ETC ECACT231M

Timers
Symmetrical Recycler and Delay on Operate
Type ECA
•
•
•
•
•
•
•
•
•
Dual-function timer
Time range 0.1 s to 10 h
Automatic start (ON or OFF time first)
Knob-adjustable time setting
Knob selection of time range and function
Oscillator-controlled time circuit
Repeatability deviation: ≤ 0.2%
Output: 5A SPDT
For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 22.5 mm Euronorm housing
• LED-indication for relay and power supply ON
• Combined AC and DC power supply
Product Description
Ordering Key
Dual-function timer, combined symmetrical and delay
on operate function with 3
selectable time ranges within
0.1 s to 1 m or 1 m to 10 h.
For mounting on DIN-rail. Often used in applications e.g.
where water has to be applied
to selected areas for a set period of time.
Housing
Function
Type
Output
Power supply
Time range
ECA C T23 1M
Type Selection
Mounting
Output
Time range
Supply: 24 VAC/DC & 115-230 VAC
For DIN-rail
SPDT
SPDT
0.1 s - 1 m
1 m - 10 h
ECA C T23 1M
ECA C T23 10H
Time Specifications
Output Specifications
Time ranges
Type 1 M
Selectable by rotary switch
Output
Rated insulation voltage
Contact ratings (AgCdO)
AC 1
Resistive loads
DC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Type 10 H
Selectable by rotary switch
Time range accuracy
Repeatability deviation
Time variation
Within rated power supply
and ambient temperature
Reset
Time and relay
0.1 s - 1 s
1 s - 10 s
0,1 m - 1 m
1 m - 10 m
0.1 h - 1 h
1 h - 10 h
±10% on max.
min. actual time
≤ min. set time
≤ 0.2%
≤ 0.05%/V
≤ 0.2%/°C
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT relay
250 VAC (contact/elect.)
µ (micro gap)
5 A, 250 VAC
5 A, 24 VDC
2 A, 250 VAC
3 A, 24 VDC
≥ 40 x 106 operations
≥ 105 operations
(at max. load)
≤ 7200 operations/h
2 kVAC (rms)
4 kV (1.2/50 µs)
Power supply interruption
≥ 200 ms
Specifications are subject to change without notice (25.10.99)
1
ECA
Supply Specifications
General Specifications
Power supply
Rated operational voltage
Through term. A1 & A2 T23
Frequency
Through term. A2 & A3 T23
Frequency
Voltage interruption
Dielectric voltage
Rated impulse withstand
voltage
Rated operational current
EMC
Overvoltage cat. III (IEC 60664)
(IEC 60038)
115-230 VAC, -10/+15%
50/60 Hz, -5/+5 Hz
24 VAC/DC, -10/+15%
50/60 Hz, -5/+5 Hz
≤ 40 ms
None
4 kV (1.2/50 µs)
20 mA @ 24 VDC
40 mA @ 24 VAC
20 mA @115 VAC
40 mA @ 230 VAC
Immunity
Power ON delay
Power OFF delay
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Screw terminals
Tightening torque
Approvals
Electromagnetic
Compatibility
Acc. to IEC 60801-4
Acc. to IEC 60801-5
≤ 200 ms
≥ 200 ms
LED, green
LED, yellow
IP 20
3
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
125 g
Max. 0.5 Nm acc. to IEC 60947
UL, CSA, SEV
Mode of Operation
Function 1 (F1)
Delay on operate timer
The delay period begins when
power supply is applied. At
the end of the set delay, the
relay will operate and will not
release until power supply is
interrupted for at least 200 ms.
is reset to zero, and the relay
is ready for a new time period.
Function 2 (F2)
Recycler,
OFF-time period first.
The time period begins when
power supply is applied. At the
end of the first time period,
the relay operates. When the
second time period (equal to
the first) has expired, the relay
releases.
If power supply is interrupted
for at least 200 ms before the
relay operates, the time circuit
Wiring Diagram
115-230 V
This sequence continues with
equal time periods until power
supply is interrupted for at
least 200 ms.
riod, the relay releases. When
the second time period (equal
to the first) has expired, the
relay operates.
Function 3 (F3)
Recycler,
ON-time period first
The relay operates and the
time period begins when
power supply is applied. At
the end of the first time pe-
This sequence continues with
equal time periods until power
supply is interrupted for at
least 200 ms.
Time Setting
~
24 V
L
Selection of time ranges
Upper knob:
Selectable on 3-position rotary switch.
~
µ
Time setting
Lower knob:
Knob-adjustable on relative
scale 1-10.
Selection of mode of operation
Centre knob:
Selectable on 3-position rotary switch.
N
Operation Diagram
Power supply
F1 Relay ON
F2 Relay ON
F3 Relay ON
2
Specifications are subject to change without notice (25.10.99)