ETC H211156115

Timers
Multi-function
Type H 211
• 3 selectable functions: - Delay on operate
- Interval timer
- Interval timer with contact
• Time ranges: 0.1 s to 10 h
• Automatic and manual start functions
• Knob-adjustable time within range
• Oscillator-controlled time circuit
• Repeatability deviation: ≤ 1%
• Output: 5 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• H2 -housing
• LED-indication for relay and power supply on
• AC and DC power supply
Product Description
Ordering Key
Multi-function, multi-voltage
time relay with 6 selectable
time ranges up to 10 h and 3
different supply voltages. For
mounting on DIN-rail. Often
used where several modes of
operation are needed for different applications.
Housing
Type/function
Output
Power supply
H 211 156 230
Type Selection
Plug
Output
Time range
Supply: 24 VAC/DC & 230 VAC Supply: 115 VAC
For mounting
on DIN-rail
SPDT
0.1 s - 10 h
H 211 156 230
H 211 156 115
Time Specifications
Output Specifications
Time ranges
Output
Basic electrical insulation
Time range accuracy
Repeatability deviation
Time variation
Within rated power supply
and ambient temperature
Reset
Time and/or relay
Pulse duration
Power supply interruption
0.1 s - 1 s
1s
- 10 s
0.1 m - 1 m
1 m - 10 m
0.1 h - 1 h
1h
- 10 h
-5% +10% on max.
min. actual time ≤ min. set time
≤ 1%
≤ 0.05%/V
≤ 0.2%/°C
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
Mechanical life
Electrical life
AC 1
Operating frequency
Insulation voltages
Rated insulation voltage
SPDT relay
250 VAC (rms)
(contact/electronics)
µ (micro gap)
5 A/230 VAC (1200 VA)
5 A/24 VDC (120 W)
≥ 10 x 106 operations
≥ 105 operations (at max. load)
≤ 7200 operations/h
2.0 kVAC (rms) (cont./elec.)
Intercon. term. 1 & 2
term. 2 pos., 8 VDC, 2.5 mA
≥ 10 ms
Min. 200 ms
Specifications are subject to change without notice (27.10.99)
1
H 211
Supply Specifications
General Specifications
Power supply AC type
Rated operational voltage
through term. 21 & 22 230
115
or term. 21 & 3
Drop-out tolerance
Rated insulation voltage
Rated transient protection volt.
Power ON time
Power OFF delay
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Installation cat. III (IEC 60664)
230 VAC ± 15%, 45-65 Hz
115 VAC ± 15%, 45-65 Hz
24 VAC +15/-10%, 45-65 Hz
≥ 40 ms
None
4 kV (1.2/50 µs)
(line/neutral)
Installation cat. III (IEC 60664)
Power supply DC type
Rated operational voltage
through term. 21 & 3
230
Rated insulation voltage
Rated transient protection volt.
Consumption
AC supply
24 VDC +15/-10% - term. 3: +
None
800 V (1.2/50 µs)
30 mA @ 50 Hz/
40 mA @ 60 Hz
1W
DC supply
Mode of Operation
Function 1
Delay on operate
No connection between the
terminals.
Function 2
Interval timer
Connection between terminals 1 and 2.
The delay period begins when
power supply is applied.
The relay operates and the
time period starts when power
supply is applied to the time
relay.
At the end of the set delay,
the relay will operate and will
not release until power supply is interrupted.
A recovery period of 200 ms
should be allowed before
reapplying power supply.
If power supply is interrupted
for more than 200 ms before
the relay operates, the time
circuit is reset to zero and the
time relay is ready for a new
time period.
At the end of the set delay,
the relay releases and will not
operate again until power
supply is reapplied.
A recovery period of 200 ms
should be allowed before
reapplying power supply.
If power supply is interrupted
for more than 200 ms before
the time period has expired,
the relay releases and the time
is reset to zero.
Accessories
For further information refer
to "Accessories".
≤ 200 ms
≥ 200 ms
LED, green
LED, red
IP 20 B/front IP 40 D
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
100 g
Wiring Diagram
Function 3
Interval timer
with time reset
Power supply must be constantly applied. When interconnecting terminals 1 and 2
the relay will operate.
Power supply
24 VAC/DC
Reset
When terminals 1 and 2 are
disconnected, the time period starts, and when the period has expired, the relay
releases.
When interconnecting terminals 1 and 2 before the delay
period has expired, the time
is reset to zero and the time
period restarts when the interconnection between terminals 1 and 2 is interrupted.
Power supply - 230 VAC
Time Setting
For other AC/DC voltages
refer to "General Information".
Knob-adjustable on relative
scale (1-10).
Left knob on housing:
Selection of time range (seconds, minutes, hours).
Centre knob on housing:
Time range multiplicator x 0.1
and x 1.
Right knob on housing:
Selection of functions.
Operation Diagram
Power supply
Reset (intercon. 1 & 2)
Function 1. Relay on
Function 2. Relay on
Function 3. Relay on
2
Specifications are subject to change without notice (27.10.99)