HPFF12 Notification Appliance Circuit (NAC) Expander Power Supply Description The Honeywell HPFF12 and HPFF12CM are Notification Appliance Circuit (NAC) Expander Power Supplies designed to extend the power capabilities of existing NACs and provide power for auxiliary devices. The HPFF12 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or stand alone panel. It is available in 12.0 amps and provides regulated and filtered 24VDC power to four NACs and an auxiliary output. The NAC outputs are rated at 3.0 amps each and the auxiliary output is rated at 2.0 amps (this output is continuously supplied, even in alarm, and therefore must be taken into account for power supply loading and battery size calculations). The combined output cannot exceed 12.0 amps. The HPFF12 provide independent output circuit supervision so that in the event of an NAC fault they can notify the attached FACP. In addition, they have a trouble memory feature that displays past troubles (by NAC) for rapid diagnostics. Synchronization is built-in for five appliance brands. The HPFF12 has two fully independent supervised initiating circuits that can be used for synchronized strobes and coded horns. The NAC outputs may be configured as any of the following: • Four Class B (Style Y) • Two Class B and one Class A • Two Class A (Style Z) • Four Class A with the optional HPP31076 Class A adapter installed These power supplies contain an internal Battery charger capable of charging up to 26.0 amp-hour (AH) batteries. The HPFF12 is mounted in a lockable wall cabinet that can accommodate up to two 18AH batteries. The HPFF12CM is designed to mount in a large lockable equipment enclosure (CAB-4; order separately). Up to three HPFF12CM power supplies can be mounted in a EQBB-D4, in positions 2, 3, and 4. Each HPFF12CM accommodates two 12AH batteries. One of the most challenging aspects of a retrofit application is locating the existing End-of-Line (EOL) resistor value. In retrofit applications that do not have the standard 3.9k EOL resistor value, the HPFF12 uses a single resistor that matches the existing EOL and can be used as a reference for all the outputs. This feature speeds installation and system checkout, because the actual EOL does not need to be located and changed in the circuit. The reference resistor value must be within the End-of-Line resistor range of 1.9k to 25k. HPFF12 Features • Complies with UL® Standard 864 9th Edition • Four (4) Class 2 power-limited, supervised notification application circuits (NACs) capable of supplying +24VDC at 3.0 amp maximum each • NAC output circuits may be configured as any of the following: - Four Class B (Style Y). - Two Class A (Style Z). - Two Class B & one Class A - Four Class A (requires the HPP31076 Class A adapter). • Four field-programmable operational modes: - Pass-through - Sync generator - Temporal generator - Pass-through Filtered • Temporal coding and sync protocols compatible with the following notification appliance brands: - System Sensor - Amseco - Faraday - Cooper-Wheelock - Gentex • Protocol pass-through for synchronizing large systems • Two fully independent supervised input/output control circuits • Redundant activation operation for survivability • Supports FACP's Selectable Silence ability • 2.0 amp auxiliary continuously supplied output • Eight status LEDs • Supervised AC input, battery voltage, auxiliary output, charger, and earth ground faults ® UL is a registered trademark of Underwriters Laboratories Inc. SIGNALING FM APPROVED S24562 7315-1637:0102 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9021-60628 Rev. C page 1 of 2 ©2013 by Honeywell International Inc. All rights reserved. Specifications Primary Input Power: Features (Continued) 120VAC, 60Hz, 5.4A; 240VAC, 50Hz, 3.2A on units with E suffix Secondary Power: 24 volt operation: two (2), 7-24 AH batteries Battery Charging Capacity Up to 26 AH batteries HPFF12 Cabinet: Holds up to two 18AH batteries HPFF12CM: Holds up to two 12AH batteries Total Output Current: 12.0A max. Standby Current: 0.075 A Auxiliary Power Output: 2.0A under all conditions NAC Output Ratings: 24VDC fully regulated 3.0A max per circuit (12.0A total) End-of-Line Resistor 1.9K to 25k ohm, ½ watt. Range: Product ships with 4 separate programming resistors. They are 3.9K (5 each - only need one for programming), 2.2K (1 each), 4.7K (1 each) and 10K (1 each) Common Trouble: 2.0A at 30VDC Relay Fail Relay: 2.0A at 30VDC Input Control Circuits: Compatible with 12 and 24 VDC control panel NACs Input Control Current 5.68 mA @ 12VDC, (alarm): 12.28 mA @ 24 VDC Temperature Rating: 32°F to 120°F (0°C to 49°C) Relative Humidity: 10% to 93% non-condensing Cabinet Dimensions: HPFF12 Cabinet: 16.65" W x 19.0" H x 5.2" D (42.29 W x 48.26 H x 13.23 D cm) CAB-4 Cabinet: 24" W x 45.9" H x 5.15" D (60.96 W x 116.52 H x 13.1 D cm) Figure 1 illustrates the HPFF12CM power supply. • Trouble indication for supervision of the following: - NAC circuits - Battery charger voltage - Auxiliary output - Earth ground faults - AC input • Optional two-hour delay for AC loss • Separate Trouble and AC Fail Form-C relay contacts • The Trouble Form-C relay contacts selectable for immediate or a 2 hour delay with AC failure • 26 AH battery charger capability; wall cabinet supports two 12V 18AH batteries, while the Multi-pack equipment cabinets supports two 12V 12AH batteries • NAC Overload protection and indication • Provision for mounting single (AOM-2SF) or 6 circuit addressable control (MMO-6SF) or relay modules (AOM-2RF) inside the enclosure. (Use mounting kit P/N:90474). Ordering Information Part Number HPFF12 HPFF12E HPFF12CM HPFF12CME HPP31076 FCI-VDR-D4B EQBB-C4 EQBB-D4 MMO-6SF AOM-2SF 90474 17070 2400-0002 Description 12.0A fire rated power supply. Unit includes red enclosure, battery cable and installation instructions. 120VAC/60Hz 240VAC/50Hz version of HPFF12 12.0A fire rated power supply (chassis mounted). Unit includes mounting hardware, battery cable and instructions for installation in a large equipment enclosure. 120VAC/60Hz 240VAC/50Hz version of the HPFF12CM Class A (Style Z) NAC Adaptor. Increase Class A circuits from 2 to 4 Louvered door with PK-625 lock and key for EQBB-C4 or EQBB-D4 backbox CAB-4 backbox enclosure for up to two (2) HPFF12CM power supplies CAB-4 backbox enclosure for up to three (3) HPFF12CM power supplies Six-circuit supervised addressable control module activated through FACP programming on a select basis to control power supply activation or output Supervised addressable control module activated through FACP programming to activate power supply Mounting kit; required to attach an addressable module onto the control circuit board (included with power supply) Replacement PK-625 lock for HPFF12 cabinet Replacement key for HPFF12 cabinet Figure 1 HPFF12CM Enclosed in the EQBB-D4 Cabinet GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60628 Rev. C page 2 of 2 www.gamewell-fci.com