POWER-ONE FXC7000-48-S

FXC7000 AC-DC Series Data Sheet
r Front-End
Distributed Powe
Features
• Three-phase AC input
• Suitable for 3U or 5U height mounting
• Single-wire current share or Droop current share
• Remote voltage adjust and current monitoring
• Overtemperature, overload, and overvoltage protection
• LED supply status indicators
• Current-share control for up to 30 units
• Front panel selectable-input-range
FXC7000
Front and Rear Views
Description
The FXC7000 Series of standalone or rack-mounted
power systems provides true AC front-end capability to
automatic test equipment, telecom, data communications, and other distributed power designs. The FXC
systems may be paralleled up to 210 kW of output power
and are intended for chassis-mounted installations with
bolted connections. These power supplies provide
excellent protection against input voltage transients.
The FXC has its fan located at the front of the supply, and
voltage adjust, indicator lights, output bussbars, and
connectors on the rear. Airflow is from the front through
the rear. Alarm, monitoring, and control signals are
floating from the main output and can be referenced to
the positive or negative output or sense line of the power
supply. The output is floating with respect to the chassis
and may be used as a positive or negative polarity
supply.
The FXC7000 Series meets international safety
requirements and is CE Marked to the Low Voltage
Directive. This series operates on three-phase European
voltages as well as (up to) 480VAC, delta or wye.
Chassis-Mountable Model
MODEL
FXC7000-48-S
OUTPUT
VOLTAGE
INPUT VOLTAGE RANGE
3-PHASE (VAC)
ADJUSTMENT
RANGE
MAXIMUM OUTPUT
CURRENT
LINE
REGULATION
LOAD
REGULATION (NOTE 1)
INITIAL SETTING
ACCURACY
48V
180 to 264 or 342 to 528
45.6V to 50.4V
145A
0.15%
0.2%
47.90V to 48.10V
(NOTE 2)
NOTES: 1) With Remote Sense connected.
2). User-selectable input voltage ranges
Input Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
Input Voltage - AC
3-phase delta low input range, nominal.
3-phase delta high input range, nominal.
Continuous deviation from the above nominals.
Per phase at full rated load.
FXC7000 at 180 VAC:
Internally limited.
Vin = 264VAC (one cycle). 25° C:
Vin = 528VAC (one cycle). 25° C:
AC input.
After last AC line peak at full power.
208 VAC:
400 VAC:
Switching frequency, fixed.
200
380
-10
Input Current
Inrush Surge Current
Input Frequency
Hold-up Time
Operating Frequency
Power Factor
AUG 18, 2006 revised to JAN 09, 2007
MAX
240
480
+10
30
30
15
60
50
17
13
UNITS
VAC
%
ARMS
APK
Hz
ms
100
0.90
Page 1 of 4
NOM
kHz
W/VA
www.power-one.com
FXC7000 AC-DC Series Data Sheet
Output Specifications
PARAMETER
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
Output Voltage
Adjustment Range
Output Power
Output Current
Efficiency
Regulation
An additional 1.0 Volt is provided to the output terminals to provide for
load lead losses.
Continuous duty rating.
Continuous duty rating.
Full rated load (208Vac).
Load, Maximum deviation with 0 to 100% load change:
With Remote Sense connected:
With Remote Sense not connected:
Utilizing Droop Current Share:
Line, Under all specified operating conditions.
Measured at mating connector w/ 0.01µF + 10µF Tant.
20 MHz BW:
100 MHz BW:
Output voltage overshoot/undershoot at turn-on.
Minimum loading required to maintain regulation.
Maximum recovery time, to within 1% of initial set
Time:
point due to a 25% load change, 1A/µS.
Deviation:
Time required for initial output voltage stabilization after power-up.
Time required for output voltage to rise from 10% to 90%.
45.6
48
50.4
V
7000
145
Watts
A
%
Ripple & Noise
Overshoot / Undershoot
Minimum Loads
Transient Response
Turn-On Delay
Turn-on Rise Time
88
91
0.2
0.75
2.0
0.2
1
2
0
%
% p-p
800
3.2
3
100
%
A
µs
%
s
ms
0
Interface Signals and Internal Protection
PARAMETER (NOTE 1,2)
DESCRIPTION/CONDITIONS
MIN
NOM
MAX
UNITS
AC Power Fail Warning
Auxiliary Power
Warning provided prior to Vout dropping 5% after loss of AC input.
Output voltage - diode isolated. Inclusive of line, load, and initial tolerances.
Output current.
Monitor output current over a compliance range of 0~10V.
Normal output:
Total error current:
Static sharing deviation as a percent of full-load rating
Active:
for loads >10%.
Passive:
Maximum signal resistance in high input voltage range selection.
Warning provided prior to protective reduction in current limit.
Voltage required to enable supply (0.5 mA sink). (NOTE 3)
Voltage required to enable supply (6 mA sink). (NOTE 3)
Straight line current limit (above approx. 5V Vout).
Signal level on overload.
Occurs on overload when Vout is below approx. 5V.
Iavg:
May operate in burst-mode.
Deviation from adjusted Vout that is considered as a fault.
Output voltage swing available through Margin pin (analog).
Time between fault warning and shutdown.
Latching shutdown.
Latch style overvoltage protection.
Resistance to logic ground upon insertion of supply.
Maximum load lead loss compensation (round trip).
4
11.6
12.0
12.4
500
ms
V
mA
Current Monitor
Current Share
Input Range Select Status
Loss of Phase Warning
Output Inhibit
Output Interlock
Output Overload Protection
Output Overload Warning
Output Short Circuit Protection
Output Voltage Fault Signal
Output Voltage Margin
Overtemperature/
Fan Failure Warning
Overvoltage Protection
Power Supply Present Signal
Remote Sense
0.10
0.5
0.5
5
10
0.10
500
1.0
1.0
156
149
2.2
25
90
mA/A
mA
%
⍀
ms
V
V
A
V
A
±3
±4.8
100
±4
±5.0
±5
±5.2
%
%
ms
55.2
57.6
1000
60.0
V
⍀
V
1.0
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V.
2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase
imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED’s indicating output loading.
3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable.
Contact factory for additional design details.
AUG 18, 2006 revised to JAN 09, 2007
Page 2 of 4
www.power-one.com
FXC7000 AC-DC Series Data Sheet
Safety, Regulatory, and EMI Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Agency Approvals
UL60950/CSA60950-00 (cULus), IEC60950 3rd Edition, EN60950 (TÜV),
CE marked for the Low Voltage Directive
FCC CFR title 47 Part 15 Sub-Part B - Conducted.
EN55022 / CISPR 22 Conducted.
Per EN61000-4-2, level 4.
Per EN61000-4-3, level 3.
Per EN61000-4-4, level 4.
Per EN61000-4-5
Line-to-Line:
Line-to-Ground:
Per SEMI F47-0200 FXC/FXP6000
Per UL60950 and
FXC7000 at 240 VAC, 60 Hz:
EN60950:
FXC7000 at 400 VAC, 50 Hz:
FXC7000 at 480 VAC, 60 Hz:
Electromagnetic Interference
ESD Susceptibility
Radiated Susceptibility
EFT/Burst
Input Transient Protection
Voltage Sag Immunity
Leakage Current
MIN
NOM
MAX
A
A
8
10
±4
4
3
UNITS
Class
kV
V/M
kV
kV
Pending
5
7
10
mA
Environmental Specifications
PARAMETER
CONDITIONS/DESCRIPTION
Altitude
Operating.
Non-Operating.
MIN
Operating Temperature
Storage Temperature
Temperature Coefficient
Relative Humidity
Shock
Vibration
Airflow
At 100% load:
At 50% load:
NOM
0
-40
0°C to 70°C (after 15-minute warm-up).
Non-Condensing.
Operating: half-sine 10 ms, 3 axis
Non-operating: half-sine 10 ms, 3 axis
Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02îDA, 32-2000 Hz
Non-operating: random 10-2000 Hz
Airflow provided through the supply from front to rear.
MAX
UNITS
10k
40k
40
70
85
.02
95
+20
+40
1
6.15
ASL Ft.
155
4.4
555
2.8
Weight
27
12
°C
°C
%/°C
%RH
GPK
GPK
Grms
cfm
m3/min
lfm
m/s
lb
kg
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components
in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective
divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the
date manufactured. Specifications are subject to change without notice.
AUG 18, 2006 revised to JAN 09, 2007
Page 3 of 4
www.power-one.com
FXC7000 AC-DC Series Data Sheet
FXC7000 OVERALL SIZE: 15.17" x 8.00" x 5.00" (385.3mm x 203.2mm x 127.0mm)
MAINTAIN 25 SQ IN MIN
FREE AREA (FRONT AND
REAR) FOR AIR COOLING
7.705"
(195.7mm)
3.510"
(89.2mm)
0.955"
(24.3mm)
1.10"
(27.9mm)
15.17"
(385.3mm)
10.260"
(260.6mm)
0.85"
(21.6mm)
A
A
A
A
6.850"
(174mm)
5.42"
(137.7mm)
4.24"
(107.6mm)
INSULATOR
BLOCK
<--AIRFLOW
SIDE VIEW
A
A
A
A
1.100" (27.9mm)
0.53"
(13.4mm)
2 PL
3.60"
4.480" (91.5mm)
(113.8mm)
0.480"
(12.2mm)
A
A
A
FOR MOUNTING, USE M4 X 0.7 SCREWS,
8PL (MARKED A) ON SIDE OR BOTTOM
WITH MAXIMUM PENETRATION 3.8mm.
2 PL 1.22"
(31.1mm)
0.70"2 PL
(17.9mm)
1.10" 2 PL
DIA 0.25"
(6.4mm)
RECOMMENDED MOUNTING TORQUE
10.5 INCH LBS. (0.64N/M)
BOTTOM VIEW
A 0.955"
A
(24.3mm)
2 PL
A
A
A
0.20"
(5.1mm)
3.510"
(89.2mm)
(28mm)
7.705"
(195.7mm)
13.455"
(341.8mm)
FRONT VIEW
REAR VIEW
9
18
26
5.00"
(127mm)
1
10
19
AC INPUT
PE
L1
L2
0.06 (1.7) 2 PL
DC OUTPUT
L3
POS
13mm CENTER-TO-CENTER
10mm
8.00"
(203.2mm)
NEG
VOLTAGE ADJUST POT
5 LED INDICATORS
M4 THREAD
26-PIN CONNECTOR
AMP PN: 749030-1
PIN 1
AC
SIGNAL
DC Vadj
T
MATING CONNECTOR:
CONNECTOR SHELL...
AMP PN 748365-1
CONTACTS...
AMP PN 748333-2
INPUT VOLTAGE RANGE
SELECT MODULE
ROTATE 180 DEGREES FOR 240 VAC
480VAC
INPUT VOLTAGE
DISPLAY CUTOUT
AUG 18, 2006 revised to JAN 09, 2007
Page 4 of 4
www.power-one.com