Features
• Two-line 16-character LCD display.
Remote Annunciator
• Indicates trouble, alarm, supervisory
and system status conditions with
LEDs and LCD display.
• Each RAN-400 is individually
supervised by the FLEX-410 FACP.
• Up to four per FLEX-410 FACP.
• Operation and appearance comparable to the control panel’s on-board
annunciator.
• Can be wired up to 1500 ft. (457.20 m)
from FACP.
g2486c1.wmf
Description
Specifications
The RAN-400 is the remote annunciator for the Flex 410 Fire Alarm
Control Panel (FACP). The RAN-400 performs all system operations. It
also provides trouble and alarm information, and can be used for programming.
Operating voltage
24 VDC.
Operation
When the system is normal and receiving AC power, the power LED is
on and all other LEDs are off. Other LEDs turn on as the conditions
occur.
Users identify themselves to the control panel by entering a code on
the annunciator. When a user presses a button, the annunciator piezo
beeps and the LCD prompts the user to enter a code or other relevant
information.
Multiple users can work at different annunciators simultaneously without affecting each other.
Current draw
Standby: 30 mA.
Alarm: 50 mA.
Dimensions
Width: 7.188” (18.26 cm).
Height: 5.0” ( 12.7 cm).
Depth: 1.125” (2.86 cm).
Operating temperature
32° to 120°F (0° to 49°C).
Maximum wiring distance
1500 ft. (457.20 m).
Engineer’s Specifications
The contractor shall furnish and install where indicated on the plans,
the RAN-400 Remote Annunciator. Module shall be of a LCD type with
a 2 x 16 display. Module shall be capable of remote programming as
well as providing alarm, trouble information along with resetting of
alarms and silencing of trouble and alarm conditions. Module ID shall
be programmed with a four position DIP. The control shall be capable
of supporting up to four supervised RAN-400. Module shall be designed to mount on a dual-gang electrical box with 18 AWG (0.821
mm²) to 14 AWG (2.08 mm²) wire.
Ordering Information
RAN-400
Remote annunciator for FLEX-410 FACP.
RAN-400 CS-2486 09/01/06
Page 1 of 2
Listings
Listings and approvals below apply to
the basic RAN-400. In some cases,
certain modules may not be listed by
certain approval agencies, or listing
may be in process. Consult factory for
latest listing status.
• UL Listed: file S521.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
Page 2 of 2
Ran-400 CS-2486
09/01/06