HPFF12 - Gamewell

HPFF12
Notification Appliance Circuit (NAC)
Expander Power Supply
Description
The Honeywell HPFF12 and HPFF12CM are Notification
Appliance Circuit (NAC) Expander Power Supplies
designed to extend the power capabilities of existing NACs
and provide power for auxiliary devices. The HPFF12 connects to any 12 or 24V Fire Alarm Control Panel (FACP) or
stand alone panel.
It is available in 12.0 amps and provides regulated and filtered 24VDC power to four NACs and an auxiliary output.
The NAC outputs are rated at 3.0 amps each and the auxiliary output is rated at 2.0 amps (this output is continuously
supplied, even in alarm, and therefore must be taken into
account for power supply loading and battery size calculations). The combined output cannot exceed 12.0 amps.
The HPFF12 provide independent output circuit supervision so that in the event of an NAC fault they can notify the
attached FACP. In addition, they have a trouble memory
feature that displays past troubles (by NAC) for rapid diagnostics. Synchronization is built-in for five appliance
brands. The HPFF12 has two fully independent supervised
initiating circuits that can be used for synchronized strobes
and coded horns.
The NAC outputs may be configured as any of the following:
• Four Class B (Style Y) • Two Class B and one Class A
• Two Class A (Style Z)
• Four Class A with the optional
HPP31076 Class A adapter installed
These power supplies contain an internal Battery charger
capable of charging up to 26.0 amp-hour (AH) batteries.
The HPFF12 is mounted in a lockable wall cabinet that can
accommodate up to two 18AH batteries.
The HPFF12CM is designed to mount in a large lockable
equipment enclosure (CAB-4; order separately). Up to
three HPFF12CM power supplies can be mounted in a
EQBB-D4, in positions 2, 3, and 4. Each HPFF12CM
accommodates two 12AH batteries.
One of the most challenging aspects of a retrofit application
is locating the existing End-of-Line (EOL) resistor value. In
retrofit applications that do not have the standard 3.9k EOL
resistor value, the HPFF12 uses a single resistor that
matches the existing EOL and can be used as a reference
for all the outputs. This feature speeds installation and system checkout, because the actual EOL does not need to be
located and changed in the circuit. The reference resistor
value must be within the End-of-Line resistor range of 1.9k
to 25k.
HPFF12
Features
• Complies with UL® Standard 864 9th Edition
• Four (4) Class 2 power-limited, supervised notification
application circuits (NACs) capable of supplying
+24VDC at 3.0 amp maximum each
• NAC output circuits may be configured as any of the following:
- Four Class B (Style Y). - Two Class A (Style Z).
- Two Class B & one Class A - Four Class A (requires the
HPP31076 Class A adapter).
• Four field-programmable operational modes:
- Pass-through
- Sync generator
- Temporal generator
- Pass-through Filtered
• Temporal coding and sync protocols compatible with
the following notification appliance brands:
- System Sensor
- Amseco
- Faraday
- Cooper-Wheelock
- Gentex
• Protocol pass-through for synchronizing large systems
• Two fully independent supervised input/output control
circuits
• Redundant activation operation for survivability
• Supports FACP's Selectable Silence ability
• 2.0 amp auxiliary continuously supplied output
• Eight status LEDs
• Supervised AC input, battery voltage, auxiliary output,
charger, and earth ground faults
®
UL is a registered trademark of Underwriters Laboratories Inc.
SIGNALING
FM
APPROVED
S24562
7315-1637:0102
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60628 Rev. C page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Specifications
Primary Input Power:
Features (Continued)
120VAC, 60Hz, 5.4A;
240VAC, 50Hz, 3.2A on
units with E suffix
Secondary Power:
24 volt operation:
two (2), 7-24 AH batteries
Battery Charging Capacity Up to 26 AH batteries
HPFF12 Cabinet:
Holds up to two 18AH
batteries
HPFF12CM:
Holds up to two 12AH
batteries
Total Output Current:
12.0A max.
Standby Current:
0.075 A
Auxiliary Power Output:
2.0A under all conditions
NAC Output Ratings:
24VDC fully regulated 3.0A
max per circuit (12.0A total)
End-of-Line Resistor
1.9K to 25k ohm, ½ watt.
Range:
Product ships with 4 separate programming resistors.
They are 3.9K (5 each - only
need one for programming),
2.2K (1 each), 4.7K (1 each)
and 10K (1 each)
Common Trouble:
2.0A at 30VDC
Relay Fail Relay:
2.0A at 30VDC
Input Control Circuits:
Compatible with 12 and 24
VDC control panel NACs
Input Control Current
5.68 mA @ 12VDC,
(alarm):
12.28 mA @ 24 VDC
Temperature Rating:
32°F to 120°F (0°C to 49°C)
Relative Humidity:
10% to 93% non-condensing
Cabinet Dimensions:
HPFF12 Cabinet:
16.65" W x 19.0" H x 5.2" D
(42.29 W x 48.26 H x 13.23 D cm)
CAB-4 Cabinet:
24" W x 45.9" H x 5.15" D
(60.96 W x 116.52 H x 13.1 D cm)
Figure 1 illustrates the HPFF12CM power supply.
• Trouble indication for supervision of the following:
- NAC circuits
- Battery charger voltage
- Auxiliary output
- Earth ground faults
- AC input
• Optional two-hour delay for AC loss
• Separate Trouble and AC Fail Form-C relay contacts
• The Trouble Form-C relay contacts selectable for
immediate or a 2 hour delay with AC failure
• 26 AH battery charger capability; wall cabinet supports
two 12V 18AH batteries, while the Multi-pack equipment cabinets supports two 12V 12AH batteries
• NAC Overload protection and indication
• Provision for mounting single (AOM-2SF) or 6 circuit
addressable control (MMO-6SF) or relay modules
(AOM-2RF) inside the enclosure.
(Use mounting kit P/N:90474).
Ordering Information
Part Number
HPFF12
HPFF12E
HPFF12CM
HPFF12CME
HPP31076
FCI-VDR-D4B
EQBB-C4
EQBB-D4
MMO-6SF
AOM-2SF
90474
17070
2400-0002
Description
12.0A fire rated power supply. Unit
includes red enclosure, battery cable
and installation instructions.
120VAC/60Hz
240VAC/50Hz version of HPFF12
12.0A fire rated power supply (chassis
mounted). Unit includes mounting hardware, battery cable and instructions for
installation in a large equipment
enclosure. 120VAC/60Hz
240VAC/50Hz version of the
HPFF12CM
Class A (Style Z) NAC Adaptor. Increase
Class A circuits from 2 to 4
Louvered door with PK-625 lock and key
for EQBB-C4 or EQBB-D4 backbox
CAB-4 backbox enclosure for up to two
(2) HPFF12CM power supplies
CAB-4 backbox enclosure for up to
three (3) HPFF12CM power supplies
Six-circuit supervised addressable control module activated through FACP programming on a select basis to control
power supply activation or output
Supervised addressable control module
activated through FACP programming to
activate power supply
Mounting kit; required to attach an
addressable module onto the control circuit board (included with power supply)
Replacement PK-625 lock for HPFF12
cabinet
Replacement key for HPFF12 cabinet
Figure 1 HPFF12CM Enclosed in the EQBB-D4 Cabinet
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60628 Rev. C page 2 of 2