SPECIFICATION DATA
FEATURES
• Wireless system provides quick and easy installation
• Pre-configured door sensor and occupancy sensor
• Guest comfort is maintained by never turning off HVAC
equipment when someone is in the room – even if they
are sleeping
• Fuse protection
• Long battery life
• Low battery indication
• Receiver memory retained after power loss
• Optional sliding door/window sensor can be easily
added
• Compatible with T7350 and T7351
(WSK-24 has a N/O relay and T7350/T7351 assume that
the dry contact inputs are N/C. Therefore, a Honeywell
R8222 low voltage switching relay [N/C] needs to be
used to reverse the logic of the dry contact input into
the thermostat. R8222B1067 [24VAC, SPDT] and
R8222N1011 [24VAC, DPDT, Pilot Duty] are available.)
APPLICATION
The WSK-24 Wireless Occupancy Solution automatically
controls HVAC equipment by determining when a room is
occupied. The WSK-24 uses the combination of an occupancy
sensor and a door switch to provide optimal control. The
WSK-24 is packaged in a kit that includes the following
components:
• One 24V dry contact receiver
• One wireless PIR (passive infrared receiver) occupancy
sensor with mounting kit
• One wireless door sensor with mounting kit
• One wiring harness.
The receiver can be wired into any thermostat or controller
that supports the connection of a remote setback device. The
receiver communicates wirelessly to a PIR occupancy sensor,
a door sensor, and an optional 2nd door/window sensor. After
the receiver determines that the room is unoccupied, it closes
a dry contact switch. After the thermostat or controller
recognizes the contact closure, it places the thermostat in
economy setback mode, which provides energy savings for
when the room is unoccupied.
63-4519-02
WSK-24 WIRELESS OCCUPANCY SOLUTION
SPECIFICATIONS
Operating Temperature:
M
Receiver: -21 to 60°C (-5 to 140°F)
Door Sensora: -20 to 60°C (-4 to 140°F)
2
PIR Sensor: -20 to 40°C (-4 to 104°F)
1
Power Supply:
1
Receiver: 24 Vac/Vdc at 50/60 Hz; Standby power
consumption 15 mA; Channel 1 relay output,
N.O.
2
C3
4 B 5
6
LENGTH 3 ~ 8 M
7
M
A 8
M29142
Fig. 1. Side view of PIR detection pattern.
Door Sensor: Two CR2032 lithium batteries
70°
PIR Sensor: Three AAA E92 1.5V alkaline batteries
60°
50°
Battery Life:
40°
Door Sensora: Two years (under normal usage)
30°
PIR Sensor: One year (under normal usage)
20°
10°
Receiver Operating Frequency:
Receiver: 433.92 MHz
0°
Door Sensora: 433.92 MHz
10°
PIR Sensor: 433.92 MHz
20°
Receiver Frequency Range:
• With antenna exposed:
• Open Range: 200 ft.
• Typical Range: 100 ft.
• With antenna coiled inside receiver:
• Open Range: 50 ft.
• Typical Range: 40 ft.
30°
40°
50°
70°
60°
M29143
Fig. 2. Top view of PIR detection pattern.
Dimensions:
PIR Detection Pattern:
Door Sensora: 1.4 x 2.3 x 0.6 in (35.8 x 57.6 x 15.2 mm)
Length: 3 to 8 meters when mounted 2 meters above
the floor (see Fig. 1)
Receiver: 3.6 x 3.4 x 1.2 in (91.4 x 86.4 x 30.5 mm)
Angle: 140 degrees (see Fig. 2)
PIR Sensor: 2.8 x 3.9 x 1.1 in (71 x 100 x 28 mm)
a and
Approvals: FCC Part 15 Class B
50037735-001, the optional sliding door/window sensor
Accessories:
• 50037735-001: Optional Sliding Door/Window Sensor
Replacement Parts:
• 50037737-001: Wireless Receiver
• 50037736-001: Wireless PIR Occupancy Sensor
63-4519—02
2
WSK-24 WIRELESS OCCUPANCY SOLUTION
3-13/32
(86)
3-29/32
(100)
3-19/32
(91)
1-13/64
(31)
M29498
2-51/64
(71)
Fig. 3. Receiver DImensions
1-3/32
(28)
M29497
Fig. 4. PIR Motion Sensor Dimensions
2-19/64
(58)
1-13/32
(36)
19/32
(15)
M29501
Fig. 5. Door Sensor DImensions
3
63-4519—02
WSK-24 WIRELESS OCCUPANCY SOLUTION
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
63-4519—02 M.S. Rev. 12-12
Printed in United States