50027910-001 Differential Pressure Switch

50027910-001
Differential Pressure Switch
INSTALLATION INSTRUCTIONS
APPLICATION
SPECIFICATIONS
The Honeywell differential pressure switch senses
changes in duct air pressure to confirm air movement,
providing a safeguard that airflow is present during the
operation of installed IAQ equipment, including the
TrueSTEAM Humidification System.
SPST: normally open, snap-acting contacts
Pressure setpoint contacts: change at 0.04 in. W.C.
Electrical
5 amp resistive @ 24VAC
One common (C), One Normally Open (NO) quick-connect terminals
Operating Temperature: -40F to 190F (-40C to 88C)
Pressure Sample Taps
Black positive pressure tap. 1/4 in. outside diameter
Grey negative pressure tap. 1/4 in. outside diameter
Use with 1/4 in. inside diameter tubing (10 ft provided)
4-13/64 (107)
3-13/16 (97)
5/64
(2)
2-1/64 (51)
1-19/32 (41)
FULL
R
Ø3/16
(5)
3/16
(5)
M27300
3-15/16
(100)
Ø3-1/4
(83)
[2] 1/2 (13)
Fig. 1. Pressure switch.
Table 1. Parts Included.
C
1
Item
Quantity
2
Rubber Grommet
1
2
2
3
3
2
Tubing Fitting Elbow
NEGATIVE
PRESSURE
PORT
27/32
(21)
POSITIVE
PRESSURE
PORT
COMMON (C) TERMINAL
1/4 (6) X 1/32 (1) THICK
QUICK CONNECT
3
2
NO
M27302
ASSEMBLED
IN MEXICO
[2] 1/4 (6)
NC
+
PI
NORMALLY OPEN (NO)
TERMINAL 1/4 (6) X 1/32 (1)
THICK QUICK CONNECT
M27301
Fig. 2. Pressure switch dimensions.
M27323
Tubing, 1/4 in. ID
10 ft
Differential Pressure Switch (Fig. 1)
1
Screws, #8 x 3/4 in. sheet metal
2
Terminal Adaptor
2
Mounting position: mount vertically (upright) with Honeywell logo right-side up.
Approvals
Underwriters Laboratories Inc. Approved: MP2168
Canadian Underwriter Laboratories Inc. Approved:
MP2168
69-2205-01
50027910-001 DIFFERENTIAL PRESSURE SWITCH
INSTALLATION
3. The return duct is recommended, however the
switch can also be mounted to the supply duct.
• Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition. This control must be installed in accordance
with the local code and regulations.
• Check ratings and descriptions given in the
Specifications section to ensure the product is suitable
for your application.
• Installer must be a trained, experienced service
technician.
A
IMPORTANT
Do not install the switch in an area where temperature exceeds rating of -40F to 190F (-40C to
88C)
1.
2.
B
Disconnect power from the TrueSTEAM before
installing.
Mount the switch vertically with pressure connectors facing down, using provided self-tapping
screws to secure the switch to the duct.
IMPORTANT
Calibration accuracy requires that the switch be
mounted vertically (as pictured in Fig. 3).
SUPPLY DUCT INSTALL - AIR LINE ONLY TO TAP A,
CONNECTED TO THE + PORT ON THE AIR FLOW SWITCH
RETURN DUCT INSTALL - AIR LINE ONLY TO TAP B,
CONNECTED TO THE – PORT ON THE AIR FLOW SWITCH
SUPPLY/RETURN DUCT INSTALL - AIR LINE CONNECTED
TO BOTH THE + AND – PORTS ON THE AIR FLOW SWITCH
M27303
Fig. 4. Mounting the pressure switch.
4. Cut a 3/4-in. diameter hole in the duct within 10 feet
of the switch to ensure the provided tubing reaches
the pressure tap elbow.
5. Insert the grommet into the duct hole, then insert
the tube elbow into the grommet.
6. Connect the tubing to the elbow fitting and the other
end to the applicable pressure connection on the
switch:
a. Black connection if installed on the supply
b. Grey connection if installed on the return
IMPORTANT
With low-speed airflow or variable speed systems it is recommended to run tubing to both the
supply and return ducts.
M27300
Fig. 3. Pressure switch—oriented vertically.
INSIDE
OF DUCT
1
1
CONNECT TUBING TO + CONNECTION IF PRESSURE TAP IS
MOUNTED TO SUPPLY DUCT. CONNECT TO – IF PRESSURE
TAP IS MOUNTED TO RETURN DUCT.
M27304
Fig. 5. Install tubing.
NOTE: You may cut the tubing to fit the connection
length between the elbow fitting and switch. It is
also recommended to secure the hose to existing structures to avoid accidental disconnection.
69-2205—01
2
50027910-001 DIFFERENTIAL PRESSURE SWITCH
WIRING
ELECTRONIC
HUMIDISTAT
HVAC
HUM
Fig. 6 shows a close-up of the pressure switch wiring.
This applies to all wiring diagrams (Fig. 7–11).
R
C
W
Y
HUM
G
24V
24V
24V
ATTACH ADAPTER
WIRE TO TrueSTEAM
C TERMINAL
RECOMMENDED
PRESSURE
SWITCH
24V
HUM
HVAC
POWER
MASTER
HUM
1
2
2
3
ASSEMBLED
IN MEXICO
C
1
COMMON (C) TERMINAL
1/4 (6) X 1/32 (1) THICK
QUICK CONNECT
C
GT
R
RT
3
GF
NORMALLY OPEN (NO)
TERMINAL 1/4 (6) X 1/32 (1)
THICK QUICK CONNECT
3
2
NO
EXT
NC
+
R
PI
ATTACH
WIRE TO HVAC
ADAPTOR
C TERMINAL
Rc
W
Y
G
TrueSTEAM - INTERNAL
M27398
Fig. 6. Close-up of pressure switch wiring.
M27394
THERMOSTAT
Fig. 8. Wiring with electronic humidistat.
MECHANICAL
HUMIDISTAT
HVAC
HUM
HUM
R
C
W
Y
G
24V
RECOMMENDED
PRESSURE
SWITCH
24V
HUM
HVAC
POWER
MASTER
HUM
C
GT
R
RT
GF
EXT
R
Rc
W
Y
G
TrueSTEAM - INTERNAL
THERMOSTAT
M27393
Fig. 7. Wiring with mechanical humidistat.
EQUIPMENT INTERFACE MODULE (EIM)
D-1
FAN
FURNACE BOARD
R-2
1
C-3
VISIONPRO IAQ
RECOMMENDED PRESSURE SWITCH
24V
24V
TrueSTEAM - INTERNAL
HUM
HUM
C
GT
R
CONV. HP
2
W1
O/B
3
W2
AUX
C
W3
AUX2
R
Y
Y
RC
Y2
Y2
RH
G
G
C
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
G
FAN RELAY
H1
U
M2
D1
H
M2
V1
N
T2
RT
GF
EXT
M27395
Fig. 9. Wiring with VisionPRO IAQTM for independent fan control.
3
69-2205—01
50027910-001 DIFFERENTIAL PRESSURE SWITCH
EQUIPMENT INTERFACE MODULE (EIM)
FAN
FURNACE BOARD
D-1
R-2
1
C-3
VISIONPRO IAQ
24V
HVAC
POWER
MASTER
24V
HUM
GT
R
2
W1
O/B
3
W2
AUX
C
W3
AUX2
R
Y
Y
RC
Y2
Y2
RH
G
G
C
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
G
FAN RELAY
H1
U
M2
HUM
C
CONV. HP
RECOMMENDED
PRESSURE
SWITCH
RT
D1
H
M2
V1
N
T2
GF
M27396
EXT
TrueSTEAM - INTERNAL
Fig. 10. Wiring with VisionPRO IAQTM for operation dependent on HVAC power.
120 VAC
24V
HVAC
R
24V
C
R8222
RED
RECOMMENDED
PRESSURE SWITCH
HUM
L1
C
120
VAC
GT
L2
HUM
HVAC POWER MASTER
R
RT
GF
EXT
TrueSTEAM - INTERNAL
BLACK
AT120
MECHANICAL
HUMIDISTAT
HUMIDISTAT
HUM
HUM
HUM
HUM
HAC
HAC
HAC
HAC
M27397
Fig. 11. Wiring with a blower fan dedicated to the TrueSTEAM.