POWER-ONE FXP7000

FXP7000 AC-DC Series Data Sheet
Front-End
r
e
w
o
P
d
te
u
ib
tr
Dis
Features
• Three-phase AC input
• Suitable for 3U or 5U height mounting
• Single-wire current share or Droop current share
• Remote voltage adjust and current monitoring
• Overtemperature, overload, and overvoltage protection
• LED supply status indicators
• Current share control for up to 30 units
• Standard & customized rack adaptors available
• Front panel selectable-input-range
FXP7000
Front and Rear Views
The FXP7000 Series of rack-mounted power systems
provides AC front-end capability to automatic test
equipment, telecom, data communications, and other
distributed power designs. The pluggable FXP supplies
do not include an output isolation diode and may be
paralleled up to 210 kW of total output power. These
supplies provide excellent protection against input
voltage transients.
Access to interfaces for remote sensing, remote voltage
adjust, current sharing, current monitoring, power supply
status, standby voltage and inhibit, as well as power
connections, is through a connector at the rear of the
supply. The FXP has its fan, handles, voltage adjust, and
indicator lights on the front panel and a single hot-plug
connector on the rear. Airflow is from the front through
the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to
the positive or negative output or sense line of the power
supply. The output is floating with respect to the chassis
and may be used as a positive or negative polarity
supply.
The FXP7000 Series meets international safety
requirements and is CE Marked to the Low Voltage
Directive. This series operates on three-phase European
voltages as well as (up to) 480VAC, delta or wye.
Hot-Pluggable Model
MODEL
FXP7000-48-S
OUTPUT
VOLTAGE
48V
INPUT VOLTAGE RANGE
3-PHASE (VAC)
180 to 264 or 342 to 528
ADJUSTMENT
RANGE
MAXIMUM OUTPUT
CURRENT
45.6V to 50.4V
145A
LINE
REGULATION
LOAD
REGULATION (NOTE 1)
INITIAL SETTING
ACCURACY
0.2%
47.90V to 48.10V
0.15%
NOTES: 1) With Remote Sense connected.
Input Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
Input Voltage - AC
3-phase delta low input range, nominal.
3-phase delta high input range, nominal.
Continuous deviation from the above nominals.
Per phase at full rated load.
FXP7000 at 180 VAC:
Internally limited.
Vin = 264VAC (one cycle). 25° C:
Vin = 528VAC (one cycle). 25° C:
AC input.
After last AC line peak at full power.
208 VAC:
400 VAC:
Switching frequency, fixed.
200
380
-10
Input Current
Inrush Surge Current
Input Frequency
Hold-up Time
Operating Frequency
Power Factor
MAY 31, 2005 revised to JAN 09, 2007
MAX
240
480
+10
30
38
38
60
50
17
13
UNITS
VAC
%
ARMS
APK
Hz
ms
100
0.90
Page 1 of 8
NOM
kHz
W/VA
www.power-one.com
FXP7000 AC-DC Series Data Sheet
Output Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
Output Voltage
Adjustment Range
Output Power
Output Current
Efficiency
Regulation
An additional 1.0 Volt is provided to the output terminals to provide for
load lead losses.
Continuous duty rating.
Continuous duty rating.
Full rated load (208Vac).
Load, Maximum deviation with 0 to 100% load change:
With Remote Sense connected:
With Remote Sense not connected:
Utilizing Droop Current Share:
Line, Under all specified operating conditions.
Measured at mating connector w/ 0.01µF + 10µF Tant.
20 MHz BW:
100 MHz BW:
Output voltage overshoot/undershoot at turn-on.
Minimum loading required to maintain regulation.
Maximum recovery time, to within 1% of initial set
Time:
point due to a 25% load change, 1A/µS.
Deviation:
Time required for initial output voltage stabilization after power-up.
Time required for output voltage to rise from 10% to 90%.
45.6
48
50.4
V
7000
145
Watts
A
%
Ripple & Noise
Overshoot / Undershoot
Minimum Loads
Transient Response
Turn-On Delay
Turn-on Rise Time
88
91
0.2
0.75
2.0
0.2
1
2
0
%
% p-p
800
3.2
3
100
%
A
µs
%
s
ms
0
Interface Signals and Protection
PARAMETER (NOTE 1,2)
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
AC Power Fail Warning
Auxiliary Power
Warning provided prior to Vout dropping 5% after loss of AC input.
Output voltage - diode isolated. Inclusive of line, load, and initial tolerances.
Output current.
Monitor output current over a compliance range of 0~10V.
Normal output:
Total error current:
Static sharing deviation as a percent of full-load rating
Active:
for loads >10%.
Passive:
Maximum signal resistance in high input voltage range selection.
Warning provided prior to protective reduction in current limit.
Voltage required to enable supply (0.5 mA sink). (NOTE 3)
Voltage required to enable supply (6 mA sink). (NOTE 3)
Straight line current limit (above approx. 5V Vout).
Signal level on overload.
Occurs on overload when Vout is below approx. 5V.
Iavg:
May operate in burst-mode.
Deviation from adjusted Vout that is considered as a fault.
Output voltage swing available through Margin pin (analog).
Time between fault warning and shutdown.
Latching shutdown.
Latch style overvoltage protection.
Resistance to logic ground upon insertion of supply.
Maximum load lead loss compensation (round trip).
4
11.6
12.0
12.4
500
ms
V
mA
0.5
0.10
0
Current Monitor
Current Share
Input Range Select Status
Loss of Phase Warning
Output Inhibit
Output Interlock
Output Overload Protection
Output Overload Warning
Output Short Circuit Protection
Output Voltage Fault Signal
Output Voltage Margin
Overtemperature/
Fan Failure Warning
Overvoltage Protection
Power Supply Present Signal
Remote Sense
0.5
5
10
0.10
500
1.0
1.0
156
149
2.2
25
90
mA/A
mA
%
⍀
ms
V
V
A
V
A
±3
±4.8
100
±4
±5.0
±5
±5.2
%
%
ms
55.2
57.6
1000
60.0
V
⍀
V
1.0
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V.
2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase
imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading.
3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable.
Contact factory for additional design details.
MAY 31, 2005 revised to JAN 09, 2007
Page 2 of 8
www.power-one.com
FXP7000 AC-DC Series Data Sheet
Safety, Regulatory, and EMI Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Agency Approvals
UL60950/CSA60950-00 (cULus), IEC60950, EN60950 (TÜV),
CE marked for the Low Voltage Directive
FCC CFR title 47 Part 15 Sub-Part B - Conducted.
EN55022 / CISPR 22 Conducted.
Per EN61000-4-2, level 4.
Per EN61000-4-3, level 3.
Per EN61000-4-4, level 4.
Per EN61000-4-5.
Line-to-Line:
Line-to-Ground:
Per SEMI F47-0200 FXC/FXP7000
Per UL60950 and
FXP7000 at 240 VAC, 60 Hz:
EN60950:
FXP7000 at 400 VAC, 50 Hz:
FXP7000 at 480 VAC, 60 Hz:
Electromagnetic Interference
ESD Susceptibility
Radiated Susceptibility
EFT/Burst
Input Transient Protection
Voltage Sag Immunity
Leakage Current
MIN
NOM
MAX
A
A
8
10
±4
4
3
UNITS
Class
kV
V/M
kV
kV
Pending
5
7
10
mA
MAX
UNITS
10k
40k
40
70
85
.02
95
+20
+40
1
6.15
ASL Ft.
Environmental Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Altitude
Operating.
Non-Operating.
MIN
Operating Temperature
Storage Temperature
Temperature Coefficient
Relative Humidity
Shock
Vibration
Airflow
At 100% load:
At 50% load:
NOM
0
-40
0°C to 70°C (after 15-minute warm-up).
Non-Condensing.
Operating: half-sine 10 ms, 3 axis
Non-operating: half-sine 10 ms, 3 axis
Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz
Non-operating: random 10-2000 Hz
Airflow provided through the supply from front to rear.
155
4.4
555
2.8
Weight
MAY 31, 2005 revised to JAN 09, 2007
29
13
Page 3 of 8
°C
°C
%/°C
%RH
GPK
GPK
Grms
cfm
m3/min
lfm
m/s
lb
kg
www.power-one.com
FXP7000 AC-DC Series Data Sheet
FXP7000 OVERALL SIZE: 16.96" x 8.00" x 5.00" (430.8mm x 203.2mm x 127.0mm)
16.09"
(408.7mm)
14.259"
(362.18mm) 11.704"
(297.28mm)
7.509"
(190.73mm)
MAINTAIN 25 SQ IN MIN
FREE AREA (FRONT AND
REAR) FOR AIR COOLING
A
A
A
4.954"
(125.83mm)
0.87"
(22.1mm)
A
LOCK HANDLE
LED HANDLE
<--AIRFLOW
5.750"
(146.05mm)
8.00"
(203.2mm)
SIDE VIEW
A
A
A
A
0.341"
(8.66mm)
1.100"
(27.94mm)
0.649"
(16.48mm)
0.590"
(14.99mm)
LOCK HOOK
0.480"
(12.19mm)
NOTE:
TOTAL BOTTOM STACKUP OF
RACK MUST BE NO GREATER
THAN 0.204".
16.96"
(430.8mm)
A
A
A
0.204"
(5.18mm)
A
4.000"
(101.6mm)
BOTTOM VIEW
A
FOR OPTIONAL HARD MOUNTING, USE
M4 X 0.7 SCREWS, 8PL (MARKED A) ON
SIDE OR BOTTOM WITH MAXIMUM
PENETRATION 3.8mm.
A
A
A
1.759"
(44.68mm)
RECOMMENDED MOUNTING TORQUE
10.5 INCH LBS. (0.64N/M)
15.462"
(392.73mm)
FRONT VIEW
5.000"
(127mm)
REAR VIEW
LOCK HANDLE
RELEASE
INPUT VOLTAGE RANGE
SELECT MODULE
ROTATE 180 DEGREES FOR 240 VAC
INPUT VOLTAGE
DISPLAY CUTOUT
2.437"
(61.90mm)
CENTER
-TOCENTER
0.090"
(2.29mm)
2PL
0.521"
(13.24mm)
480VAC
4.552"
(115.62mm)
3.901"
(99.09mm)
0.222"
(5.64mm)
MATING CONNECTOR INFORMATION
Tyco PN
Elcon PN
Description
1648601-1
296-22-01100
CONN HSING FEM 52P TOP DRAWER
1648420-1
712-12-01107
CONTACT SOCKET #0 DOUBLE CROWN
1648318-1
702-32-01107
CONN SOCKET #12 BLIND MATE
1648325-1
702-92-01109
CONN SOCKET #20 BLIND MATE
MAY 31, 2005 revised to JAN 09, 2007
Page 4 of 8
C
L
0.226"
(5.74mm)
C
L
www.power-one.com
FXP7000 AC-DC Series Data Sheet
FRH7000 POWER SHELF, FRONT VIEW
®
NOTE:
FXP7000 POWER SUPPLIES ARE SHOWN FOR ILLUSTRATION PURPOSES
ONLY AND ARE NOT INCLUDED AS PART OF POWER SHELF ASSEMBLY.
19.000"
(482.6mm)
18.312"
(465.12mm)
0.129" 4PL
(3.28mm)
5.215"
(132.46mm)
480VAC
480VAC
2.250" 2PL
(57.15mm)
1.484" 2PL
(37.69mm)
FXP7000 2PL
Note: The FRH7000 Power Shelf is designed for alternative vertical mounting with the right side down.
FRH7000 POWER SHELF, REAR VIEW
5/16-18 STUD 2 PL
ACCOMODATES RING
LUG 1.08 MAX WIDTH
2.74"
4.38"
(69.6mm) (111.25mm)
5.215"
(132.46mm)
UNIT
LABEL
-
+
3.56"
(90.4mm)
2 PL
AMP PN 213581-1
WITH SILVER-PLATED
CONTACTS
J2 AC INPUTS J3
2
1
1.86"
(47.24mm) 2 PL
3
3 PHASE 3 WIRE + PE
0.61"
(15.5mm)
0.66"
(16.76mm) 2 PL
J1
ATTACH EARTH GNDS BEFORE AC CONNECTORS
0.000
0.000
9.42"
(239.27mm)
NOTES:
1. FOR CLARITY, FINGER GUARD FOR DC OUTPUT
TERMINALS IS NOT SHOWN IN THIS ILLUSTRATION.
MAY 31, 2005 revised to JAN 09, 2007
PIN 1
19.000"
(482.6mm)
15.14"
(384.56mm)
50-PIN SIGNAL HEADER
WITH KEYING AND LATCHES
15.44"
(AMP PN: 1-499141-0)
(384.56mm)
17.14"
(435.34mm)
10/32 GROUND
STUD 2PL
16.84"
(427.74mm)
Page 5 of 8
www.power-one.com
FXP7000 AC-DC Series Data Sheet
FRH7000 POWER SHELF, RIGHT-SIDE VIEW
24.000"
(609.6mm)
1/4-20 INSERTS 2 PL
EACH SIDE FOR
REAR SUPPORT
21.91"
(556.5mm)
4.000"
(101.6mm)
0.715"
(18.16mm)
CUSTOMER-SUPPLIED
CABLES OR BUS BARS
RACK MOUNTING FLANGE
FILLER PANEL KIT, PN: 088-101378
(Used with FRH7000 Power Shelf)
This kit is used to cover an unused right-side slot of the FRH7000 Power Shelf (as viewed from the front of the FRH7000). The kit can be installed before, or after
installation of the power shelf into the rack.
BRACKET, 2 PLACES
FILLER PANEL
(FILLER PANEL KIT AS SEEN FROM INSIDE OF POWER SHELF)
MAY 31, 2005 revised to JAN 09, 2007
Page 6 of 8
www.power-one.com
FXP7000 AC-DC Series Data Sheet
19.000"
(482.6mm)
18.656" 2PL
(473.86mm)
®
0.344" 2PL
(8.74mm)
FRV7000 POWER SHELF, FRONT VIEW
NOTE:
FXP7000 POWER SUPPLIES ARE SHOWN FOR ILLUSTRATION PURPOSES
ONLY AND ARE NOT INCLUDED AS PART OF POWER SHELF ASSEMBLY.
8.70"
(221.0mm)
7.184" 2PL
(182.47mm)
INPUT VOLTAGE
DISPLAY CUTOUT
R 0.129" 4PL
(3.28mm)
INPUT VOLTAGE RANGE
SELECT MODULE
1.434" 2PL
(36.42mm)
480VAC
480VAC
480VAC
0.000
0.000
FRV7000 POWER SHELF, REAR VIEW
5/16-18 STUD 2PL
ACCOMODATES CABLE
LUG 1.08" WIDTH MAX.
- DC OUT +
AMP PN: 213581-1
WITH SILVER-PLATED
PIN CONTACTS
3.55"
(90.17mm)
1
UNIT
LABEL
2
3
J4
J2 AC INPUTS J3
3 PHASE
1.01"
(25.65mm)
J1
3W + PE
ATTACH EARTH GNDS BEFORE AC CONNECTORS
1.07" 3PL
(27.2mm)
10/32 PE STUD 3PL
0.000
MAY 31, 2005 revised to JAN 09, 2007
Page 7 of 8
17.07"
(433.58mm)
16.77"
(425.96mm)
13.67"
(347.22mm)
15.37"
(390.40mm)
15.07"
(382.78mm)
50-PIN SIGNAL HEADER
WITH KEYING AND LATCHES
(AMP PN: 1-499141-0)
13.37"
(339.60mm)
NOTES:
1. FOR CLARITY, FINGER GUARD FOR DC OUTPUT
TERMINALS IS NOT SHOWN IN THIS ILLUSTRATION.
9.42"
(239.27mm)
4.95"
(125.73mm)
3.31"
(84.07mm)
PIN 1
0.000
0.40"
(10.16mm)
2.71" 3PL
(68.8mm)
www.power-one.com
FXP7000 AC-DC Series Data Sheet
0.000
22.50" 2PL
(571.5mm)
24.00"
(609.6mm)
25.56"
(649.2mm)
FRV7000 POWER SHELF, LEFT-SIDE VIEW
1/4-20 THREADED INSERTS 2PL
EACH SIDE FOR REAR SUPPORT
OF UNIT. DO NOT EXCEED 0.500"
PENETRATION OF SCREW INTO UNIT.
7.20"
(182.9mm)
COOLING AIR
INTAKE
COOLING AIR
EXHAUST
FINGER GUARD
FOR DC OUTPUT
TERMINALS
1.20"
(30.5mm)
0.214"
0.000 (5.44mm)
0.40"
(10.2mm)
POWER SUPPLY LOCK
HOOK; CLEARANCE
REQUIRED 6 PLACES
CUSTOMER-SUPPLIED
DC CABLES
FILLER PANEL KIT, PN: 088-101348
(Used with FRV7000 Power Shelf)
This kit is used to cover an unused left or center slot of the FRV7000 Power Shelf (as viewed from the front of the FRV7000). One kit is required per slot. Kits
can be installed before, or after installation of the power shelf into the rack.
UPPER BRACKET
FILLER PANEL
LOWER BRACKET
(FILLER PANEL KIT AS SEEN FROM INSIDE OF POWER SHELF)
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components
in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective
divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
MAY 31, 2005 revised to JAN 09, 2007
Page 8 of 8
www.power-one.com