SYSTEMSENSOR PDRP-1002

PDRP1002.CD
System Sensor
3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: 630-377-6495
The PDRP-1002/PDRP-1002E
Agent Release Control System
Manual
Document 51135
I56-1358-00
03/11/99
PN 51135:A
Revision:
ECN 99-017
A
Installation Precautions – Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the
fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables
while the unit is energized. Do not attempt to install, service, or operate
this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To
ensure proper system operation, this product must be tested in
accordance with NFPA 72-1993 Chapter 7 after any programming
operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations or software functions known
to be affected by a change must be 100% tested. In addition, to ensure
that other operations are not inadvertently affected, at least 10% of
initiating devices that are not directly affected by the change, up to a
maximum of 50 devices must also be tested and proper system
operation verified.
This system meets NFPA requirements for operation at 0-49O C/
32-120O F and at a relative humidity of 85% RH (non-condensing) at
30O C/86O F. However, the useful life of the system's standby batteries
and the electronic components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a nominal
room temperature of 15-27O C/60-80O F.
Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightning
transients and interferences, proper grounding will reduce
susceptibility. Overhead or outside aerial wiring is not recommended
due to an increased susceptibility to nearby lightning strikes. Consu
with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reamin
or punching of the enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs. Over tightenin
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
This system contains static-sensitive components Always ground
yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating and
programming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating device loops. Most
devices cannot tolerate more than a 10% I.R. drop from the specified
device voltage.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices
and a fire alarm control with remote notification capability can provide
early warning of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life resulting from a
fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another
level or floor of a building. A second floor detector, for example, may not
sense a first floor or basement fire. Furthermore, all types of smoke
detectors - both ionization and photoelectric types, have sensing
limitations. No type of smoke detector can sense every kind of fire
caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials,
overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as
the control panel and in rooms used by the system for the connection of
alarm transmission wiring, communications, signaling and /or power. If
detectors are not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
Audible warning devices such as bells may not alert people if thes
devices are located on the other side of closed or partly open doors o
are located on another floor of a building.
A fire alarm system will not operate without any electrical power. I
AC power fails, the system will operate from standby batteries only fo
a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity
over time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection
specialist.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed fo
service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to
central monitoring station may be out of service or temporarily
disabled.
The most common cause of fire alarm malfunctions, however, is
inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following
written procedures supplied with each device. System inspection an
testing should be scheduled monthly or as required by National and/o
local fire codes. Adequate written records of all inspections should b
kept.
FCC Warning
WARNING: This equipment generates, uses and can radiate radio
frequency energy and if not installed and used in accordance with the
instruction manual, may cause interference to radio communications, It
has been tested and found to comply with the limits for class A
computing device pursuant to Subpart B of 15 of FCC Rules, which is
designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which
case the user will be required to correct the interference at his own
expense.
2
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiatio
noise emissions from digital apparatus set out in the Radio
Interference Regulations of the Canadian Department of
Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques
depassant les limites applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le brouillage
radioelectrique edicte par le ministere des Communications du
Canada.
The PDRP-1002 PN 51135:A 03/11/99
The PDRP-1002 PN 51135:A 03/11/99
3
4
The PDRP-1002 PN 51135:A 03/11/99
NFPA Standards
This control panel complies with the following NFPA standards:
NFPA 12 CO2 Extinguishing Systems (High Pressure Only)
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 12B Halon 1211 Extinguishing Systems
NFPA 72 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected
Premises Unit (Requires NOTI•FIRE 911AC DACT or MS-5012 Slave Communicator)*
NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems
NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM)
NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. Requires
4XTM, NOTI•FIRE 911AC DACT*
NFPA 2001 Clean Agent Fire Extinguishing Systems
*Applications which require the NOTI•FIRE 911AC are not FM approved.
Additional Information
Before proceeding, the installer should be familiar with the following documents and
standards:
NFPA Standards:
NFPA 12 CO2 Fire Extinguishing Systems
NFPA 12A Halon 1301 Fire Extinguishing Systems
NFPA 12B Halon 1211 Fire Extinguishing Systems
NFPA 72 Installation, Maintenance and Use of Central Station Signaling Systems
NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Alarm Systems
UL 268 Smoke Detectors for Fire Alarm Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Alarm systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Alarm Systems
UL 864 Standard for Control Units for Fire Alarm Systems
UL 1481 Power Supplies for Fire Alarm Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for the Hearing Impaired
CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Alarm Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document, 15378
ADA Americans with Disabilities Act
The PDRP-1002 PN 51135:A 03/11/99
5
1 The PDRP-1002/PDRP-1002E
Input Circuits
1 The PDRP-1002/PDRP-1002E
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Microprocessor-controlled
Power-limited on all circuits except Municipal Box output
Alarm and trouble resound
Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
Two Class B (Style Y) Release Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays (4XZM)
Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm systems
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator (RZA-4X)
Requires LED Interface Module (4XLM)
Optional digital communicator (NOTI•FIRE 911AC)*
Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
Supervisory Input Option
Delay timer (adjustable)
Three abort function options
Designed for suppression standards NFPA 12, 12A and 12B
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release Circuits
RMS regulated output power, 2.25 amps
7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
Resettable and non-resettable regulated power outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5 in (368.3 mm) wide by 16 in ( 406.4 mm) high by 5 in (127 mm)
deep
Dead-front dress panel option (DP-4X)
Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
Abort and manual release circuits
Cross-zone option
*Applications which require the NOTI•FIRE 911AC are not FM approved.
Circuits
Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B)
Detector Zone 2, Class A (Style D)/Class B (Style B)
Abort, Class A (Style D)/Class B (Style B)
Manual Release, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y)
Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Releasing Circuit 2, Class B (Style Y)/Supervisory Input, Class B (Style B)
6
The PDRP-1002 PN 51135:A 03/11/99
1 The PDRP-1002/PDRP-1002E
Front Panel Control Switches
Front Panel Control Switches
+
-
24 VNR
REGULATED
NON-RESETTABLE
24 VVU
RMS-REGULATED
+24VU
24 VR
REGULATED
RESETTABLE
Switch 1
Switch 2
Switch 3
Switch 4
+24VR
+24VNR
+
-
+
-
Tone Silence
Alarm Silence
Alarm Activate
System Reset
Notification Appliance
Circuits
Class A (Style Z)
Class B (Style Y)
1
2
B+ A+ A- B- B+ A+ A- B-
Releasing
Circuits
Initiating Device
Circuits
Class A (Style D)
Class B (Style B)
Relays
Alarm Trouble
3
4
B+ B-
B+ B-
Contacts
1
Contacts
NO NC C NO NC C
2
Abort
Switch
Manual
Release
3
4
B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-
TB1
TB4
TB2
TB3
JP 1
NO DACT
DACT
SUPV 2
4XTM
or
GEN ALM2
J1
Transformer
4XLM
AC Circuit Breaker
or
4XZM
TB5
Ground
*Jumper “OPT 1” must
be cut if a module is
installed in this position
Neutral
Hot
J2
J9
+
J3
Optional Ammeter
Connection
OPT 1*
Batteries
4XTM
Optional
VoltmeterConnection
or
4XLM
or
*Jumper “OPT 2” must
be cut if a module is
installed in this position
O1 2 3 4 5 6
N
BATT
Battery Fail LED
EARTH
Ground Fault LED
OPT 2*
SW1
Cross Zone
Abort Option
Supervisory
Abort Option
Delay Timer Delay Timer
Micro Fail LED
Figure 1 PDRP-1002/PDRP-1002E Installation Diagram
The PDRP-1002 PN 51135:A 03/11/99
7
4XRP1002.cdr
4XZM
1 The PDRP-1002/PDRP-1002E
Transmitter Module (4XTM - NOTIFIER)
Optional Boards
The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of
the three option modules may be installed.
Transmitter Module (4XTM - NOTIFIER)
The Transmitter Module provides a supervised output for
local energy municipal box transmitter (for NFPA 72
Auxiliary Fire Alarm System) and alarm and trouble
reverse polarity circuits (for NFPA 72 Remote Station Fire
Alarm System). Also included is a DISABLE switch and
disable trouble LED.
4XTM.cdr
As a jumper option, the alarm reverse polarity circuit will
open on trouble if no alarm exists.
LED Interface Module (4XLM - NOTIFIER)
4XLM.cdr
The LED Interface Module supports the RZA-4X Remote
Annunciator module. Annunciator wiring is supervised for
open conditions by this module. The Annunciator Driver
Module mounts to the main board, occupying one of the
two option connectors.
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the
following:
As a jumper option, the first four relays described below can
be made silenceable.
DIP 1=OFF
Either Zone
DIP 1=ON
Cross Zone
Alarm Detected First Alarm
If Supervisory (DIP 2=ON)
Either Zone
Cross Zone
Alarm Detected First Alarm
8
Release 1
Release 1
Release
Release
Release 2
Release 2
Not Used
Not Used
4XZM.cdr
Alarm Detected Second Alarm Alarm Detected Second Alarm
The PDRP-1002 PN 51135:A 03/11/99
Transmitter Module (4XTM - NOTIFIER)
1 The PDRP-1002/PDRP-1002E
Transmitter Module (4XTM - NOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA
Trip current: 0.35 amps. (Subtracted from Notification Appliance power)
Coil Voltage: 3.65 VDC
Coil resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
For Remote Station service (NFPA 72 Remote Station Fire Alarm
System):
Maximum load for each circuit: 10mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
LED Interface Module (4XLM - NOTIFIER)
Maximum voltage/current, each output: 27.6V/8mA
Note: Outputs are power limited
Zone Relay Module (4XZM - NOTIFIER)
Dry Form-C contacts rated: 2.0 amps @ 30VDC (resistive), 0.5 amps @ 30 VAC
(resistive)
Remote Annunciator
Remote Annunciator (RZA-4X - NOTIFIER)
RZA4Xfr.cdr
The Remote Annunciator mounts on a standard singlegang box, and provides LED indication of the same
functions as the zone relay module. For example with
DIP 1=ON and DIP 2=OFF:
• One Zone in Alarm (red)
• Two Zones in Alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also
provided. All LED wiring is supervised for open
conditions. Any open condition will cause the System
Trouble LED to illuminate.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
Optional Meters
Voltage, Current Meters (4XMM - NOTIFIER)
The Meter Module provides a voltmeter to measure the
voltage across the batteries and an ammeter to measure
the charging current to the batteries. The meters are
provided as an assembly that mounts to the lower lefthand corner of the cabinet.
20
10
0
30
DC VOLTS
0
5
5
voltmter.cdr
DC AMPERES
The PDRP-1002 PN 51135:A 03/11/99
9
1 The PDRP-1002/PDRP-1002E
AC Power
Specifications
AC Power
For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps
For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
AC Circuit
Breaker
Battery (lead acid only)
Acctbrkr.cdr
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH. (Batteries larger
than 12 AH require NOTIFIER #BB-17 or other UL
listed external battery cabinet.)
Initiating Device Circuits
Power-limited circuitry
Operation: Class A (Style D)/Class B (Style B)
Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including end-of-line resistor)
Notification Appliance and Releasing Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC
(resistive). All relays must be connected to a power limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from 4-wire
smoke power).
Maximum ripple voltage: 1.0 V p/p
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility, refer to Device Compatibility Chart.
10
The PDRP-1002 PN 51135:A 03/11/99
1 The PDRP-1002/PDRP-1002E
RMS Regulated Power
Cabinet
Door
Backbox
Door
Backbox
= 5.375 in.
(136.53 mm)
Backbox = 4.750 in.
(120.65 mm)
= 14.625 in.
(371.48 mm)
= 14.5 in.
(368.3 mm)
= 16.125 in.
(409.58 mm)
= 16 in.
(406.4 mm)
1.5 in
(38.1 mm)
TR-4XR
RUBY RD
STEEL
16 GA.
14.594 in.
(370.69 mm)
RPCABDIM.cdr
16.094 in.
(408.79 mm)
Optional Trim Ring
TR-4XR
Figure 2 Cabinet Dimensions
The PDRP-1002 PN 51135:A 03/11/99
11
2 System Operation
RMS Regulated Power
2 System Operation
!
WARNING:When used for CO2 releasing applications, observe proper
precautions as stated in NFPA 12. Do not enter the protected space unless physical
lockout and other safety procedures are fully completed. Do not use software
disable functions in the panel as lockout.
System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been
acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate
steadily.
AC POWER
Green LED that illuminates steadily to
indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm
occurs.
SUPERVISORY
Yellow LED that flashes upon activation of
a supervisory device (such as tamper
switch) on Output 4 if selected (see
“Setting Mode of Operation” in Section 3
of this manual).
BATT EARTH
SYSTEM TROUBLE
Yellow LED that flashes for any trouble
condition, including those associated with option boards.
MICRO
FAIL
4Xoper2.cdr
RELEASE
Red LED that illuminates steadily when
release occurs.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification and
releasing circuits).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
POWER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BATT
Yellow LED that illuminates steadily on motherboard when battery is low or not
detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on motherboard during a ground fault condition
(not visible through door)
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer detects
microprocessor failure (not visible through door)
12
The PDRP-1002 PN 51135:A 03/11/99
2 System Operation
RMS Regulated Power
Control Switches
Tone Silence
4XPTL.cdr
Acknowledge alarms, troubles and
supervisories. The panel has alarm and
trouble resound with LED flash of new
conditions. The flashing trouble LED(s)
illuminate steadily on TONE SILENCE and
the piezo sounder silences. A second trouble
will resound the piezo. The piezo has three
sounds for alarm, trouble, and supervisory.
Trouble conditions are self-restoring. Alarms
latch and require RESET to clear.
Alarm Silence
Acknowledge for alarms and supervisories.
The ALARM SILENCE switch will silence
the local piezo, change any flashing alarm
LEDs to steady, and turn off the notification
circuits (not the releasing circuits). The
“ALARM SILENCED” LED will illuminate.
Alarm silence is a latching function and
requires a RESET to clear.
Alarm Activate
The ALARM ACTIVATE switch may be used
to activate Notification Appliance Circuits.
ALARM ACTIVATE also activates the
System Alarm relay. ALARM Activate is a
latching function. Pressing ALARM
SILENCE silences the notification circuits
and System Alarm Relay and lights the Alarm
Silenced LED. Pressing RESET returns the
system to normal.
System Reset
The RESET switch breaks power to all
initiating circuits, 4-wire smoke power and
option boards and will clear any activated
output circuits. If any alarms or troubles still
exist after reset, they will reactivate the panel.
Holding RESET down will perform a LAMP
TEST function and will activate the piezo sounder.
Zone Status LEDs
The alarm and/or trouble LED(s)
will flash until the event(s) has
been acknowledged (TONE or
ALARM SILENCE), at which
point the LED(s) will illuminate
steadily.
ALARM LED
TROUBLE LED
Zone 1
ALARM LED
TROUBLE LED
Zone 2
ABORT LED
ABORT TROUBLE LED
MANUAL RELEASE
MANUAL RELEASE TROUBLE LED
The PDRP-1002 PN 51135:A 03/11/99
Abort
Manual
Release
13
2 System Operation
RMS Regulated Power
Supervisory
Output circuit #4 is used as an input for monitoring supervisory devices such as valve
tamper switches (note that SW1 DIP switch #2 must be set “ON” -- see section “Setting
Mode of Operation”) By setting Switch short circuit on this input (activation of a N.O.
contact) will cause the supervisory LED to flash. The piezo sounder will generate a
unique sound. TONE SILENCE will silence the piezo and cause the LED to illuminate
steadily. Supervisory signals latch and require RESET to clear. An open circuit will be
reported as a circuit trouble.
Zone Disable
If a zone has been disabled, an alarm
that occurs on that zone will flash the
red zone LED, but not the piezo or any
output circuit. If both power sources
are removed from the system, all zones
will be re-enabled upon restoration of
power. Disable status will be lost.
The Zone Disable routine makes use of
the four panel switches as follows:
Press and hold in the TONE
SILENCE switch.
2.
With the TONE SILENCE switch
held in, press (in sequence) the
ALARM SILENCE switch, the
ALARM ACTIVATE switch, and
then the RESET switch.
3.
The Zone 1 Alarm LED will flash.
4.
To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to
show that the zone is disabled.
4XPTL.cdr
1.
Note: The RESET switch toggles disable status for the selected zone.
5.
To select the next zone, press the ALARM SILENCE switch.
6.
To select the previous zone, press the ALARM ACTIVATE switch.
7.
When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED
will flash.
Last Event Recall
Last Event Recall allows the user to display the previous panel status. The last event
recall uses the four panel switches as follows:
1.
Press and hold in the TONE SILENCE switch.
2.
With the TONE SILENCE switch held in, press (in sequence) the RESET switch,
the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3.
Last Event is displayed.
4.
Release the TONE SILENCE switch to return to normal operation.
Note: To clear the last event buffer, press RESET twice.
14
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
UL Power Limited Wiring Requirements
3 Installation Procedure
General
Carefully unpack the system and check for shipping damage. Mount the cabinet in a
clean dry, vibration-free area in which extreme temperatures are not encountered. The
location should be readily accessible with sufficient room for easy installation and
maintenance. Locate the top of the cabinet approximately five feet above the floor with
the hinge mounting on the left. Determine the number of conductors required for the
devices to be employed. Pull required conductors into the box through the knockout
provided. All wiring should be in accordance with the National and/or Local codes for
fire alarm systems.
UL Power Limited Wiring Requirements
Power limited and non-power limited circuit wiring must remain separated in the
cabinet. All power limited circuit wiring must remain at least 0.25 in (6.35 mm) away
from any non-power limited circuit wiring. Furthermore, all power limited circuit
wiring and non-power limited circuit wiring must enter and exit the cabinet through
different knockouts and/or conduits. A typical wiring diagram for the PDRP-1002/
PDRP-1002E is shown below.
Non-Power
Limited Circuits
Relays
Notification Appliance
Circuits
Initiating Circuits
Power Limited
Circuit
4XZM
AC Power
Power Limited
Circuits
4XTM
Power Limited
Circuits
Non-Power
Limited Circuit
RP1002PL.cdr
PC Board
Figure 3 Typical Wiring Diagram for UL Power Limited Requirements
The PDRP-1002 PN 51135:A 03/11/99
15
3 Installation Procedure
Zones
Initiating Device Circuits
Zones
Wire all alarm initiating devices sequentially for proper supervision. Initiating devices
include: heat, photoelectric, and ionization type detectors; and waterflow alarm
devices. Refer to the Compatibility Chart in Appendix B.
Note:
•
Observe polarity when connecting polarized devices.
•
All circuits are supervised and power limited.
•
Leave Dummy Load (provided) on all unused circuits.
Class B (Style B)
Initiating Device Circuit
4.7K, 1/2-Watt (part # 71252 UL listed)
Heat
Detector
Manual
Pull Station
+
_
+
_
_
+
+
_
+
_
Abort Switch
Manual Release
4.7K, 1/2-Watt
(part # 71252
UL listed)
4.7K, 1/2-Watt
(part # 71252
UL listed)
B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-
1
2
3
4
IN #1
5
6
7
IN #2
8
9
10
11
IN #3
12
13
14
15
IN #4
16
AIDEX.cdr
TB4
_
+
Two-wire
Smoke
Detector
Class A (Style D)
Initiating Device
Circuit
Figure 4 Example of an Alarm Initiating Device
16
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
Zones
4-Wire Smoke Detector Connections
Refer to the Device Compatibility Document for suitable 4-wire smoke detectors.
24 VDC (+)
24 +VDC+ (+)
Red
Common (-)
Common (-)
Black
+
-
+
-
-
IDC (+)
+
+
-
-
-
IDC (+)
IDC (-)
+
+
-
-
IDC (-)
UL listed 24 VDC
Four-wire Smoke Detectors
1
2
+
-
3
4
Listed
Power
Supervision
Relay
TB4
+24VR
A maximum of 200mA is available from the +24VDC
4-wire smoke detector power circuit on TB1 terminals 3
and 4. Any power that is drawn from the +24VDC Nonresettable Power on TB2 terminals 1 and 2 must be
subtracted from available 4-wire detector power. (See
“Specifications” and “Power” sections.)
B+
A+
A-
B-
1
2
3
4
IN #1
Class B Initiating Device Circuit
RP4WR.cdr
TB1
UL listed
4.7K, 1/2-Watt
ELR
Initiating Device Circuits 1,2,3, or 4
can be used. Class A (Style D) wiring
can also be employed.
Figure 5 Diagram of Connections for a 4-Wire Smoke Detector
Notes on Class A (Style D) and Class B (Style B) field wiring:
1)
The Power Supervision Relay coil leads must be connected to the last detector
base 24V screw terminals.
2)
Calculation of the maximum allowable resistance in the 24VDC detector power
wiring:
RMAX =
(20.6 - VOM)
_________________________________________________________________________________________
(N x IS) + (NA x IA) + (IR)
Where:
RMAX is the maximum resistance of the 24V wires.
VOM is the minimum operating voltage of the detector or end-of-line relay, whichever is
greater, in volts.
N is the total number of detectors on the 24V supply loop.
IS is the detector current standby.
NA is the number of detectors on the 24V power loop which must function at the same
time in alarm.
IA is the detector current in alarm.
IR is the end-of-line relay current.
The PDRP-1002 PN 51135:A 03/11/99
17
3 Installation Procedure
Notification Appliance Circuits
Output Circuits
Notification Appliance Circuits
This control panel can provide two Class A (Style Z)/Class B (Style Y) Notification
Appliance Circuits and two Class B (Style Y) Releasing Circuits (see section “Setting
Mode of Operation” for DIP switch configuration). Each circuit is capable of 1.5 amps
of current. Total current drawn from all four circuits cannot exceed 2.25 amps. Refer
to the Compatibility Chart. Circuits are supervised and power-limited.
Note: Wiring must be configured to maintain a minimum voltage of 20.4V on release circuits. Calculation of
maximum allowable resistance:
RMAX =
20.6V-20.4V
________________________________________________________________________
IS
Where: RMAX = maximum allowable resistance of wiring
IS = solenoid current
Class B (Style Y) Notification
Appliance Circuit
Class A
(Style Z)
Notification
Appliance Circuit
Polarized Bell
4.7K, 1/2-Watt
(part #71252 UL listed)
-
+
-
+
Releasing Circuits
UL listed & FM approved
Releasing Devices
Polarized Strobe
+-
+No Connection
No Connection
Polarized Horn
B+ A+ A- B- B+ A+ A- B- NC B+ B- NC B+ B-
3
4
5
OUT #1
6
7
8
9
10
11
OUT #2
B+ A+ A- B-
15
16
OUT #4
See note
below
4.7K, 1/4-Watt
4.7K, 1/4-Watt
Dummy Load all
unused Notification
Appliance Circuits
12 13 14
OUT #3
B+ B-
Dummy Load all
unused Releasing
Circuits
RPNAC.cdr
TB2
Note: Output #4 can be configured for releasing or supervisory circuit (see Section “Setting Mode of Opera
configured as a releasing circuit, the circuit will be non-power limited. If configured as a supervisory circuit,
will be power limited. All wiring must follow the power limited “General” Section.
Figure 6 Notification Appliance Circuits
18
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
Alarm Relay
Alarm Relay
One Form-C dry alarm contact is provided in the basic panel for controlling
supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC
(resistive), and is non-silenceable when an alarm occurs. See below for terminal
location.
Trouble Relay
One Form-C dry trouble contact is provided in the basic panel for controlling
supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC
(resistive), and will silence when trouble condition is cleared. See below for terminal
location.
Note: The alarm and trouble Form-C dry contact relays must be power limited relays. They must be wired
from one of the 24V power limited terminals as shown in the figure below or a comparable UL listed power
limited power supply.
Alarm
Trouble
NO NC C NO NC C
or
or
1
3
2
4
1
+24VU +24VR
2
1
2
3
4
+24VNR
5
6
RPALMTBL.CDR
TB3
TB2
TB1
Trouble
Alarm
Schematic representation of
Alarm/Trouble coils and contacts.
Figure 7 Alarm/Trouble Coils and Contacts
Power
CAUTION: Several different sources of power can be connected to this panel.
Disconnect all sources of power before servicing. The panel and associated equipment
may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while this unit is energized.
This output is not suitable
for powering devices
requiring filtered DC power.
The combined current draws from the Resettable
and Non-resettable outputs cannot exceed 200 mA.
RMS-Regulated Power
24 VDC power for inductivetype devices such as door
holders can be connected to TB1
terminals 1 (+) and 2(-).
4-Wire Smoke Detector Power
24 VDC filtered, resettable power
for 4-wire smoke detectors can be
obtained from TB1 Terminals 3(+)
and 4(-).
+24VU +24VR
+ - + -
Non-resettable Power
24 VDC filtered, nonresettable
power can be drawn from TB2
Terminals 1 (+) and 2(-).
+24VNR
+ -
TB 2
TB 1
1
2
3
4
1
2
RPPWRTRM.cdr
!
Figure 8 Diagram of Power Terminals
The PDRP-1002 PN 51135:A 03/11/99
19
3 Installation Procedure
AC Power
AC Power
Primary power required for the PDRP-1002 panel is 120 VAC, 50/60 Hz, 1.2 amps and
primary power for the PDRP-1002E is 220/240 VAC, 50 Hz, 0.6 amps. Overcurrent
protection for this circuit must comply with Article 760 of the National Electrical Code
(NEC) and/or local codes. Use #14 AWG (2.00 mm2)or larger wire with 600 volt rating.
Battery Power
Observe polarity when connecting battery. Connect battery cable to J9 on the main
board using the plug-in connector provided. See Appendix A for calculation of correct
battery rating.
!
CAUTION: Batteries contain sulfuric acid which can cause severe burns to the skin and
eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush
skin or eyes with water for 15 minutes and seek immediate medical attention.
Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM (NOTIFIER) is
required. To install the power meter module, remove the jumper labeled “AMP” and
connect cable assembly P2 to pin connector J2 and cable assembly P3 to pin connector
J3 on the main board. Secure the 4XMM to the backbox with the two screws provided.
On some models, it will be necessary to install the meter bracket with the nuts and bolts
provided.
P2
J2
J9
P3
J3
20
10
0
30
DC VOLTS
0
5
5
RPMBVM.cdr
DC AMPERES
Figure 9 Diagram of the 4XMM Voltmeter Connected to the Main Board
20
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
Voltmeter/Ammeter
Optional Modules
The fire control panel has two module connectors - J5 and J8. Three modules are
available for the panel and they can be used in any combination, including duplicate
modules. The corresponding option jumper must be cut before installation of an
optional module.
Transformer
J4
J5
Ground
Neutral
Hot
*Jumper “OPT 1”
must be cut if a
module is
installed in this
position
Optional Ammeter
Connection
Batteries
J7
J8
Battery Fail LED
Ground Fault LED
Cross Zone
Abort Option
Supervisory
Abort Option
Delay Timer Delay Timer
*Jumper “OPT 2”
must be cut if a
module is
installed in this
position
4XRP102a.cdr
Optional
VoltmeterConnection
Micro Fail LED
Note:
•
Optional 4XLM module for an RZA-4X Annunciator must be installed on J7 and J8 only.
•
4XTM and 4XZM modules can be installed in either location.
Figure 10 Optional Panel Modules
The PDRP-1002 PN 51135:A 03/11/99
21
3 Installation Procedure
Installing Option Modules
Installing Option Modules
Insert the two stand-offs (provided) into the holes located on the right-side edge of the
main board. Carefully align the pins on the main board with J1 and/or J2 on the option
board. Insert screw through the option board until it is secured on the stand-offs. Affix
the terminal identification labels provided with the option modules as shown below.
(Part # 42050)
Stand-offs)
Main
Board
4XOPTNBD.cdr
4XSTNOFF.cdr
Option Board
(4XZM shown)
Figure 11 Installing Option Modules.
22
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
Transmitter Module - 4XTM (NOTIFIER)
Transmitter Module - 4XTM (NOTIFIER)
Polarities shown in activated positions. The wiring of this module must follow the
requirements as specified in the “General” section, “UL Power Limited Wiring
Requirements.”
1
2
3
4
5
6
7
+ } Remote Alarm
+ Remote Trouble
-}
Power Limited Circuit
No Connection
+ Municipal Box*
-}
Non-Power Limited Circui
TBL Jumper
4XTBa.cdr
Disconnect LED
* Dummy load terminals
6 and 7 (4.7K, 1/4 W
resistor) if Municipal
Box is not connected.
Disconnect Switch
Push the disconnect switch down to prevent unwanted activation of the Municipal Box
and Remote Station Outputs during testing of the control panel. The Disconnect LED
will remain illuminated while the Municipal Box is disconnected. The System Trouble
LED will indicate disconnected and/or Open Circuit conditions on the Municipal box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble,
if no alarm exists.
Note: Remote Alarm, Remote Trouble, and Municipal Box wiring can leave the building.
The PDRP-1002 PN 51135:A 03/11/99
23
3 Installation Procedure
Zone Relay Module - 4XZM (NOTIFIER)
Zone Relay Module - 4XZM (NOTIFIER)
Non-power limited and power limited wiring must have a minimum distance of 0.25 in.
(6.35 mm) wire to wire. If this module is used to drive non-power limited and power
limited circuits, please follow the instructions below.
4XZMA.cdr
Relay #1 through #4 will activate with Output #1 through #4
and remain latched unless jumper “LATCH” is cut.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
Relay #1
Relay #2
Relay #3
Relay #4
Alarm
Trouble
Use Disable switch to disconnect the relays.
Cut jumper for non-latching (silenceable) relay operation.
1)
Skip a set of dry contacts to maintain the 0.25 in (6.35 mm) required space
between power limited and non-power limited circuits. The wiring of this module must
follow the requirements as specified in the “General” section, “UL Power Limited
Wiring Requirements.”
OR
2)
If this module is needed to drive power limited and non-power limited relays that
are next to each other, refer to the figure below showing a typical connection.
Relay #1
NO
NC
C
Power Limited Circuit
Relay #2
NO
NC
C
Power Limited Circuit
Relay #3
NO
NC
C
Relay #4
NO
NC
C
No Connection
Non-power Limited Circuit
4XZMptl.cdr
Non-power Limited Circuit
Note: Refer to the Protected Premises Unit label, located on the door of the control panel, to
indicate if any dry contacts are to be used as non-power limited dry contacts.
24
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
LED Interface Module - 4XLM (NOTIFIER)
LED Interface Module - 4XLM (NOTIFIER)
The wiring of this module must follow the requirements as specified in section”UL Power Limited Wiring
Requirements.”
+24V
Out#1
Out#2
Out#3
Out#4
System Trouble
Sound
Resound
4XLMa.cdr
1
2
3
4
5
6
7
8
RZA4Xfr.cdr
RZA4XBX.cdr
Connect to corresponding terminals
of RZA-4X Remote Annunciator.
Side View
Front View
Single-gang Box
Note: Make wiring connections with system
power off. Maximum wire impedance is 50
ohms per wiring connection.
Figure 12 LED Interface Module - 4XLM
The PDRP-1002 PN 51135:A 03/11/99
25
3 Installation Procedure
DIP Switch
Setting Mode of Operation
DIP Switch
4XRPDIPS.cdr
The DIP switch is located at the bottom of the PDRP-1002/PDRP-1002E main board.
To set a switch to the “ON” position, slide the switch up until it stops. The flushsurface switches are designed to prevent accidentally changing a switch setting and may
therefore require use of a pen or screwdriver to set them.
O1 2 3 4 5 6
N
Battery Fail
LED
Ground Fault LED O 1 2 3 4 5 6
Micro Fail LED
N
DIP Switches
Switch 3: DELAY TIMER
Switch 4: DELAY TIMER
Switch 1: CROSS ZONE
Switch 5: ABORT OPTION
Switch 2: SUPERVISORY
Switch 6: ABORT OPTION
Note: The Reset key must be depressed after any switch configuration has been made.
Cross Zone
Select the desired mode of operation and set SW1 DIP switch 1.
Switch 1
OFF
ON
Output 1 is activated by an alarm on
either Zone 1 or Zone 2.
Output 1 (Pre-discharge alarm) is
activated by the first alarmed zone
in the system. Initiation of an alarm
on the other zone will shut this
output off.
Output 2 is activated by an alarm on
either Zone 1 or Zone 2. Output 2
will pulse at 60 ppm while timer is
running or frozen by abort. Output 2
will sound steadily upon release (time
out).
Output 2 is activated when alarms
occur on both Zone 1 and Zone 2.
Output 2 will pulse at 60 ppm while
timer is running or frozen by abort.
Output 2 will sound steadily upon
release (time out).
Outputs 3 and 4 will be activated when the timer expires (provided that
Output 4 is functioning as a releasing circuit - set via DIP Switch 2).
The Timer will start whenever an
alarm occurs on either Zone 1 or
Zone 2.
The Timer will start when alarms
occur on both Zone 1 and Zone 2.
Note: Outputs 1 and 2 refer to Notification Appliance Circuits. Output 3 refers to a releasing circuit. Output
4 is determined by setting switch 2. Zones 1 and 2 refer to Initiating Device Circuits.
26
The PDRP-1002 PN 51135:A 03/11/99
3 Installation Procedure
Output 4 Supervisory/Releasing Service
Output 4 Supervisory/Releasing Service
Set the function of Output 4 via SW1 DIP switch 2.
Switch 2
OFF
ON
Output 4 will function as a
solenoid releasing circuit. This
circuit will be a non-power
limited circuit in this mode.
Output 4 will function as a supervisory input
circuit. A short condition on this circuit will
illuminate the Supervisory LED and sound
the supervisory tone on the piezo. An open
condition generates a circuit trouble
condition. This circuit will function as a
power limited circuit in this mode.
Timer
Select the desired Timer setting and set SW1 DIP switches 3 and 4 per the appropriate
column.
No Delay*
10 Seconds
20 Seconds
30 Seconds
Switch 3
OFF
OFF
ON
ON
Switch 4
OFF
ON
OFF
ON
*Abort switch is inoperative when no delay is selected.
Abort Function
Select the desired abort functions and set SW1 DIP switches 5 and 6 per the appropriate
column.
Switch 1
OFF
OFF
ON
ON
Switch 2
OFF
ON
OFF
ON
Standard UL-type
delay timer which
continues to count down
upon ABORT, and stops
and holds at 10 seconds
until release of the
ABORT switch. Upon
release of the ABORT
switch, the timer
resumes the countdown
at 10 seconds.
IRI-type delay
timer which
functions the same as
the UL-type timer
with the exception
that the ABORT will
function only if
pressed and held
before 2nd zone goes
into alarm.
NYC-type delay
timer. Pressing
ABORT, once an
alarm exists, changes
timer value to the
time selected via DIP
Switches 3 and 4
plus 90 seconds.
The timer will not
start as long as the
ABORT switch is
held. SYSTEM
RESET restores
timer to original
times selected via
DIP Switches 3 and
4. Successive
ABORTS will add
90 seconds to
selected timer value.
Local Jurisdiction
delay timer. Once
the timer has started,
pressing ABORT
restores timer to its
full time as set on
DIP Switches 3 and
4. The timer will
not start as long as
ABORT is held.
Release of the
ABORT switch
continues the
countdown, whereas
pressing ABORT
again will restore
the timer to its full
value.
These modes are the only ones that
comply with UL Standard 864
Note: ABORT timer will not operate when timer is set for “NO DELAY”.
The PDRP-1002 PN 51135:A 03/11/99
27
Appendix A: Power Calculations
Standby Battery Requirements
Appendix A: Power Calculations
Standby Battery Requirements
The Standby Battery Current figure obtained in the following table (Table 1) represents
the amount of current that must be supplied by the secondary power source (batteries)
to sustain control panel operation for one hour.
Basic Control Panel
88 mA
Control panel with AC power off, System Trouble LED and audible trouble sounder on.
If using a 4XZM Zone Relay Module1
[ ] X 8 mA =
If using a 4XTM Transmitter Module, add 11 mA
If using the Reverse Polarity Alarm output, add 5 mA
If using the Reverse Polarity Trouble output, add 5 mA
If using a 4XLM/RZA-4X Driver/Annunciator combination:1
[ ] X 19 mA =
If using a 4XMM Meter Module, add 1 mA
If using the Noti•Fire 911AC DACT, add 30 mA
Number
in use
Device
Total
Current
Current
(see Appendix B for data)
a. Two-wire detector heads
X
=
b. Four-wire detector heads
X
=
c. End of Line Relays
X
d.
25.0 mA
=
Add lines a, b, & c for
Place subtotal here
Add last column for Standby Battery Current :
and continue to next table (Table 2)
Table 1 Standby Battery Requirements
Note: The control panel will support the installation of one or two optional modules, including two of the
same type of module.
28
The PDRP-1002 PN 51135:A 03/11/99
Appendix A: Power Calculations
Ampere-Hour Calculations
Ampere-Hour Calculations
Standby Battery Current
Convert the total from
Table 1 to amps and enter
here
StandbyTime
24, 60, or 90
hours
hours =
Standby
amp/hours
Enter 0.25 for 5 minutes in alarm +
or 0.5 for 10 minutes in alarm
Alarm
amp/hours
Add Standby and Alarm amp/hours =
Total amp/
hours needed
amps
X
Table 2 Ampere-Hour Calculations
Select a battery with an equal or greater amp/hour rating than the figure obtained
in Table 2. Batteries must be lead-acid type.
PS-1270 12 volt, 7 amp/hour (two required)
PS-12120 12-volt, 12 amp/hour (two required)
Notes:
1. Alarm amp-hours assumes a maximum system draw of 3 amps in alarm for 5
minutes (0.25 amp/hour) or for 10 minutes (0.5 amp/hour)
2.
NFPA 72 Central Station and Local and Proprietary Fire Alarm Systems require 24
hours of standby.
3.
NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of
standby.
4.
Factory Mutual Systems require 90 hours of standby.
5.
The battery charger in this panel will charge a maximum of 15 amp/hours of
batteries within 48 hours (7 amp/hour minimum). Batteries larger than 12 amp/
hour will require a UL listed battery cabinet (e.g. NOTIFIER BB-17).
The PDRP-1002 PN 51135:A 03/11/99
29
Appendix B: Device Compatibility
FM-Approved Releasing Devices
Appendix B: Device Compatibility
Smoke Detector/Base
Detector Type
Max Standby
Current (mA)
Max Alarm
Current (mA)
System Sensor 2424
Photoelectric
0.10
41
System Sensor 2424TH
Photoelectric
0.10
41
System Sensor 2451
Photoelectric
0.10
39
System Sensor 2451TH (with/B402B Base)
Photoelectric
0.10
39
System Sensor 1424
Ionization
0.10
41
System Sensor 1451 (w/B402B Base)
Ionization
0.10
39
System Sensor 2412
Photoelectric
0.12
77
System Sensor 2412AT
Photoelectric
0.12
58
System Sensor 2412TH
Photoelectric
0.12
77
System Sensor 2312/24TB
Photoelectric
0.12
50
System Sensor B112LP
Base
see note
39
System Sensor B114LP
Base
see note
75
System Sensor B404B
Base
see note
see note
System Sensor 6424
Projected Beam
10
28.4
System Sensor DH400ACDCI
Ionization Duct
25
95
System Sensor DH400ACDCP
Photoelectric Duct
25
95
System Sensor 1112/24
Ionization
0.05
50
System Sensor 2112/24
Photoelectric
0.05
50
System Sensor 2112/24B
Photoelectric
0.05
65
System Sensor 2112/24T
Photoelectric w/135°
Thermal
0.05
50
System Sensor 2112/24TSRB
Photoelectric w/135°
Thermal Supervisory Relay
15
45
Note: Contact manufacturer for currents.
Table 3 UL Listed Four-Wire Smoke Detectors
FM-Approved Releasing Devices
(System Sensor’s PDRP-1002/PDRP-1002E)
Solenoid Group [A]
Skinner solenoid valve Model LV2LBX25, 24 VDC, 11 Watts, 458 mA, 1/2 in. NPS, 5/
8 in. orifice.
Solenoid Group [B] These valves are interchangeable.
ASCO solenoid valve Model T8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS,
5/8 in. orifice.
ASCO solenoid valve Model R8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS,
5/8 in. orifice.
ASCO solenoid valve Model 8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS, 5/
30
The PDRP-1002 PN 51135:A 03/11/99
Appendix B: Device Compatibility
FM-Approved Releasing Devices
8 in. orifice.
Solenoid Group [C]
Star Sprinkler Corp. Solenoid P/N 5550, 24 VDC, part of Model D deluge valve.
Kidde-Fenwal Electric Control Head P/N 890181; 24V, 2.0 Amps
Kidde-Fenwal Electric Control Head P/N 899175; 24V, 2.0 Amps
Kidde-Fenwal Electric Control Head Stackable (XP) P/N 48650001; 24V, 0.2 Amps
Kidde-Fenwal Electric and Cable Op Control Head (XP) P/N 897494; 24V, 1.5 Amps,
33 Watts
Refer to the FM approval guide for automatic water control valves which are
compatible with solenoids listed above.
Model
Type
Current (mA)
FM980-24
Floor Mount, single
68
FM996-24
Wall Mount Surface Wiring
68
FM998-24
Wall Mount Concealed Wiring
68
Table 4 24 VDC Door Holders
Vendor
Model
Current(mA)
System Sensor
A77-716B
20
Air Products & Controls, LTD
MR-101/C
MR-201/C
15
35
Table 5 UL Listed 24 VDC Relays
The PDRP-1002 PN 51135:A 03/11/99
31
Appendix B: Device Compatibility
FM-Approved Releasing Devices
SYSTEM SENSOR
Rated
Voltage²
FWR
DC
Filtered
DC
System Sensor MA-12/24D Electronic Sounder
24VDC
73
46
System Sensor SS24 Strobe
24VDC
note 5
30
System Sensor SS24LO Strobe
24VDC
45
25
System Sensor SS24LOC Ceiling Strobe (SS24LOBC - beige)
24VDC
45
25
System Sensor SS24M Strobe
24VDC
125
75
System Sensor SS24MC Ceiling Strobe
24VDC
125
75
System Sensor MASS24D Electronic Sounder/Strobe
24VDC
118
71
System Sensor MASS24LO Electronic Sounder/Strobe
24VDC
118
71
System Sensor MASS24LOC Electronic Ceiling Sounder/Strobe
24VDC
118
71
System Sensor MASS24LOLA Electronic Sounder/Strobe with Fuego lens
24VDC
118
71
System Sensor MASS24M Electronic Sounder/Strobe
24VDC
198
121
System Sensor MASS24MC Electronic Ceiling Sounder/Strobe
24VDC
198
121
System Sensor PA400R Sounder
24VDC
note 5
15
System Sensor PS24LO Add-on Strobe
24VDC
45
25
System Sensor SS2415ADA Signaling Strobe
24VDC
90
75
System Sensor SS2475ADA Signaling Strobe
24VDC
200
170
System Sensor SS24110ADA Signaling Strobe
24VDC
245
210
System Sensor SS241575ADA Signaling Strobe
24 VDC
120
93
System Sensor SS2415ADAS Signaling Strobe with Synch. Circuit
24 VDC
125
106
System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit
24 VDC
180
115
System Sensor MASS2415ADA Sounder/Signaling Strobe
24VDC
163
121
System Sensor MASS2475ADA Sounder/Signaling Strobe
24VDC
273
216
System Sensor MASS24110ADA Sounder/Signaling Strobe
24VDC
318
256
System Sensor MASS241575ADA Sounder/Signaling Strobe
24 VDC
193
139
System Sensor MASS2415ADAS Sounder/Signaling Strobe w/ Synch. Ckt.
24 VDC
163
121
System Sensor MASS241575ADAS Sounder/Signaling Strobe w/ Synch. Ckt.
24 VDC
193
139
System Sensor PS2415ADA Mini-Sounder/Strobe
24VDC
110
90
System Sensor PS2475ADA Mini-Sounder/Strobe
24VDC
135
108
System Sensor PS241575ADA Mini-Sounder/Strobe
24VDC
135
108
System Sensor PS24110ADA Mini-Sounder/Strobe
24VDC
240
225¥
System Sensor SP1R2415ADA Speaker/Signaling Strobe
24VDC
90
75
System Sensor SP1R2475ADA Speaker/Signaling Strobe
24VDC
200
170
System Sensor SP1R24110ADA Speaker/Signaling Strobe
24VDC
245
210
32
The PDRP-1002 PN 51135:A 03/11/99
FM-Approved Releasing Devices
Appendix B: Device Compatibility
System Sensor SP1R241575ADA Speaker/Signaling Strobe
24 VDC
120
93
System Sensor V4R2415ADA Speaker/Signaling Strobe
24VDC
90
75
System Sensor V4R2475ADA Speaker/Signaling Strobe
24VDC
200
170
System Sensor V4R24110ADA Speaker/Signaling Strobe
24VDC
245
210
System Sensor V4R241575ADA Speaker/Signaling Strobe
24 VDC
120
93
System Sensor SP100W24LOC Ceiling Speaker/Strobe, 8" round grille
24VDC
45
25
System Sensor SP101R24LO Speaker/Strobe, 5" square grille
24VDC
45
25
System Sensor SP101R24M Speaker/Strobe, 5" square grille
24VDC
125
75
System Sensor SP100W24MC Ceiling Speaker/Strobe, 8" round grille
24VDC
125
75
System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone
12VDC/
24VDC
20/64
38/43
System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe
24VDC
109
68
System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe
24VDC
109
68
System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe
24VDC
153
96
System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe
24VDC
189
118
System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe
24VDC
189
118
System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe
12VDC
240
191
System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe
12VDC
310
246
System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe
24VDC
278
216
System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe
24VDC
273
216
System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe
24VDC
343
271
System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe
24VDC
318
256
System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe
24VDC
198
152
System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone/Strobe
24VDC
253
241
System Sensor H12 SpectrAlert Horn
12VDC
25
14
System Sensor H42 SpectrAlert Horn3
24VDC
42
37
System Sensor S1215 SpectrAlert Strobe
12VDC
159
133
System Sensor S121575 SpectrAlert Strobe
12VDC
182
168
System Sensor S2415 SpectrAlert Strobe3
24VDC
142
83
System Sensor S241575 SpectrAlert Strobe3
24VDC
132
76
System Sensor S2475 SpectrAlert Strobe3
24VDC
170
145
System Sensor S24110 SpectrAlert Strobe3
24VDC
220
169
System Sensor P1215 SpectrAlert Horn/Strobe
12VDC
173
144
System Sensor P121575 SpectrAlert Horn/Strobe
12VDC
196
179
System Sensor P2415 SpectrAlert Horn/Strobe3
24VDC
165
94
System Sensor P241575 SpectrAlert Horn/Strobe3
24VDC
177
111
The PDRP-1002 PN 51135:A 03/11/99
33
Appendix B: Device Compatibility
FM-Approved Releasing Devices
System Sensor P2475 SpectrAlert Horn/Strobe3
24VDC
215
180
System Sensor P24110 SpectrAlert Strobe3
24VDC
265
214
System Sensor RP1215ADAARetrofit Strobe Plate
12VDC
200
170
System Sensor RP121575ADAARetrofit Strobe Plate
12VDC
240
255
System Sensor RP2415ADAARetrofit Strobe Plate
24VDC
90
75
System Sensor RP241575ADAARetrofit Strobe Plate
24VDC
120
93
System Sensor RP2475ADAARetrofit Strobe Plate
24VDC
200
170
System Sensor RP24110ADAARetrofit Strobe Plate
24VDC
245
210
System Sensor H24 SpectrAlert
24VDC
42
37
System Sensor S2415 SpectrAlertStrobe3
24VDC
142
83
System Sensor S241575 SpectrAlert Strobe3
24VDC
132
76
System Sensor S2475 SpectrAlert Strobe3
24VDC
170
145
System Sensor S24110 SpectrAlert Strobe3
24VDC
220
169
System Sensor S2415 SpectrAlert Horn/Strobe3
24VDC
165
94
System Sensor S241575 SpectrAlert Horn/Strobe3
24VDC
177
111
System Sensor S2475 SpectrAlert Horn/Strobe3
24VDC
215
180
System Sensor P24110 SpectrAlert Horn/Strobe3
24VDC
265
214
System Sensor S2415 SpectrAlertStrobe3
24VDC
142
83
System Sensor S241575 SpectrAlert Strobe3
24VDC
132
76
Note:
1) Control panels suppling Special Application (FWR, Filtered) power must use the notification appliances,
relays or door holders listed in this table.
2) All currents are in Millamperes and worst case average.
3) Nominal Operating voltage.
4) Refer to Installation Instructions for more information.
5) Contact manufacturer for currents.
Table 6 UL Listed Notification Appliances
34
The PDRP-1002 PN 51135:A 03/11/99
Appendix B: Device Compatibility
FM-Approved Releasing Devices
Number of
Detectors Per Zone
Model
Det.
ID
Detector Type
Base Model
Base
ID
Standby
Current
(uA)
PDRP-1002/
PDRP-1002E
System Sensor 1400
A
Ionization
n/a
n/a
100
20
System Sensor 1451
A
Ionization
B401B / B406B
A
120
15 / 1
System Sensor 1851DH
A
Ionization
DH1851DC
A
120
15
System Sensor 2400
A
Photoelectric
n/a
n/a
120
15
System Sensor 2400AIT
A
Photo / Isolated
Thermal / Horn
n/a
n/a
120
1
System Sensor 2400AT
A
Photo / Thermal / Horn
n/a
n/a
120
1
System Sensor 2400TH
A
Photo / Thermal
n/a
n/a
120
15
System Sensor 2451
A
Photoelectric
B401B / B406B
A
120
15 / 1
System Sensor 2451TH
A
Photo / Thermal
B401B / B406B
A
120
15 / 1
System Sensor 2851DH
A
Photoelectric
DH2851DC
A
120
15
System Sensor 1451DH
A
Ionization
DH-400
A
120
15
System Sensor 2451
A
Photoelectric
DH-400
A
120
15
System Sensor 2300T
A
Photo / Thermal
n/a
n/a
120
15
System Sensor 1800
A
Ionization
n/a
n/a
100
n/a
System Sensor 1851B
A
Ionization
B101B
A
120
n/a
System Sensor 1851B
A
Ionization
B107B
A
120
n/a
System Sensor 2800
A
Photoelectric
n/a
n/a
120
n/a
System Sensor 2800TH
A
Photo / Thermal
n/a
n/a
120
n/a
System Sensor 2851B
A
Photoelectric
B101B
A
120
n/a
System Sensor 2851B
A
Photoelectric
B107B
A
120
n/a
System Sensor 2851BTH
A
Photo / Thermal
B101B
A
120
n/a
System Sensor 2851BTH
A
Photo / Thermal
B107B
A
120
n/a
System Sensor 1151
A
Ionnization
B401 / B110LP /
B116LP
A
120
15 / 15 / 1
System Sensor 2151
A
Photoelectric
B401 / B110LP /
B116LP
A
120
15 / 15 / 1
Table 7 UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels
The PDRP-1002 PN 51135:A 03/11/99
35
Appendix C: NFPA Standard-Specific Requirements
FM-Approved Releasing Devices
Appendix C: NFPA Standard-Specific Requirements
The PDRP-1002/PDRP-1002E has been designed for use in commercial, industrial, and
institutional applications and meets the requirements for service under the National Fire
Protection Association (NFPA) Standards outlined in this appendix. The minimum
system components required for compliance with the appropriate NFPA standards are
listed below.
PDRP-1002/PDRP-1002E Control Panel containing the main control board, cabinet
(backbox and door), main supply transformer and power supply.
Batteries (refer to Appendix A for Standby Power Requirements).
Initiating Devices - connected to one of the control panel’s Initiating Device Circuits.
Notification Appliances - connected to one of the control panel’s Notification
Appliance Circuits.
Releasing Devices - connected on one of the control panel’s Releasing Circuits.
The following additional equipment is needed for compliance with the NFPA standards
listed below.
NFPA 72 Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI•FIRE 911AC DACT* - for connection to a compatible listed Central Station
DACR or Protected Premises Receiving Unit. This unit must be installed as outlined in
Figure 13.
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy
Municipal Box. This unit must be installed as outlined in Figure 15.
NFPA 72 Remote Station Fire Alarm System
4XTM Transmitter Module for connection to Fire•Lite RS82-9 Remote Station
Receiver. See Figure 16 for installation instructions.
OR
NOTI•FIRE 911AC DACT* - For connection to a compatible listed remote station
DACR. This unit must be installed as outlined in Figure 13.
*Applications which require the NOTI•FIRE 911AC are not FM approved.
36
The PDRP-1002 PN 51135:A 03/11/99
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Signaling Systems for Central Station Service
NFPA 72 Signaling Systems for Central Station Service
(Protected Premises Unit) and Remote Station Fire Alarm System (Protected Premises Unit)
NOTI•FIRE 911AC DACT* - for connection to a Central Station Receiver or Protected
Premises Receiving Unit. This unit must be installed as illustrated below. For
additional information on the 911AC, refer to document 74-06200-005.
All connections between the FACP and 911AC must be in conduit, less than 20 ft
(609.6cm) in length in the same room. If the NOTI•FIRE 911AC is not mounted in the
PDRP-1002/PDRP-1002E backbox all connections must be in conduit, less than 20 ft.
(609.6 cm) in length in the same room.
*This application using the NOTI•FIRE 911AC is not FM approved.
Note: For 911AC
• The Maximum standby load shall be 125 mA.
• The Standby by Battery Requirement: 24VDC, 7Amp-Hour-Max.
• The PDRP-1002/PDRP-1002E is not suitable for transmission of a supervisory signal to the DACT.
Note: The PDRP-1002/
PDRP-1002E is not
suitable for transmission
of a supervisory signal to
the DACT
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1 2VAC , 20VA, 60Hz or +2 4VD C
1 2VAC , 20VA, 60Hz or -2 4VD C
(R efer to m an ua l)
B AT TE RY 1 2 V D C Se a le d
B AT TE RY +
INI T IAT IN G A1 -
+
NOTE on STD DACT:
Place jumper over pins 2 and 3,
marked DACT, when employing a
DACT. This directs the control panel
to transmit all trouble conditions
except AC LOSS.
D i g it a l Ala rm C o mm u n ic a t or Tra n sm it t e r L i st e d for C e ntr al S ta t i o n o r R e m o te S ta t i on S e rv ic e.
S lid e C ov er B ack to A cces s Pro gr am m in g Ja c k a n d R el ay s
R e c h a rg e ab le
B a tt e ry
INI T IAT IN G A2 INI T IAT IN G B1 +
INI T IAT IN G B2 +
A lte rn a te R J3 1 X
Te l co Ja c k
S U PE RV IS OR Y H I
S U PE RV IS OR Y LO
T ROU B L E R EL AY N C
T ROU B L E R EL AY C O M
T ROU B L E R EL AY N O
A LA R M R ELAY N C
P ri ma r y R J 31 X
Te l co Ja c k
A LA R M R ELAY C OM
A LA R M R ELAY N O
To AC
Power
-+
PS1270
12Volt
7AH Battery
Alarm
To Central Station
JP-1
STD DACT
RP911AC.CD
Motherboard 911AC
Alarm
TB3-1
6 and 7
normally open
contacts
TB3-3
8 and 9
Trouble
TB3-4
10
normally open
contacts
TB3-6
11
Figure 13 NFPA 72 Signaling Systems for Central Station Service
The PDRP-1002 PN 51135:A 03/11/99
37
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Signaling Systems for Central Station Service
Using the MS-5012 as a DACT
1)
Reference the MS-5012 manual for additional information.
2)
Program the MS-5012 for slave applications.
3)
The PDRP-1002/PDRP-1002E is not suitable for transmission of a supervisory
signal to the DACT.
Secondary
Phone Line
Primary
Phone Line
Modular Cable
P/N MCBL-6
MS-5012
Alarm
TB2
J2
J3
Trouble
AC POWER
TROUBLE
ALARM
SUPERVISORY
1
2
3
F
4
5
6
E
7
8
9
D
1st
EVENT
A
O
B
C
ENTER
STORE
TB3
Red
Yellow
120 VAC
HOT
Black
Yellow
Neutral
Black
Ground
12VDC
Battery
2-7AH
White
Green
Motherboard
MS-5012
TB3-1
TB2-2
TB3-3
TB2-1
TB3-4
TB2-4
TB3-6
TB2-3
Alarm
12 3 4 5 6
TB3
MS5012X2.CDR
AC Wiring for DACT/FACP must be
connected to the same circuit.
PDRP-1002/PDRP-1002E
Trouble
Figure 14 Using the MS-5012 as a DACT
38
The PDRP-1002 PN 51135:A 03/11/99
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Auxiliary Fire Alarm System
All connections are power limited and supervised. This application is not suitable for
separate transmission of sprinkler supervisory or trouble conditions.
Note: Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
+
FIRE
Municipal Box Circuit
AUXPROSS.CDR
4XTB
+
-
6
Gamewell
Model M34-56
Local Energy
Municipal Box
7
4XTM (NOTIFIER)
Transmitter Module
(activated polarities
shown)
Figure 15 NFPA 72 Auxiliary Fire Alarm System
The PDRP-1002 PN 51135:A 03/11/99
39
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
NFPA 72 Remote Station Fire Alarm System
Intended for connection to a polarity reversal circuit of a remote station receiving unit
having compatible ratings. All connections are power limited and supervised with the
exception of the reverse polarity loop. Supervision of the loop is the responsibility of
the receiver.
N.C.2
DRY
SUPPLEMENTARY
CONTACTS,
RATED
3A, 120 VAC
RESISTIVE
3A, 30 VDC
RESISTIVE
N.O.2
POLE 2
N.C.1
N.O.1
POLE 1
REMOTE STATION
MASTER BOARD
(RSM-9)
9
10
11
12
13
A.C. CKT BREAKER
120 VAC
1.2 AMPS
PRESS TO
RESET
BATTERY
SIGNALING
CKT FUSE
RELAY FOR
8 AG
BELLS AND
5A
DRY
125 V
CONTACTS
--K
----
8
}
7
6
N/C
5
14
CONTROL CARD
(RSC)
FILTER
CIRCUIT SIDE
CAP
BATT
CONN
K
4
3
-
BELL
H
or
HORN
10 K
ELR
1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
ALARM
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
} SIGNAL
INPUT 3
ALARM
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
1
2
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
+
2
ZONE CARD(RSZ)
CIRCUIT SIDE
OPTIONAL ZONE CARD
(RSZ) CIRCUIT SIDE
Fire•Lite
RS82-9
Remote Station
Receiver
UL listed
GROUNDING
TERMINAL
120 VAC 1.2 A
50-60 Hz
INPUT
1
2
1
} SIGNAL
INPUT 4
ALARM
} SIGNAL
INPUT 5
} ALARM
SIGNAL
INPUT 6
ALARM
} SIGNAL
INPUT 7
ALARM
} SIGNAL
INPUT 8
ALARM
} SIGNAL
INPUT 9
+ - + -
K | | | | | | | | | | K
+
Power Transformer
-
Remote Alarm
Remote Trouble
REMPROSS.CDR
1
2
3
4
Recommended Types:
ELPOWER EP 1250C
POWER SONIC PS 1245
POWER SONIC PS 1260
POWER SONIC PS 1265
YUASA NPG-12
or equivalent
MAXIMUM BATTERY SIZE
6.0 X 2.6 X 4.1 in. (15.24 x 6.6 x10.41
4XTM (NOTIFIER)
Transmitter Module
(activated polarities shown)
Figure 16 NFPA 72 Remote Station Fire Alarm System
40
The PDRP-1002 PN 51135:A 03/11/99
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Troubleshooting Table
SYMPTOM
PROBLEM
Circuit trouble LED on
Any of the right column
yellow LEDs flashing
Any of the right column
System trouble LED on yellow LEDs steady on
SOLUTION
1. Check TB2 for proper connections. (TB3 for
4XB panels)
2. Remove all field wiring and install dummy ELR
at output circuit. Check for supervisory voltage
across it. (Normal -2.3 V). If problem persists,
Notification appliance circuit trouble replace circuit board.
3. Removed dummy ELR, reconnect field wiring
and measure voltage across output; (trouble -5V,
short OV).
4. Check for ELR at last device.
5. Check field wiring.
Initiating zone open circuit trouble
1. Check TB4 for proper connections.
2. Remove field wiring for zone in trouble and
install dummy ELR (4.7K for 24V; 2.2K for 12V).
If problem persists, replace circuit board.
3. Check for ELR at last device.
4. Check field wiring.
Zone Disable
Check installation manual.
Missing or
Disconnected
Battery trouble
Batt yellow LED
on
Power trouble LED on
AC Power LED on
1. Remove batteries, check voltage across charger
output (17 to 19V for 24V; 8-10V for 12V),
otherwise replace circuit board.
Low or damage
2. Reconnect batteries, measure battery voltage at
battery
battery terminals. If voltage is less than 85% of
rated voltage, allow them to charge for 48 hours.
3. If problem persists, replace batteries.
Ground fault trouble
Earth yellow LED on
Yellow LED on 4XTM on 4XTM
AC Power LED off
Check battery connections
1. Remove field wiring from main panel and
optional module(s) (if installed). Install dummy
ELR (4.7K for 24V; 2.2K for 12V).
2. Remove both battery leads.
3. If trouble clears, connect one circuit at a time to
pinpoint the problem.
4. If trouble doesn’t clear, replace circuit board.
1. Move Municipal Box disconnect switch SW1 up
OPT1, OPT2 jumper cut
Install optional module(s) or replace jumper if
module(s) is not used.
Municipal Box open circuit
1. Install dummy load if Municipal Box option
isn’t used.
2. Check Municipal Box wiring.
Any of the right column red LEDs on
Short on initiating circuit wiring
Remove field wiring and install ELR. If trouble
clears, look for faulty or incorrectly wired devices.
Disconnecting Municipal Box switch on 4XTM
does not create a trouble
Jumper for optional modules isn’t
cut.
Cut associated jumper OPT1 or OPT2.
4XZM: associated LED does not activate for alarm,
Optional module trouble
trouble or supervisory conditions
1. Make sure module is properly installed.
2. Move disable switch SW1 on 4XZM to the left.
RZA-4X piezo doesn’t sound for alarm, trouble or
supervisory conditions
4XLM
1. Make sure that 4XLM module is installed on J7
and J8.
2. Check field wiring.
Micro Fail yellow LED on
Microprocessor damaged.
Replace circuit board.
All RZA-4X LEDs stay on
Power wasn’t removed prior to
installation.
Hit system reset.
Loss of main power
Check incoming power (TB5). (TB1 for 4XB
panels)
Damaged circuit breaker
Replace circuit board.
Microprocessor damaged
Replace circuit board.
System trouble LED on
Micro Fail yellow LED on
Table 8 Trouble Shooting Table
The PDRP-1002 PN 51135:A 03/11/99
41
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Notes
42
The PDRP-1002 PN 51135:A 03/11/99
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Notes
The PDRP-1002 PN 51135:A 03/11/99
43
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Limited Warranty
System Sensor® warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under normal
use and service. Products are date stamped at time of manufacture. The sole and
exclusive obligation of System Sensor® is to repair or replace, at is option, free of
charge for parts and labor, any part which is defective in materials or workmanship
under normal use and service.
For products not under System Sensor®
manufacturing date-stamp control, the warranty is eighteen (18) months from date of
original purchase by System Sensor® distributor unless the installation instructions
or catalog sets forth a shorter period, in which case the shorter period shall apply.
This warranty is void if the product is altered, repaired or serviced by anyone other
than System Sensor® or its authorized distributors or if there is a failure to maintain
the products and systems in which they operate in proper and workable manner. In
case of defect, phone System Sensor® Repair Department, RA #_____________,
3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the
malfunction and suspected cause of failure.
This writing constitutes the only warranty made by System Sensor® with respect to
its products. System Sensor® does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the protection for
which they are installed or intended. Buyer acknowledges that System Sensor® is
not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident or similar incident.
SYSTEM SENSOR® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL SYSTEM SENSOR® BE LIABLE
FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
SYSTEM SENSOR® PRODUCTS. FURTHERMORE, SYSTEM SENSOR® SHALL
NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN
THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR
INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by
System Sensor®. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized.
System Sensor
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 Fax: 630-377-6495
44
The PDRP-1002 PN 51135:A 03/11/99