is committed to providing
full customer satisfaction both in quality products and
quality service.
The Magnetrol quality assurance system
is registered to ISO 9001 affirming its
commitment to known international
quality standards providing the strongest
assurance of product/service quality
available.
51-604 Echotel Model 910
1.0
Introduction
Echotel Model 910 Level Switches utilize ultrasonic
contact technology for measuring level in clean liquid
applications.
1.1
Ultrasonic
transducer
Transmit
crystal
Receive
crystal
Ultrasonic signal transmission
across transducer gap
Figure 1
Principle of Operation
The Model 910 Level Switch uses ultrasonic energy to
detect the presence or absence of liquid in a transducer gap.
The basic principle behind ultrasonic contact technology is
that high-frequency sound waves are easily transmitted
across a transducer gap in the presence of a liquid medium,
but are severely attenuated when the gap is dry. The
Model 910 uses an ultrasonic frequency of 3 MHz to
perform this liquid level measurement in a wide variety of
process media and application conditions.
The transducer uses a pair of piezoelectric crystals that are
encapsulated in epoxy at the tip of the 316 stainless steel
transducer. The crystals are made of a ceramic material,
that vibrates at a given frequency when subjected to an
applied voltage. The transmit crystal converts an electrical
signal from the Model 910 electronics into an ultrasonic
signal. When liquid is present in the gap, the receive
crystal is able to sense the ultrasonic signal from the
transmit crystal and convert it back to an electrical signal.
This signal is sent to the electronics to indicate the presence of liquid in the transducer gap. When there is no
liquid present, the ultrasonic signal is attenuated, and is
not detected by the receive crystal.
2.0
Installation
2.1
Unpacking
Unpack the instrument carefully. Inspect all units for
damage. Report any concealed damage to carrier within
24 hours. Check the contents of the packing slip and
purchase order. Check and record the serial number for
future reference when ordering parts.
Model # _____________________________________
Serial # _____________________________________
51-604 Echotel Model 910
3
2.2
Electrostatic Discharge (ESD)
Handling Procedure
Magnetrol electronic instruments are manufactured to the
highest quality standards. These instruments use electronic
components that may be damaged by static electricity
present in most work environments.
•
•
•
•
2.3
The following steps are recommended to reduce the risk of
component failure due to electrostatic discharge.
Ship and store circuit boards in anti-static bags. If an antistatic bag is not available, wrap the board in aluminum
foil. Do not place boards on foam packing materials.
Use a grounding wrist strap when installing and removing
circuit boards. A grounded workstation is recommended.
Handle circuit boards only by the edges. Do not touch
components or connector pins.
Make sure that all electrical connections are completely
made and none are partial or floating. Ground all equipment to a good, earth ground.
Preliminary Operational Check
1.
2.
3.
4.
After unpacking and before installation, perform the
following operational check on the unit in a nonhazardous area:
Apply proper operating voltage to terminals L1 and L2/N.
Power supply ground should be connected to the green
ground screw in housing base.
Fill a suitable container with liquid.
Place transducer gap in the liquid. The relay output should
actuate.
Remove transducer from the liquid. The relay output
should de-actuate. In case of malfunction, consult
Section 3.1, Troubleshooting on page 8.
Caution: This unit contains CMOS electronics which may become
damaged by static electricity. Do not touch any semiconductor devices unless you are properly grounded.
4
51-604 Echotel Model 910
2.4
Mounting
Filling line
High alarm
Gap must be
turned vertical
Low alarm
High alarm
Pump protection
Top View of
Horizontal Mounting
Pump
Low alarm
Figure 2
Typical Mounting Orientations
Conduit
connection
Never tighten by
turning housing
3 4 " NPT
Use wrench here
thread
Figure 3
Vertical Mounting
Gap must be
turned vertical
to allow medium
to fall through
Install so that
wrench flats
are vertical
Model 910 level switches are shipped as integral units with
the electronics assembled to the transducer. They may be
mounted in a variety of positions as shown in Figures 2
through 5.
Proper orientation of the transducer gap will provide
maximum performance in difficult applications. When
the switch is mounted horizontally, the transducer gap
must be turned vertical to allow proper drainage of the
liquid media. See Figures 2 and 4.
Screw transducer into the opening using pipe compound
or thread tape. If flanged, bolt unit to mating flange with
proper gasket.
Tank wall
Figure 4
Horizontal Mounting
Gap must
extend 1" (25 mm)
beyond
end of
nozzle
Caution: Never tighten unit on the tank connection by turning the
housing. Use a wrench on the transducer mounting nut
flats. Use thread tape or suitable pipe compound on the
threads. Do not overtighten.
When installed in a nozzle or pipe, the transducer gap
must extend into the tank at least one inch beyond the
inside tank wall. Refer to Figure 5.
Figure 5
Nozzle Mounting
51-604 Echotel Model 910
5
2.5
Wiring
2.5.1 Power
Power connections are made at the two-position terminal
block labeled TB1 within the electronics enclosure.
Use of 14–22 AWG wire is recommended.
NOTE: Observe all applicable electrical codes and proper wiring
procedures.
1. Make sure the power is turned off.
2. Unscrew and remove the housing cover.
3. Prevent moisture seepage into housing by installing an
approved seal-drain fitting in the conduit run leading to
the unit.
4. Route wires into housing.
5. Connect ground wire to green ground screw located in
the base of the housing. DO NOT proceed until ground
connection is made.
6. After grounding is complete, connect the power leads to
proper terminals as follows:
VAC Units
VDC Units
L1, L2/N
+, –
Caution: In hazardous areas, do not power the unit until the
conduit is sealed and the enclosure cover is screwed
down securely.
7. Dress wiring to ensure no interference or contact with
cover or circuit board components.
TB1 Power Wiring
6
51-604 Echotel Model 910
2.5.2 Relay
Model 910 switches have a number of possible relay
wiring options. The table below lists the relay contact
positions for all possible combinations of power failure,
condition of the transducer gap, and fail-safe jumper
position. The user must decide which combinations
constitute fail-safe and alarm conditions, and then select
the appropriate relay wiring and fail-safe position.
1. Run relay output wiring to the terminal blocks labeled
TB2 and TB3. Ensure that the load to be controlled is
within the relay’s rated capacity as shown in Section 3.3.2,
Electrical on page 10.
2. Select high or low fail-safe using the P1 jumper.
P1 Fail-safe
Jumper Position
Line Transducer
Power
Gap
On
Low level
Failure
On
High level
Relay Output Wiring
Failure
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Relay Terminals
CM to NC CM to NO
Closed
Open
Closed
Closed
Open
Closed
Closed
Closed
Open
Closed
Open
Open
Closed
Open
Open
Open
3. Replace housing cover. Installation is complete.
Caution: Never tighten unit to the tank connection by turning the
housing. Use a wrench on the transducer mounting nut
flats. Use thread tape or suitable pipe compound on
threads. Do not overtighten.
P1
P1
LL HL
P1 Fail-safe Jumper
51-604 Echotel Model 910
7
3.0
Reference Information
3.1
Troubleshooting
Caution: In hazardous areas, do not remove housing cover until power is disconnected and atmosphere is determined to be safe.
3.1.1 No signal with level change
a. Verify power and control circuit wiring.
b. Make sure liquid is filling the transducer gap.
c. Check for dense foam on surface or dried product in the gap. Unit will not function properly if
either condition exists.
d. Check transducer phone plugs for proper insertion in J1 and J2.
e. If control circuit does not actuate, consult factory.
3.1.2 Calibration
Model 910 switches do not require field calibration. The set point is not adjustable.
3.1.3 Switch chatter
a.
b.
c.
d.
Check voltage to make sure it is within tolerances shown in Section 3.3.2.
Check for turbulence. Relocate control or isolate from turbulence.
Check for excessive aeration.
Consult factory.
3.1.4 Control output will not de-actuate
a. Check transducer for plugged gap.
b. Check for dense foam or liquid in gap.
c. If control circuit does not de-actuate, consult factory.
3.2
Agency Approvals
AGENCY
APPROVED MODEL
PROTECTION METHOD
FM
910-XXXX-XXX
Explosion Proof
910-XXXX-XXX
Non-Incendive
910-XXXX-XXX
Explosion Proof
910-XXXX-XXX
Non-Incendive
CSA
ATEX
910-5XXX-XXX
910-PXXX-XXX
Note: Consult factory for Brazilian INMETRO BR-Ex d IIC T6 IP66 approval.
8
AREA CLASSIFICATION
Class I, Div. 1; Groups B, C & D
Class II, Div. 1; Groups E, F, & G
Class III, NEMA Type 4X, T6
Class I, Div. 2; Groups A, B, C, & D
Class II, Div. 2; Groups F & G
Class III, NEMA Type 4X, T5
Class I, Div. 1; Groups C & D
Class II, Div. 1; Group E, F, & G
Class III, Type 4X, T6
Class I, Div. 2; Groups A, B, C, & D
Class II, Div. 2; Groups E, F, & G
Class III, Type 4X, T5
II 1/2 G EEx d II C T6/EEx e II T6
These units have been tested to EN 50081-2
and EN 50082-2 and are in compliance with
the EMC Directive 89/336/EEC.
51-604 Echotel Model 910
3.3
Specifications
3.3.1 Physical
inches (mm)
4.63
(117) Dia.
3.44 (87)
Rotation clearance
3/4"
2.75
(70)
4.48
(113)
6.25
(158)
3/4"
3/4" NPT
tank connection
4.48
(113)
NPT
plugged
2.75
(70)
6.25
(158)
NPT
Optional
mounting
flange
Actuation point
4.63
(117) Dia.
3.00 Rotation
(76) clearance
3/4"
3.50
(88)
Actuation length ➀➁
Optional
mounting
flange
3/4" NPT
tank connection
Actuation point
.25 (6)
.25 (6)
.875 (22) Dia.
316 stainless steel housing
(Single 3⁄4" NPT conduit)
Aluminum sand cast housing
(Dual 3⁄4" NPT conduits)
4.63
(117) Dia.
4.63
(117) Dia.
3.44 (87)
Rotation clearance
3/4"
NPT
plugged
2.75
(70)
6.25
(158)
3/4"
3.50
(88)
Actuation length ➀➁
.875 (22) Dia.
4.48
(113)
NPT
NPT
3/4" NPT
3.44 (87)
Rotation clearance
2.75
(70)
(plugged)
4.48
(113)
3/4"
NPT
.25 (6)
1" BSP
process connection
Actuation point
Actuation length ➁
Actuation length ➀➁
Actuation point
.25 (6)
.875 (22) Dia.
Aluminum sand cast housing
(Dual 3⁄4" NPT conduit w/1" BSP process connection)
.25 (6)
.875 (22) Dia.
Aluminum sand cast housing
(Dual 3⁄4" NPT conduit with hygienic flange)
1" (Code 001) minimum with NPT threaded process connections.
2" (Code 002) minimum with hygienic or ANSI flanged process connections.
25 (Code 003) mm minimum with NPT threaded process connections.
50 (Code 005) mm minimum with 1" BSP, and hygienic or ANSI flanged process connections.
51-604 Echotel Model 910
9
3.3.2 Electrical
Power Supply:
120 VAC (+10%/-15%), 50/60 Hz
240 VAC (+10%/-15%), 50/60 Hz
24 VDC (±10%)
Power Consumption:
2.5 VA nominal
Gold flash DPDT relay: 10 amps @ 120 VAC, 240 VAC, 24 VDC Relay Output:
Hermetically sealed DPDT relay: 5 amps @ 120 VAC, 24 VDC, and
3 amps @ 240 VAC
Repeatability:
0.078" (2 mm)
Fail-safe Configuration:
Field selectable high or low
Calibration:
None required
Ambient Temperature:
Electronics: -40° to +158° F (-40° to +70° C)
Process Temperature:
Transducer: -40° to +250° F (-40° to +121° C)
Operating/Non-Operating Pressure: 800/1500 psig (55/103 bar)
Shock
ANSI/ISA-S71.03 Class SA1
Vibration
ANSI/ISA-S71.03 Class VC2
Gold flash DPDT relay is rated at 8 amps when used with housing codes 5 or P
3.4
Replacement Parts
No.
1
Description
PC Board
3
1
4
2
2
5
3
Housing
Base
Housing
Cover
Part Number
120 VAC w/10 amp relay
240 VAC w/10 amp relay
Z30-2043-003
Z30-2043-004
24 VDC w/10 amp relay
Z30-2043-002
120 VAC w/5 amp HS relay
Z30-2043-011
240 VAC w/3 amp HS relay
Z30-2043-012
24 VDC w/5 amp HS relay
Z30-2043-010
Aluminum w/FM and CSA
004-9182-002
Aluminum w/all 3 approvals
004-9182-008
316 SS w/FM and CSA
004-9140-001
316 SS w/CENELEC
004-9140-001
Aluminum w/FM and CSA
004-9105-001
Aluminum w/all 3 approvals
004-9105-005
316 SS w/FM and CSA
004-9142-001
316 SS w/CENELEC
004-9142-001
4
O-Ring
012-2101-345
5
Transducer
Consult factory
WARNING! Explosion hazard — Substitution of components may impair suitability for Class 1,
Division 2 rating.
WARNING! Explosion hazard — Do not disconnect
equipment unless power has been switched
off, or the area is known to be nonhazardous.
10
51-604 Echotel Model 910
3.5
Model Numbers
3.5.1 Model 910
HOUSING
A
Aluminum sand cast with 3⁄4" NPT dual conduit, FM or CSA approvals
Y
316 stainless steel with 3⁄4" NPT single conduit, FM or CSA approvals
P
Aluminum sand cast with 3⁄4" NPT dual conduit, FM, CSA and ATEX approvals
5
316 stainless steel with 3⁄4" NPT single conduit, ATEX approval
TRANSDUCER UNIT OF LENGTH
1
English (actuation length in inches)
M
Metric (actuation length in centimeters)
PROCESS CONNECTION
3
A
⁄4" NPT
2
1" NPT
9
1" BSP
3
11⁄2" hygienic flange (Compatible with Tri-Clamp® fittings)
4
2" hygienic flange (Compatible with Tri-Clamp® fittings)
1
1" 150 lb. ANSI raised face flange
C
11⁄2" 150 lb. ANSI raised face flange
D
2" 150 lb. ANSI raised face flange
E
1" 300 lb. ANSI raised face flange
F
11⁄2" 300 lb. ANSI raised face flange
G
2" 300 lb. ANSI raised face flange
INPUT POWER
0
120 VAC with 10 amp DPDT gold flash relay
1
240 VAC with 10 amp DPDT gold flash relay
2
24 VDC with 10 amp DPDT gold flash relay
H
120 VAC with 5 amp DPDT hermetically sealed relay
J
240 VAC with 3 amp DPDT hermetically sealed relay
K
24 VDC with 5 amp DPDT hermetically sealed relay
ACTUATION LENGTH
1" to 96" in 1" increments (with Transducer Unit of Length
code 1) Example: 4 inches = 004 3 cm to 244 cm in 1 cm increments (with Transducer Unit
of Length code M) Examples: 6 centimeters = 006 9
1
0
1" (code 001) minimum with NPT process connections, 2" (code 002) minimum with hygienic or ANSI flanged process connections.
2.5 cm (code 003) minimum with NPT process connections, 5 cm (code 005) minimum with 1" BSP, or hygienic or ANSI flanged
process connections.
Consult factory for longer lengths.
51-604 Echotel Model 910
11
ASSURED QUALITY & SERVICE COST LESS
Service Policy
Return Material Procedure
Owners of Magnetrol may request the return of a control
or any part of a control for complete rebuilding or replacement. They will be rebuilt or replaced promptly. Controls
returned under our service policy must be returned by
Prepaid transportation. Magnetrol will repair or replace
the control at no cost to the purchaser (or owner) other
than transportation if:
So that we may efficiently process any materials that are
returned, it is essential that a “Return Material
Authorization” (RMA) number be obtained from the
factory, prior to the material’s return. This is available
through a Magnetrol local representative or by contacting
the factory. Please supply the following information:
1. Returned within the warranty period; and
2. The factory inspection finds the cause of the claim
to be covered under the warranty.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be
charges for labor and the parts required to rebuild or
replace the equipment.
In some cases it may be expedient to ship replacement
parts; or, in extreme cases a complete new control, to
replace the original equipment before it is returned. If
this is desired, notify the factory of both the model and
serial numbers of the control to be replaced. In such
cases, credit for the materials returned will be determined
on the basis of the applicability of our warranty.
No claims for misapplication, labor, direct or consequential damage will be allowed.
1.
2.
3.
4.
5.
Company Name
Description of Material
Serial Number
Reason for Return
Application
Any unit that was used in a process must be properly
cleaned in accordance with OSHA standards, before it is
returned to the factory.
A Material Safety Data Sheet (MSDS) must accompany
material that was used in any media.
All shipments returned to the factory must be by prepaid
transportation.
All replacements will be shipped F.O.B. factory.
NOTE: See Electrostatic Discharge Handling Procedure
on page 4.
5300 Belmont Road • Downers Grove, Illinois 60515-4499 • 630-969-4000 • Fax 630-969-9489 • www.magnetrol.com
145 Jardin Drive, Units 1 & 2 • Concord, Ontario Canada L4K 1X7 • 905-738-9600 • Fax 905-738-1306
Heikensstraat 6 • B 9240 Zele, Belgium • 052 45.11.11 • Fax 052 45.09.93
Regent Business Ctr., Jubilee Rd. • Burgess Hill, Sussex RH15 9TL U.K. • 01444-871313 • Fax 01444-871317
Copyright © 2011 Magnetrol International, Incorporated. All rights reserved. Printed in the USA.
Tri-Clamp® is a registered trademark of Ladish Co.
BULLETIN: 51-604.16
EFFECTIVE: February 2011
SUPERSEDES: July 2010