ETC TDEA

DIN Timers TD
22.5mm DIN rail mounting Electronic Timers
R
❚ Multi-function, On-delay, Off-delay and Star/Delta
versions
TE
YEA
❚ Multi-time range
E
❚ AC/DC coil operation
GUARAN
❚ Voltage range selectable
❚ Marking plate cover
Options and ordering codes
TD
DIN rail mount
timers
MA
Multi Voltage Options
TD
Multi-function
4 function
Multi-function 2 C/O
On-delay
Off-delay
Asymmetrical recycling
True off-delay 3 minutes
True off-delay 10 minutes
Star/Delta
On delay single function
MA
MC
MB
EA
RA
IA
AA
AB
SD
SF
All timers are Multi-voltage
I/P 24VAC/DC and
100-230VAC selectable
on unit. Except EA+RA
models
EA + RA models only
EA + RA models only
SF model only
SF model only
SF model only
Multi Voltage Options
110VAC + 24VAC/DC
230VAC + 24VAC/DC
24VAC/DC
110VAC
230VAC
Specification
Operation modes
Time range
Accuracy
Supply voltage
Nominal power
consumption
Input signal
Control contact must be
90% of A1-A2
Contact configuration
Control output
Life expectancy
Allowable ambient
temperature
IP rating
Terminals
TD/03/03
Electrical
Mechanical
TDMA
A,B,C,D
E,F,G,H
0.05sec- 10 days
TDMC
A,B,F,G
0.05sec10 days
24V 1.5VA/
1W-110V
2VA 230V
8VA
Power on
control
contact
1 C/O
24V 1.5VA/
1W-110V
2VA 230V
8VA
Power on
control
contact
1 C/O
8A@250VAC
400,000
30 x 106
8A@250VAC
400,000
30 x 106
TDMB
A,B,C,D
E,F,G,H
0.05sec- 10 days
TDEA
A
TDRA
B
TDIA
Rp,Ri
TDAA
T
0.05sec- 10 days
TDAB
T
TDSD
S
0.05sec- - 0.05sec- - 0.1sec- - 0.1sec- - 0.5sec-3minY
10 days
10 days
3 min
10 min
40-100ms Y▲
▲
±0.5% FS
24VDC ±10%, 24VAC-15% +10%, 110-230VAC-15% +10%
24V 1.5VA/
24V 1.5VA/
24V 1.5VA/
24V 1.5VA/
24V 1.5VA/ 24V 1.5VA/
24V 1.5VA/
1W-110V
1W-110V
1W-110V
1W-110V
1W-110V
1W-110V
1W-110V
2VA 230V
2VA 230V
2VA 230V
2VA 230V
4VA 230V
4VA 230V
2VA 230V
11VA
8VA
11VA
8VA
15VA
15VA
11VA
Power on Power on
Power on Power on
Power on Power on Power on
control
control
contact
contact
2 C/O
1 C/O
1 C/O
1 C/O
1 C/O
1 C/O
1 C/O with
programmable
rest position
8A@250VAC 5A@250VAC 5A@250VAC 5A@250VAC 5A@250VAC 5A@250VAC 8A@250VAC
400,000
100,000
100,000
400,000
100,000
100,000
400,000
30 x 106
10 x 106
10 x 106
30 x 106
30 x 106
30 x 106
30 x 106
TDSF
A
0.1sec- 10 min
24V 1.5VA/
1W-110V
2VA 230V
11VA
Power on
1 C/O
5A@250VAC
100,000
10 x 106
-25 ˚C upto +55˚C
Enclosures
Terminals
IP40
IP20
Box clamp screw terminal upto 4mm2
www.imopc.com
DIN Timers TD continued
Mode functions
A On Delay
U/t
On application of supply voltage the time period starts to run. On completion of time the relay energises. Power
off reset.
A
R
B Off delay
U/t
B
Supply to the unit must be continuous. On closure of the control contact (S) the relay energises immediately.
On re-opening of S the time period starts to run and (R) de-energises If the control contact ( S ) is reclosed
before “the actual time period is completed, this period will be deleted” and a new one starts on re-opening of (
S ).
S
R
C Single shot leading edge pulse started
U/t
C
Supply to the unit must be continuous. On closure of the control contact (S) the relay energises immediately
and the time starts to run. On completion of the time the relay will de-energise. Activation of (S) during the time
out period has no effect.
S
R
D Single shot trailing edge
U/t
Supply to the unit must be continuous. The first closure of (S) has no effect. On opening of ( S ) the time
period starts to run and (R) energises immediately. On completion of time the relay de-energises. Activation of
the control contact (S) during the time out period has no effect.
DS
R
E On delay with control contact
U/t
Supply to the unit must be continuous. On closure of (S) the time period starts to run. On completion of time
the relay energises and stays energised as long as (S) is closed. Opening the control contact before the time
out is complete will reset the time period.
ES
R
F Single shot leading edge
U/t
On application of supply voltage the time starts and (R) energises immediately. Following time out the relay will
de-energise. For a new start of function the supply voltage must be interrupted.
F
R
G Flasher pause first
U/t
On application of supply voltage the time period starts to “run. The relay switches on and off for the periods,
beginning” with a pause. The time period for pause and pulse is equal.
G
R
H Pulse detection
U/t
HS
memory
On application of supply voltage the relay energises. The first pulse of (S) starts the time period. Receiving
pulses during the time period extends it and (R) stays energised. Receiving no pulses during the time period
completes it and (R) de-energises. (R) stays latched until supply voltage has been interrupted.
R
Ri Cyclic timer pulse started
U/t
On application of supply voltage the time period starts to run. “The relay switches on and off for the periods,
beginning with a” pulse. The time period for t1 and t2 can be different. The function continues as long as
voltage is applied.
Ri
R
Rp Cyclic timer pause started
U/t
On application of supply voltage the time period starts to run. “The relay switches on and off for the periods,
beginning with a” pause. The time period for t1 and t2 can be different. The function continues as long as
voltage is applied.
Rp
R
S Star Delta
U/t
SY
▲
U
T
TD/03/03
R
On application of supply voltage the contact 17 - 18 of the star relay is closed and the star time t1 begins to
run. On completion of the t1 the star relay de-energises and the dwell time t2 starts. On completion of t2 the
contact 17 - 28 of the delta relay is closed and remains in operation as long as the supply voltage is applied.
17 - 18
t1
t2
17 - 28
T True Off Delay
When supply voltage U is engaged the relay energises (contacts 15-18). When the supply voltage is removed
the set time t begins to run. On completion of time t the output falls back to the off position (contacts 15-16). If
the supply voltage U is re-engaged to “the unit before t has elapsed, the time already elapsed is cancelled” and
starts again next time the supply voltage is interrupted.
www.imopc.com
DIN Timers TD continued
Function switches
TDMB
TDMA
Positions of function
switch with one
contact as
instantaneous c.t.
H pulse detection
G flashing pause first
F single shot
E ON-delay controlled by trigger input
D single shot trailing edge
C single shot pulse operated
B Off-delay
A On-delay
TDMC
Both contacts delayed
H
G
A
B
H
G
F
G
F
C
F
E
D
D
E
C
C
F
B
A
G
H
B
B
A
A
Start function B, C, D, E and H by control contact A1-B1
if instantaneous option is selected R1 becomes timed and R2 becomes instantaneous
Connection diagrams
TDMA; TDRA
U+
~
–
TDMB
U+
~
–
S
A1 15 B1
TDEA, TDAA, TDAB,
TDSF
U+
~
–
S
25
A1 15
TDSD
TDIA
U+
~
–
U+
~
–
A1 15 B1
A1 17
A1 15 B1
A1
15
A1
15
R
A2 16
R1
25
A1
A21 61 82 62 8
18
15
A1
A2 16
A1
17
15
R
R
R2
R
A2
18
18
28
A2 16
18
16 18 A2
16 18 A2
Control Function
16 18 A2
26 28
Function Rp: without link
18 28 A2
16 18 A2
Function Ri: link A1-B1
Dimensions
TDMB
85mm
64mm
TDMA, TDEA, TDRA, TDIA, TDAA, TDAA, TDAB, TDSD, TDSF
65mm
5mm
TD/03/03
70mm
85mm
22.5mm
5mm
89mm
22.5mm
www.imopc.com