ETC A109156220M

Timers
Multi-function
Type A 109
• 2 selectable functions:
- Delay on operate
- Interval timer
• 5 selectable time ranges: A 109 ...M: 1 s to 10 m
A 109 ...H: 1 m to 10 h
• Automatic start
• Knob-adjustable time within range
• Oscillator-controlled time circuit
• Repeatability deviation: ≤ 1%
• Output: 10 A SPDT or 8 A DPDT relay
• Plug-in type module
• LED-indication for relay on
• AC or DC power supply
Product Description
Ordering Key
Multi-function, multi-voltage,
miniature time relays up to 10 h
each covering 3 selectable
time ranges. The combination of functions causes these
Function
Type
Output
Power supply
Time range
economical timers to be extensively applied, e.g. monitoring pumps or where a time
function is needed to extend
a certain operation.
A 109 156 220M
Type Selection
Plug
Output
Time ranges
Supply: 120 VAC, 24 VAC/DC
Supply: 220 VAC, 24 VAC/DC
Circular
SPDT
1 s - 10 m
1 m -10 h
A 109 156 120M
A 109 156 120H
A 109 156 220M
A 109 156 220H
DPDT
1 s - 10 m
1 m -10 h
A 109 166 120M
A 109 166 120H
A 109 166 220M
A 109 166 220H
Time Specifications
Time ranges
Selectable by DIP-switch
Time range accuracy
A 109 ... ...M A 109 ... ...H
1 s - 10 s
1 m - 10 m
10 s - 100 s 10 m - 100 m
1 m - 10 m 1 h - 10 h
0 to +30% on max.
min. actual time ≤ min. set time
Repeatability deviation
Time variation
Within rated power supply
and ambient temperature
Reset
Time and/or relay
≤ 1%
≤ 0.2%/°C
≤ 0.05%/V
Power supply interruption min.
≥ 500 ms
Output Specifications
Output
Basic electrical insulation
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
Operating frequency
Insulation voltages
Rated insulation voltage
Rated transient protection volt.
A 109 156
SPDT relay
250 VAC (rms) (contact/electronics)
µ (micro gap)
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations (at max. load)
≤ 7200 operations/h
A 109 166
DPDT relay
250 VAC (rms)(contacts/elec., contact/contact)
µ (micro gap)
8 A/250 VAC (2000 VA)
0.4 A/250 VDC (100 W)
4 A/25 VDC (100 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations (at max. load)
≤ 7200 operations/h
≥ 2.0 kVAC (rms)(contact/electronics)
4 kV (1.2/50 µs) (contact/electronics) (IEC 60664)
≥ 2.0 kVAC (rms) (contact/electronics)
4 kV (1.2/50 µs)(contact/electronics) (IEC 60664)
Specifications are subject to change without notice (25.10.99)
1
A 109
Supply Specifications
General Specifications
Power supply AC types
Rated operational voltage
through pins 2 & 10
220
120
or pins 6 & 10
Dropout tolerance
Rated insulation voltage
Rated transient protection volt.
Power ON delay
Power OFF delay
Indication for
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Installation cat. III (IEC 60664)
220 VAC + 15/- 20%, 45 to 65 Hz
120 VAC + 15/- 20%, 45 to 65 Hz
24 VAC + 15/- 20%, 45 to 65 Hz
≥ 10 ms
None
4 kV (1.2/50 µs) @ 230 VAC
2.5 kV (1.2/50 µs) @ 120 VAC
800 V (1.2/50 µs) @ 24 VAC
(line/neutral)
≤ 500 ms
≥ 500 ms
LED, red
IP 20 B
2 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-40° to +80°C (-40° to +176°F)
85 g
Power supply DC types
Rated operational voltage
through pins 6 & 10
24 VDC ± 15%
24 VDC + 15/- 20%
(pin 6 pos.)
Rated insulation voltage
None
Rated transient protection volt. 800 V (1.2/50 µs)
Consumption
AC supply
60 mA @ 50 Hz/
70 mA @ 60 Hz
DC supply
1W
Mode of Operation
Example 1
Delay on operate
The delay period begins when
power supply is applied.
At the end of the set delay
period, the relay will operate
and not release again until
power supply is disconnected.
After disconnection of power
supply, a recovery period of
500 ms should be allowed
before the relay is activated
again.
If power supply is removed
for more than 500 ms before
the relay operates, the time is
reset and the relay is ready
for a new time period.
Wiring Diagrams
Example 2
Interval timer
The relay operates and the
time period starts when power
supply is applied.
At the end of the set delay
period, the relay releases and
will not operate again until
power supply is reapplied.
A recovery period of 500 ms
should be allowed before the
relay is activated again.
If power supply is removed
for more than 500 ms before
the time has expired, the relay releases and the time is
reset.
Accessories
Socket◊
Hold down spring◊
Mounting rack
Socket cover
Potentiometer lock
Power supply
Power supply
120 or 220 VAC
Function/Time Setting
Selection of time range
DIP-switch selector (1 & 2).
Selection of function
DIP-switch selector (3).
Time
ranges A 109 ... ...M A 109 ... ...H
1. Delay on operate
1 - 10 s
1 - 10 m
10 - 100 s
10 - 100 m
1 - 10 m
S 411
HF
SM 13
BB 4
PL 1
24 VAC/DC
1 - 10 h
2. Interval timer
Time setting:
Knob-adjustable on relative
scale 1-10.
For further information refer
to "Accessories". For other
AC/DC voltages refer to "General Information".
Operation Diagram
Power supply
Example 1: Relay on
Example 2: Relay on
2
Specifications are subject to change without notice (25.10.99)