ETC AD-155C

MEAN WELL
AD-155
SERIES
SWITCHING POWER SUPPLY
ISO-9001 CERTIFIED
MANUFACTURER
.LOW COST, HIGH RELIABILITY
.COMPACT SIZE, LIGHT WEIGHT
.105ºC OUTPUT CAPACITOR
.100% FULL LOAD BURN-IN TEST
.INTERNATIONAL AC INPUT RANGE
.BUILT IN EMI FILTER, LOW RIPPLE
NOISE
.HIGH EFFICIENCY, LOW WORKING TEMPERATURE
.SOFT-START CIRCUIT, LIMITING AC SURGE CURRENT
.SHORT CIRCUIT, OVERLOAD, OVER VOLTAGE PROTECTED
AD-155A
MODEL
AD-155B
AD-155C
SPECIFICATION
CH1
CH2
CH1
CH2
CH1
CH2
DC OUTPUT VOLTAGE
13.8V
13.3V
27.6V
27.1V
54V
53.5V
OUTPUT V. TOLERANCE
±2%
----------
±1%
----------
±1%
----------
OUTPUT RATED CURRENT
10.5A
0.5A
5A
0.5A
2.7A
0.2A
OUTPUT CURRENT RANGE
0-11.5A
0-0.5A
0-5.5A
0-0.5A
0-2.7A
0-0.5A
150mVp-p
----------
150mVp-p
----------
240mVp-p
----------
LINE REGULATION
±0.5%
----------
±0.5%
----------
±0.5%
----------
LOAD REGULATION
±0.5%
----------
±0.5%
----------
±0.5%
----------
RIPPLE & NOISE
DC OUTPUT POWER
151.55W
151.55W
156.5W
80%
84%
84%
CH1:12-14.5V
CH1:24-29V
CH1:48-58V
EFFICIENCY
DC VOLTAGE ADJ.
INPUT VOLTAGE RANGE
88~264VAC 47~63Hz; 124~370VDC
AC CURRENT
2.5A/115V 1.5A/230V
INRUSH CURRENT
COLD START 20A/115V 40A/230V
LEAKAGE CURRENT
<1mA/240VAC
OVERLOAD PROTECTION
CH1:105%~135% CH2:0.51~0.9A TYPE:CONSTANT CURRENT LIMITING
RESET:AUTO RECOVERY
OVER VOLTAGE PROTECTION
CH1:115%~135% TYPE:SHUTDOWN
BATTERY LOW PROTECTION
10V±0.8V
19.5V( +1.5V, -1V )
39V±2V
TEMP. COEFFICIENT
±0.03% / ºC (0~50ºC)
SETUP, RISE, HOLD UP TIME
2s, 90ms, 16ms/115VAC 1s, 90ms, 20ms / 230VAC
POWER FACTOR
PF>0.92
VIBRATION
10~500Hz, 2G 10min./1cycle, PERIOD FOR 60min. EACH AXES
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:500VDC / 100M Ohms
WORKING TEMP., HUMIDITY
-10ºC~+60ºC(REFER TO OUTPUT DERATING CURVE), 20%~90% RH
STORAGE TEMP., HUMIDITY
-20ºC~+85ºC, 10%~95% RH
DIMENSION
199*110*50mm CASE:906
WEIGHT
1Kg
SAFETY STANDARDS
UL1950, TUV EN60950 APPROVED
EMC STANDARDS
CISPR22(EN55022)CLASS B,EN61000-4-2,3,4,5,6,8,11;ENV50204,EN61000-3-2,-3
NOTE :
1.ALL PARAMETERS ARE SPECIFIED AT 230VAC INPUT, RATED LOAD, 25ºC 70% RH. AMBIENT.
2.TOLERANCE:INCLUDE SET UP TOLERANCE, LINE REGULATION, LOAD REGULATION.
3.RIPPLE & NOISE ARE MEASURED AT 20MHz BY USING A 12" TWISTED PAIR TERMINATED WITH A 0.1uF & 47uF CAPACITOR.
4.LINE REGULATION IS MEASURED FROM LOW LINE TO HIGH LINE AT RATED LOAD.
5.LOAD REGULATION IS MEASURED FROM 20% TO 100% RATED LOAD, AND OTHER OUTPUT AT 60% RATED LOAD.
6.EACH OUTPUT PROVIDE UP TO MAXIMUM CURRENT, BUT TOTAL LOAD CAN NOT EXCEED MAX. OUTPUT POWER.
2001-08-20