TOTAL-POWER T60

TOTAL POWER INT.
T60 AC-DC 60W POWER SUPPLY
.LOW COST, HIGH RELIABILITY
.COMPACT SIZE, LIGHT WEIGHT
.105ºC OUTPUT CAPACITOR
.100% FULL LOAD BURN-IN TEST
.INTERNATIONAL AC INPUT RANGE
.HIGH EFFICIENCY, LOW WORKING TEMPERATURE
.SOFT-START CIRCUIT, LIMITING AC SURGE CURRENT
.SHORT CIRCUIT, OVERLOAD, OVER VOLTAGE PROTECTED
T-60A
MODEL
SPECIFICATION
DC OUTPUT VOLTAGE
CH1
CH2
T-60B
CH3
CH1
T-60C
CH2
CH3
CH1
CH2
CH3
5V
12V
-5V
5V
12V
-12V
5V
15V
-15V
±2%
±6%
±6%
±2%
±6%
±6%
±2%
±6%
±6%
OUTPUT RATED CURRENT
5A
2.5A
0.5A
5A
2.5A
0.5A
5A
2A
0.5A
OUTPUT CURRENT RANGE
0.5-7A
0.2-3.5A
0-1A
0.5-7A
0.2-3.5A
0-1A
0.5-7A
0.2-3A
0-1A
RIPPLE & NOISE(Vp-p)
100m
100m
100m
100m
100m
100m
100m
100m
100m
LINE REGULATION
±0.5%
±1%
±0.5%
±0.5%
±1%
±0.5%
±0.5%
±1%
±0.5%
LOAD REGULATION
±1%
±4%
±1%
±1%
±4%
±1%
±1%
±4%
±1%
OUTPUT V. TOLERANCE
RATED OUTPUT POWER
57.5W
EFFICIENCY
DC VOLTAGE ADJ.
61W
62.5W
72%
72%
72%
CH1:+10,-5%
CH1:+10,-5%
CH1:+10,-5%
INPUT VOLTAGE RANGE
85~264VAC 47~63Hz ; 120~370VDC
AC CURRENT
2A/115V 1A/230V
INRUSH CURRENT
COLD START 30A/115V 60A/230V
LEAKAGE CURRENT
<1mA/240VAC
OVERLOAD PROTECTION
105%~150%/115VAC TYPE:PULSING HICCUP SHUTDOWN RESET:AUTO RECOVERY
OVER VOLTAGE PROTECTION
CH1:5.75~6.75V
TEMP. COEFFICIENT
±0.03% / ºC (0~50ºC) ON +5V OUTPUT
SETUP,RISE,HOLD UP TIME
800ms, 50ms, 10ms / 115VAC 300ms, 50ms, 80ms / 230VAC
VIBRATION
10~500Hz, 2G 3AXES 10min. / 1cycle ( 1 HOUR / EACH AXES )
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC 1min.
ISOLATION RESISTANCE
I/P-O/P,I/P-FG,O/P-FG:500VDC / 100M Ohms
WORKING TEMP., HUMIDITY
-10ºC~+60ºC(REFER TO OUTPUT DERATING CURVE), 20%~90% RH
STORAGE TEMP., HUMIDITY
-20ºC~+85ºC, 10%~95% RH
DIMENSION
159*97*38mm CASE:901
WEIGHT
0.56Kgs
SAFETY STANDARDS
UL1012, TUV EN60950, IEC950, UL1950 APPROVED
EMC STANDARDS
CISPR22(EN55022) CLASS B, IEC801-2,3,4, IEC555-2 VERIFICATION
NOTE :
1.ALL PARAMETERS ARE SPECIFIED AT 230VAC INPUT, RATED LOAD, 25ºC 70% RH. AMBIENT.
2.TOLERANCE GINCLUDE SET UP TOLERANCE, LINE REGULATION, LOAD REGULATION.
3.RIPPLE & NOISE ARE MEASURED AT 20MHz BY USING A 12" TWISTED PAIR TERMINATED WITH A 0.1uF & 47uF CAPACITOR.
4.LINE REGULATION IS MEASURED FROM LOW LINE TO HIGH LINE AT RATED LOAD.
5.LOAD REGULATION IS MEASURED FROM 20% TO 100% RATED LOAD, AND OTHER OUTPUT AT 60% RATED LOAD
6.EACH OUTPUT PROVIDE UP TO MAXIMUM CURRENT, BUT TOTAL LOAD CAN NOT EXCEED MAX. OUTPUT POWER.
7.C23,6 MUST BE REMOVED.