UNPACKING
Unpack the instrument carefully. Make sure all components
have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the carton/crates against the packing slip and report any discrepancies to Magnetrol. Check the nameplate model number
(Model number/approvals as per inserted separate sheet) to
be sure it agrees with the packing slip and purchase order.
Check and record the serial number for future reference
when ordering parts.
0038
0343
These units are in compliance with:
1. The EMC directive 89/336/EEC. The units
have been tested to EN 61000-6-4 and EN 61000-6-2.
2. The ATEX directive 94/9/EC. EC-Type examination
number DMT 03ATEX E037 (4 th digit A only).
3. The PED directive 97/23/EC (pressure equipment directive). Safety accessories per category IV module H1.
Model and
serial number
MOUNTING
The Solitel can easily be bench tested prior to installation. Power the unit and insert the vibrating part in a sample of the medium. When the unit does not react properly, the density setting of the unit needs to be adjusted (see WIRING).
Correct mounting
Incorrect mounting
Avoid mounting the
sensor in a recess
where build-up
could dampen the
vibration.
A deflection plate is
required when the
probe is exposed to
falling material or, in
case of a low level
switch, when the drag
force of the emtying
material exceed the
specifications.
Full
Empty
Caution:
- Units with extended flexible sensor:
- Low level alarms: Install these in line with the outlet of the tank (as shown in the above left picture).
- A higher Pull force (F) of 45 kN, will cause the cable to break and will permanently damage the unit.
- Units with standard / extended rigid sensor:
- Side mounted: Install these under a preferred angle of 45°. This will assure a proper functioning of the self-cleaning of
the rod (as shown in the above left picture).
- Higher mechanical loads than 85 Nm (M), will cause permanent damage to the unit. Avoid to install as low level alarm
in media with high SG.
F
M
M
2
F
WIRING/SETTING
Status LED
Dip switches for settings
1
2
3
250VAC
8A/AC1
N L1
1 2 3
4 5 6
Relay or solid
state output
POWER
SETTINGS
Dip switch
position
Density
3
Time delay
2
Failsafe
1
Up
> 0,1 kg/dm3
5s
Low level
Down
< 0,1 kg/dm3
2s
High level
16 .. 40 V AC (50/60 Hz) / 19 .. 55 V DC
85 .. 265 V AC (50/60 Hz) / 120 .. 375 V DC
OUTPUT DIAGRAM
Failsafe mode
Level
Relay status
Relay output
4
Green
Solid state output
2,7 k
6
5
6
High level
4
Red
On
2,7 k
6
5
6
4
Off
2,7 k
6
5
6
Low level
4
5
5
4
Energized
Red
5
4
De-energized
Green
5
4
Energized
On
2,7 k
6
6
5
4
De-energized
4
No power
High/Low level
Not lit
Off
2,7 k
6
5
6
De-energized
4
5
Off
3
WIRING
SPDT Relay (8 A @ 250 V AC / 1 A @ 24 V DC)
85 ... 265 V AC / 120 ... 375 V DC or 19 ... 55 V DC / 16 ... 40 V AC
Solid State output
85 ... 265 V AC / 120 ... 375 V DC or 19 ... 55 V DC / 16 ... 40 V AC
Connection to an opto-coupled input
Connection to a logical voltage input
Connection to a load
max 350 mA
Device to be
controlled + 5 V
IN
IN
COM
max 50 V
+ 24 V
PLC
4
GND
REPLACEMENT PARTS
Electronic module for model:
Partnumber
VSx-S2BA-xxx
030-9015-001
VSx-S2BD-xxx
030-9015-002
VSx-S2EA-xxx
030-9015-003
VSx-S2ED-xxx
030-9015-004
VHx-S2BA-xxx
030-9015-005
VHx-S2BD-xxx
030-9015-006
VHx-S2EA-xxx
030-9015-007
VHx-S2ED-xxx
030-9015-008
NOTE: Dust Ex units need to return to factory for repair.
REPLACEMENT PROCEDURE FOR ELECTRONIC MODULE:
The replacement electronic modules are delivered unassembled to ease the tuning from the sensor to the electronics. This simple procedure allows to replace the module in the field, without dismantling the unit.
1
2
3
Step 1: Switch off power and unplug both power and output terminal blocks.
Loosen the two screws in the base of the housing
to remove electronic module.
250VAC
8A/AC1
N L1
1 2 3
4 5 6
Step 2: Snap off the cover of the new module, so that the
internals of the module are visible. Refasten the
new module in the base of the housing and plug in
the power block.
Density
Tuning
potentiometer
LED needs to blink
when the tuning is
O.K.
Status LED
N L1
1 2 3
Step 3: Turn power on and
- put the density dip switch “3” in the Low (down) position
- the internals of the electronic module show a potentiometer and an LED. Tweek the potentiometer until the LED lits
up. The electronics are now tuned with the electronics. Remove power block to snap the cover onto electronic module and reconnect power block.
Step 4: Adjust the settings as per initial setting (see WIRING on page 3) and reconnect the output block.
5
SPECIFICATIONS
PERFORMANCE
Description
Response time
Electromagnetic compatibility
Specification
< 1,8 s (when covered) – 2 s (when free) or with time delay: 5 s + 1,5 s (field selectable)
Meets CE requirements (EN 61000-6-4, EN 61000-6-2)
PHYSICAL/FUNCTIONAL SPECIFICATIONS
Description
Specification
Input voltage
Power consumption
85 ... 265 V AC / 120 ... 375 V DC or 19 ... 55 V DC / 16 ... 40 V AC
1.3 VA
8 A SPDT relay @ 250 V AC (1A @ 24 V DC)
Solid state output - 350 mA / 50 V peak
Output status LED (green/red) – visual indication on cover
Signal output
Indication
IP 67, Aluminium (2x M20 x 1,5 and 2 x 1/2" NPT - all plugged)
2 x M20 x 1,5 cable gland separately included
Housing material
Approvals
Min density
Max mechanical load on sensor
Weight of unit
ATEX II 1/2 D IP 65
All wetted parts of polished 316 Ti SST (1.4571) (except VSK)
PE coated cable (VSK)
Threaded: 11/2" BSP (G 11/2)
VSH/VHH: 235 mm (9.2")
VSR/VHR: from 500 mm up to 3000 mm (19.7" up to 9.8')
VSK: from 1 m up to 20 m (3.3' up to 65.6')
25 bar abs. (360 psia)
Flexible version VSK: 6 bar abs. (87 psia)
0,05 kg/dm3 - max granular size: 10 mm (0,39")
VSH/VHH: 85 Nm
2,5 kg (VSH/VHH) + 1,4 kg/m for VSR/VHR + 0,6 kg/m for VSK
Description
Process temp.
Ambient temp.
-30 °C to +110 °C
(-20 °F to +230 °F)
-30 °C to +160 °C
(-20 °F to +320 °F)
-35 °C to +95 °C
(-30 °F to +200 °F)
-30 °C to +50 °C
(-20 °F to +120 °F)
-30 °C to +35 °C
(-20 °F to +95 °F)
-30 °C to +60 °C
(-20 °F to +140 °F)
Sensor material
Mounting
Actuation length
Max pressure
VSH/VSR
Max temperature
VHH/VHR
VSK
AMBIENT TEMPERATURE (TA) VERSUS PROCESS TEMPERATURE (TP)
TA (°C)
50
35
20
-30
(VSK: -35 °C)
0
-30
6
0
50
95
VSK
110
VSH/
VSR
160 TP (°C)
VHH/
VHR
temp. at process conn.
max +90 °C (+195 °F)
max +135 °C (+275 °F)
max +85 °C (+185 °F)
MODEL IDENTIFICATION
A complete measuring system consists of:
1. One code for electronics and sensor
2. Optional: threaded mounting flanges – consult factory
1. One code for electronics and sensor
BASIC MODEL NUMBER
Standard electronics - max process temperature 110 °C (230 °F) - 90 °C (200 °F) for flexible version
V S H
V S R
V S K
Solitel with STANDARD sensor
Solitel with EXTENDED RIGID sensor
Solitel with FLEXIBLE sensor
- 235 mm (9.2") insertion length
- selectable insertion length / 10 cm (3.9") increments
- selectable insertion length / 1 m (3.3') increments
High temperature electronics - max process temperature 160 °C (320 °F)
V H H
V H R
Solitel with STANDARD sensor
Solitel with EXTENDED RIGID sensor
- 235 mm (9.2") insertion length
- selectable insertion length / 10 cm (3.9") increments
HOUSING MATERIAL / CABLE ENTRY / APPROVAL – IP 67
S
A
Aluminium, 4 entries (2x M20 x 1,5 and 2 x 1/2" NPT - all plugged)
Aluminium, 4 entries (2x M20 x 1,5 and 2 x 1/2" NPT - all plugged)
General purpose
ATEX II 1/2 D IP 65 (Dust Ex)
SIGNAL OUTPUT
2 B
2 E
8 A SPDT relay
Solid state output 350 mA / 50 V
POWER SUPPLY
A
D
85 .. 265 V AC / 120 ..375 V DC
19 .. 55 V DC / 16 .. 40 V AC
INSERTION LENGTH
0
0
3
0
0
0
5
0
0
2
0
0
0
1
0
VSH/VHH:
VSR/VHR:
235 mm (9.2")
min 50 cm (19.7")
max 300 cm (9.8'), Specify length in 10 cm (3.9") increments
min 1 m (3.3')
max 20 m (65.60'), Specify length in 1 m (3,3') increments
VSK:
complete code for SOLITEL electronics and sensor
V
DIMENSIONS IN mm (inches)
VSH/VHH
VSR/VHR
100 (3.94)
89 (3.50)
100 (3.94)
89 (3.50)
M20 x 1,5
2 entries
120
(4.72)
100 (3.94)
89 (3.50)
M20 x 1,5
2 entries
120
(4.72)
M20 x 1,5
2 entries
120
(4.72)
1/2"
NPT
2 entries
1/2" NPT
2 entries
1/2"
NPT
2 entries
1 1/2" BSP
process connection
1 1/2" BSP
process connection
1 1/2" BSP
process connection
Ø 44 (1.73)
Ø 44 (1.73)
Insertion
length
500 - 3000
(19.68 - 118.11)
Insertion
length
235 (9.25)
VSK
Insertion
length
1000 - 20000
(39.37 - 787.40)
Ø 44 (1.73)
161
(6.34)
161
(6.34)
161
(6.34)
7
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
the purchaser, (or owner) other than transportation cost if:
a. Returned within the warranty period; and,
b. The factory inspection finds the cause of the malfunction to be defective material or workmanship.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.
RETURNED MATERIAL PROCEDURE
So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorisation” (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:
1. Purchaser Name
2. Description of Material
3. Serial Number and Ref Number
4. Desired Action
5. Reason for Return
6. Process details
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
All replacements will be shipped FOB factory.
BULLETIN N°:
EFFECTIVE:
SUPERSEDES:
UNDER RESERVE OF MODIFICATIONS
www.magnetrol.com
®
BE 51-639.2
MAY 2007
March 2003
BENELUX
Heikensstraat 6, 9240 Zele, België
Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: [email protected]
DEUTSCHLAND
Alte Ziegelei 2-4, D-51491 Overath
Tel. 02204 / 9536-0 • Fax. 02204 / 9536-53 • E-Mail: [email protected]
FRANCE
40 - 42, rue Gabriel Péri, 95130 Le Plessis Bouchard
Tél. 01.34.44.26.10 • Fax. 01.34.44.26.06 • E-Mail: [email protected]
ITALIA
Via Arese 12, I-20159 Milano
Tel. (02) 607.22.98 (R.A.) • Fax. (02) 668.66.52 • E-Mail: [email protected]
UNITED
KINGDOM
Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
Tel. (01444) 871313 • Fax (01444) 871317 • E-Mail: [email protected]
INDIA
C-20 Community Centre, Janakpuri, New Delhi - 110 0058
Tel. 91 (11) 41661840 • Fax 91 (11) 41661843 • E-Mail: [email protected]