Phase Failure Relays WILMAR™ Protective Relays – 1000 Series Function: 47 • ANSI/IEEE C37.90-1978 TERMINAL STRIPS #6 - 32 SCREWS • UL file No. E58048 • CSA file No. LR61158 Phase failure relays protect motors, equipment and personnel from damage or injury caused by open phase, reversed phase sequence, or low voltage in a three phase system. Models are available for 50 and 60 Hz with voltages up to 575 volts. Motor control switchboards are a common application. 3 13/16 Operation: The contacts of the relay will close only when it senses normal conditions of three phase power at the proper phase sequence. 3.0 1 /2 3 /8 7 3 The relay contacts will remain in their normally open position (de-energized) when voltage with incorrect phase sequence is applied, one or more phases are open, or at undervoltage condition. 2 3/4 1/2 3 11/64" DIA. 4 MTG. HOLES PART NUMBER SELECTION Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm. PART NUMBER SELECTION PRODUCT SPECIFICATIONS Part Number 1000 Series Nominal Voltage ............................. See Table Voltage Drop-Out ........................... 75% to 100% of nominal, screwdriver adjustable Pick-Up to Drop-Out Differential .... 3% approx. Ambient Operating Temperature .... -40oC to +70oC Temperature Drift ........................... ± 1% Time Delay ..................................... See Curve Output Contacts ............................. One set, normally open Contact Ratings .............................. 10 amp at 28 VDC resistive 10 amp at 230 VAC resistive 30 Sample Part No. 1004X Type: 1001 = 120 V, 60 Hz, 3 phase,L-L 1007 = 208 V, 60 Hz, 3 phase, L-L 1002 = 230 V, 60 Hz, 3 phase,L-L 1012 = 300 V, 60 Hz, 3 phase, L-L 1013 = 350 V, 60 Hz, 3 phase, L-L 1003 = 380 V, 50 Hz, 3 phase, L-L 1004 = 460 V, 60 Hz, 3 phase,L-L 1005 = 525 V, 60 Hz, 3 phase,L-L 1006 = 575 V, 60 Hz, 3 Phase, L-L Mounting: X = Flange Blank - Stud Consult factory for additional models and options Notes: 1. Remove screw for access to the undervoltage adjustment. 2. Clockwise rotation of the adjustment potentiometer will raise the drop-out voltage. Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)