HPFF8 - Gamewell

HPFF8
NAC Expander/Power Supply
Description
The Gamewell-FCI, HPFF8 is a Notification Appliance Circuit (NAC) expansion panel designed to extend the power
capabilities of existing NACs and provide power for the
auxiliary devices. The HPFF8 connects to any 12 or 24V
Fire Alarm Control Panel (FACP) or stand alone.
The HPFF8 is available in 8.0 amps. It provides regulated
and filtered 24VDC power to each of the four NACs and an
auxiliary output. The NAC outputs are rated at 3.0 amps
each (the total output cannot exceed 8.0 amps). The auxiliary output is rated at 2.0 amps. This output is continuously
supplied, even in alarm, and therefore must be taken into
account for power supply loading and battery size calculations.
The NAC outputs may be configured as any of the following:
• Four Class B (Style Y)
• Two Class A (Style Z)
• Two Class B and one Class A
• Four Class A with the optional HPP31076 Class A
adapter installed
These power supplies contain an internal Battery charger
capable of charging up to 26.0 amp-hour (AH) batteries.
The HPFF8 is mounted in lockable wall cabinet units that
can accommodate up to two (2), 18AH batteries. A multipack option allows for up to four chassis mount units
installed in a single lockable SBB-D4 enclosure. These
chassis mount units have a "CM" suffix, HPFF8CM and
can accommodate two 12AH batteries. Power supplies are
available in either 120VAC/60 Hz or 240VAC/50 Hz.
One of the most challenging aspects of a retrofit application is locating the existing End-of-Line (EOL) resistor. In
these applications that have EOL values, other than the
3.9k normally used with the HPFF8, a single resistor
matching the existing EOL can be used as a reference for
all the outputs. This feature speeds the installation and the
system checkout, because the actual EOL does not need
to be located and changed in the circuit. The reference
resistor must be within the range of 1.9k to 25k.
HPFF8
Features
• Four (4) supervised notification application circuits
(NACs) capable of supplying +24VDC at 3.0 amp
maximum each
• NAC output circuits may be configured as any of the
following:
- Four Class B (Style Y) - Two Class B & one Class A
- Two Class A (Style Z)
- Four Class A with the
optional HPP31076 Class A
adapter installed
• Four field-programmable operational modes
• 2.0 amp auxiliary continuously supplied output
• Two (2) fully supervised input/output control circuits
• Temporal coding and sync protocols compatible with
the following notification appliance brands:
- System Sensor
- Faraday
- Gamewell
- Amseco
- Cooper-Wheelock
- Gentex
• Supervised AC input, battery voltage, auxiliary output,
charger, and earth ground faults
• Trouble indication for supervision of the following:
- NAC circuits
- Auxiliary output
- AC input
- Charger
- Battery voltage
- Open contacts in the initiating device signal inputs (for
- Earth ground faults by
FACP trouble notification)
individual status LED's
• Separate Trouble and AC Fail Form-C relay Contacts
An ISO 9001-2000 Company
SIGNALING
FM
S24562
APPROVED
7315-1637:0102
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60521 Rev. B page 1 of 2
©2010 by Honeywell International Inc. All rights reserved.
Features (Continued)
Specifications (Continued)
NAC Output Ratings:
• The Trouble Form-C relay contacts selectable for immediate or a 2 hour delay with AC failure
• 26 AH battery charger capability; the wall cabinet
supports two 12V 18AH batteries, while the multi-pack
equipment cabinets supports two 12V 12AH batteries.
• NAC Overload protection and indication
• Up to four chassis mount units (HPFF8CM) can be
installed in the SBB-D4 backbox
• Wall mount units can be configured to internally house
the following:
- one AOM-2SF single control module
- one AOM-2R single relay module
End-of-Line Resistor
Range:
Common Trouble Relay/AC
Fail Relay:
Input Control Circuit:
Temperature Rating:
Relative Humidity:
Cabinet Dimensions:
HPFF8 Cabinet:
SBB-D4 Cabinet:
Specifications
Primary Input Power:
120VAC/60Hz, 3.6A or
220VAC/50Hz, 1.5A
Secondary Power:
24 volt operation:
two (2), 7-24 AH batteries
Battery Charging Capacity: Up to 26 AH batteries
mounted
Battery Space:
HPFF8 Cabinet:
Up to two 18AH batteries
SBB-D4 Cabinet:
Up to two 12AH batteries
per supply
Total Output Power:
8.0A max
Standby Current:
0.030 A
Auxiliary Power Output:
0.15A under all conditions
2.0A if load is removed during operation (external relay
or AC Fail Relay is required)
24VDC fully regulated, 3.0A
max per circuit (8.0A total)
2K to 25k ohm, ½ watt
2.0A at 28VDC or 120VAC
16-30VDC @ 5mA min.
32°F to 120°F (0°C to 49°C
10% to 93%
non-condensing
16.65” W x 19.0” H x 5.2” D
(42.29 W x 48.26 H 13.23 D cm)
24” W x 45.9” H x 5.15” D
(60.96 W x 116.52 H x 13.1D cm)
Ordering Information
Part Number
Description
HPFF8
8A fire rated power supply operating at
120VAC/60 Hz. Unit includes red
enclosure with HPP lock and key
8A fire rated power supply - chassis
mounted operating at 120VAC/60 Hz.
Unit includes mounting hardware for
installation in the SBB-D4 enclosure
8A fire rated power supply operating at
240VAC/50 Hz
8A fire rated power supply chassis
mounted operating at 240VAC/50 Hz
Class A (Style Z) NAC module
Vented door, PK-625 lock and key for
SBB-D4 backbox, black
Backbox, accepts up to 4 chassis,
black
HPFF8CM
HPFF8E
HPFF8CME
HPP31076
FCI-VDR-D4
SBB-D4
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60521 Rev. B page 2 of 2