ETC ATS22D47Q

Product data sheet
Characteristics
ATS22D47Q
soft starter-ATS22-control 220V-power
230V(11kW)/400...440V(22kW)
Range of product
Altistart 22
Product or component
type
Soft starter
Product destination
Asynchronous motors
Product specific
application
Severe and standard applications
Component name
ATS22
Network number of
phases
3 phases
Power supply voltage
230...440 V (- 15...10 %)
Motor power kW
11 kW at 230 V
22 kW at 400 V
22 kW at 440 V
Factory setting current
42 A
Power dissipation in W
48 W for standard applications
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 3.5 In)
Icl nominal current
47 A (connection in the motor supply line) for
standard applications
IP degree of protection
IP20
Complementary
Assembly style
With heat sink
Function available
Internal bypass
Power supply voltage limits
195...484 V
Power supply frequency
50...60 Hz (- 10...10 %)
Network frequency
45...66 Hz
Device connection
In the motor supply line
To the motor delta terminals
Control circuit voltage
220...230 V -15...10 % at 50/60 Hz
Control circuit consumption
20 W
Discrete output number
2
Discrete output type
(R1)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
(R2)Relay outputs 230 V running, alarm, trip, stopped, not stopped, starting,
ready, C/O
Minimum switching current
Relay outputs 100 mA at 12 V, DC
Maximum switching current
Relay outputs 5 A at 250 V, AC resistive load, cos phi = 1
Relay outputs 5 A at 30 V, DC resistive load, cos phi = 1
Relay outputs 2 A at 250 V, AC inductive load, cos phi = 0.4, L/R = 20 ms
Relay outputs 2 A at 30 V, DC inductive load, L/R = 7 ms
Discrete input number
3
Discrete input type
(LI1, LI2, LI3)logic 5 mA 4.3 kOhm
Discrete input voltage
24 V (<= 30 V)
Discrete input logic
(LI1, LI2, LI3)positive logic state 0 < 5 V and < 2 mA state 1 > 11 V and > 5 mA
Output current
0.4...1 Icl adjustable
PTC probe input
750 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
10/8/2011
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Transmission rate
4800, 9600 or 19200 bps
Max nodes number
31
Protection type
Phase failure on line
Thermal protection on motor
Thermal protection on starter
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Product weight
7 kg
Environment
Electromagnetic compatibility
Conducted and radiated emissions conforming to IEC 60947-4-2 level A
Damped oscillating waves conforming to IEC 61000-4-12 level 3
Electrostatic discharge conforming to IEC 61000-4-2 level 3
Immunity to electrical transients conforming to IEC 61000-4-4 level 4
Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3
level 3
Voltage/Current impulse conforming to IEC 61000-4-5 level 3
Standards
EN/IEC 60947-4-2
Product certifications
CCC
CSA
C-Tick
GOST
UL
Vibration resistance
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level
45 dB
Pollution degree
Level 2 conforming to IEC 60664-1
Relative humidity
<= 95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
-10...40 °C without derating
> 40...< 60 °C with current derating 2.2 % per °C
Ambient air temperature for storage
-25...70 °C
Operating altitude
<= 1000 m without derating
> 1000...< 2000 m with current derating of 2.2 % per additional 100 m
RoHS EUR status
Compliant
RoHS EUR conformity date
0938
2
Product data sheet
Dimensions Drawings
ATS22D47Q
Frame Size A
Dimensions
3
Product data sheet
Mounting and Clearance
ATS22D47Q
Precautions
Standards
The Altistart 22 soft starter is compliant with pollution Degree 2 as defined in NEMA ICS1-1 or IEC 60664-1.
For environment pollution degree 3, install the Altistart 22 soft starter inside a cabinet type 12 or IP54.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ATS22 soft starters are open devices and must be mounted in a suitable enclosure.
Failure to follow these instructions will result in death or serious injury.
Air Circulation
Leave sufficient free space to help the air required for cooling purposes to circulate from the bottom to the top of the unit.
Overheating
To avoid the soft starter to overheat, respect the following recommendations:
● Mount the Altistart 22 Soft Starter within ± 10° of vertical.
● Do not locate the Altistart 22 Soft Starter near heat radiating elements.
● Electrical current through the Altistart 22 Soft Starter will result in heat losses that must be dissipated into the ambient air immediately
surrounding the soft starter. To help prevent a thermal fault, provide sufficient enclosure cooling and/or ventilation to limit the ambient
temperature around the soft starter.
● If several soft starters are installed in a control panel, arrange them in a row. Do not stack soft starters. Heat generated from the
bottom soft starter can adversely affect the ambient temperature around the top soft starter.
Mounting
4
Connection Between the Fan and the Altistart 22 Soft Starter
1
2
Altistart 22 Soft Starter
Fan
Wall mounted or Floor-standing Enclosure with IP 23 Degree of protection
Introduction
To help proper air circulation in the soft starter, grilles and forced ventilation can be installed.
Ventilation Grilles
Forced Ventilation Unit
5
ATS22D47Q
Product data sheet
Connections and Schema
Power Terminal
Cage Style
1
Ground connection
Power connections, minimum and maximum wiring capabilities, tightening torque
IEC cable
UL cable
Power supply and output to motor
Size/gauge
min
max
16 mm
4 AWG
Tightening torque
min
3 N.m
max
3 N.m
26.25
lb.in
Strip length
10 mm
2.5 mm
26.25 lb.in
0.4 in.
Power connections, minimum required wiring section
IEC cable
UL cable
mm² (Cu 70°C/158°F) (1)
AWG (Cu 75°C/167°F) (1)
10
6
230 Vac control, logic Inputs (LI) 24 Vdc, 3-wire control
6
12 AWG
With Line Contactor, Freewheel or Controlled Stop
230 Vac control, logic Inputs (LI) 24 Vdc, 2-wire control,freewheel stop
Connection in the motor delta winding in series with each winding
Wiring
ATS22 soft starters connected to motors with the delta connections can be inserted in series in the motor windings.
The following wiring requieres particular attention. It is documented in the Altistart 22 Soft start - soft stop unit user manual. Please contact
Schneider Electric commercial organisation for further informations.
7
Example
A 400 V - 110 kW motor with a line current of 195 A (nominal current for the delta connection). The current in each winding is equal to
195/1.5 or 130 A. The rating is determined by selecting the soft starter with a permanent nominal current (ICL) just above this current.
8
Product data sheet
Performance Curves
ATS22D47Q
Motor Thermal Protection - Cold Curves
Curves
A
B
C
Class 10
Class 20
Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
32 s
Trip time for a Severe Application (Class 20)
3.5 ln
63 s
Trip time for a Severe Application (Class 30)
3.5 ln
95 s
9
Motor Thermal Protection - Warm Curves
Curves
A
B
C
Class 10
Class 20
Class 30
Trip time for a Standard Application (Class 10)
3.5 ln
16 s
Trip time for a Severe Application (Class 20)
3.5 ln
32 s
Trip time for a Severe Application (Class 30)
3.5 ln
48 s
10