LCD-E3 Description LCD Keypad Display The LCD-E3 provides the main panel display of the E3 Series® Expandable Emergency Evacuation System with indicating LEDs and operating switches. Up to six (6), LCD-E3 displays may be locally or remotely located from the panel via a local RS-485 bus of the ILI-MB-E3 subassembly. The LCD-E3 includes an LCD display for the system status and the following switches and LED indicators: Switches • Alarm acknowledge • System reset/lamp test • Trouble acknowledge • Function buttons: - menu/back - back space/edit - OK • Signal silence • 12 button keypad LED Indicators • AC Power On • Alarm • Supervisory • System Trouble (green) (red) (yellow) (yellow) • Power Fault (yellow) • Ground Fault (yellow) • System Silenced (yellow) Installation The LCD-E3 is adaptable for installation in any of the following E3 Series® System cabinets: • “A” size cabinet, inner door (E3ID2-A) • “A2” size cabinet, inner door (E3ID-A2) • “B” size cabinet, inner door (E3ID2-B) • “C” size cabinet, inner door (E3ID2-C) • “D” size cabinet, inner door (E3ID2-D) LCD-E3 Features • Listed under UL Standard 864, 9th Edition • Provides an 80-character display of system events together with indicating LEDs and control switches • The ILI-MB-E3 can support up to six (6), LCD-E3 displays, any or all of which may be remotely located via the RS-485 serial interface • Easy to read backlit LED display, low power consumption Ordering Information Model Description LCD-E3 LCD keypad display Specifications Operating Voltage: 24 VDC FWR (from PM-9 power supply) Operating Current: 0.024 amp. Alarm Current: 0.028 amp. Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93%, non-condensing at 90° F (32° C) An ISO 9000-2000 Company SIGNALING E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc. S1869 FM MEA APPROVED Approved City of Chicago Approved 3025415 231-06-E 7165-0694:268 7165-0694:269 Class 1 Class 2 High Rise City of Denver Approved GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0606 Rev. e1 page 1 of 1 ©2007 by Honeywell International Inc. All rights reserved.