69-0482 R8285A,B CONTROL CENTERS

TRADELINE
R8285A,B
Control Centers
®
Application
R8285A,B Control Centers provide low voltage control
of line voltage fan motors and auxiliary circuits in heating,
cooling, or air conditioning systems. For model specifications, refer to Table 1.
TABLE 1—R8285 MODEL SPECIFICATIONS.
Control
Center
Replacement
Relay
R8285A
R8285B
Contact Rating
Input Voltage (Vac)
See Wiring
Diagram
spdt
120 or 208/240
Fig. 1
dpdt
120, 208/240, or 120/208/240
Fig. 2
AFL
ALR
Switching
R8222B
12
60
R8222D
12
60
The R8285A has spdt switching for two-speed fan motor applications.
The R8285B has dpdt switching for Total Comfort
applications with electronic air cleaner, humidifier, and
blower motor.
CONTACT RATINGS: Refer to Table 2.
TABLE 2—R8285A,B CONTACT RATINGS.a
Voltage
Full Load (amp)
120 Vac
12
Locked Rotor (amp)
60
aMeets UL 3/4 horsepower requirements.
208/240 Vac
6
35
RELAY COIL RATINGS:
Inrush: 20 VA maximum.
Sealed: 9 VA nominal.
Wattage: 5 watts.
Pickup Voltage: Must pick up below 18 volts.
TRANSFORMER RATINGS:
Power Rating: 40 or 50 VA.
Primary Voltage: 120, 208/240, or 120/208/240 Vac.
Secondary Voltage for 40 VA at 1.67 Amps: 24 Vac.
Secondary Voltage for 50 VA at 2.08 Amps: 24 Vac.
Open Circuit Secondary Voltage: 27.0.
Overload Protection: Inherent.
Voltage Frequency: 60 Hz.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in these instructions and on
the product to ensure the product is suitable for your
application.
3. Ensure installer is a trained, experienced service
technician.
4. After completing installation, use these instructions
to check product operation.
CAUTION
Disconnect power supply before beginning installation to prevent electrical shock and equipment
damage.
MOUNTING
The R8285 mounts on a standard four inch square
junction box. Make wiring connections in the junction box,
then fasten the R8285 to the junction box by placing the
junction box screws through the notches in the R8285
mounting plate.
J. H. • 4-94
1 • ©Honeywell Inc. 1994 • Form Number 69-0482—2
NOTE: The R8285 must be mounted in an enclosure. The
R8285 may be mounted in any position except with the
mounting plate horizontal and the relay on top of the
mounting plate.
Fig. 2—R8285A typical hookup in two-speed
fan motor application.
R8225 ISOLATION
RELAY
HEATING
CONTROL
WIRING R8285A, B MODELS
All wiring must comply with local codes and ordinances. Disconnect power before making wiring connections to prevent electrical shock or equipment damage.
1. Make primary connections to line voltage power
supply. On multitap models, make sure you are using
correct leads or terminals for available power supply. See
Fig. 1.
2. On multitap models with leadwires, insulate ends of
unused leads by taping or capping with a solderless connector.
3. Make secondary connections to 24 Vac control circuit.
4. Refer to Figs. 2 or 3 for typical wiring diagrams.
THERMOSTAT
2
PLENUM SWITCH
OR OTHER
SWITCHING DEVICE
W
R
PRIMARY
HEATING
CONTROL
GY
BROWN
RED
R8285A,H
W
COIL
BLACK
R
L1
(HOT)
G
1
WHITE
Y
L2
C
LO
HI
BLACK
C
Fig. 1—Schematic for single and multitap
transformers.
TWO SPEED
FAN MOTOR
CONTACTOR OR
COMPRESSOR
CONTROL PANEL
120 VAC MODELS
COMMON
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
BLACK
PRIMARY
120 V
1
2 USE OPTIONAL HOOKUP WITH ISOLATING RELAY (DASHED LINE) IF
HEATING CONTROL HAS A SEPARATE POWER SUPPLY. ISOLATION
OF THE POWER SUPPLIES MAY ALSO BE ACCOMPLISHED BY USING
SPECIAL THERMOSTAT SUBBASE COMBINATIONS WITH ISOLATED
CIRCUITS (SUCH AS T87F-Q539A1147, T834A, T822A).
M1157B
REFER TO SPECIFICATION SHEETS FOR DETAILS.
SECONDARY
3
120V - WHITE
208/240 VAC MODELS
COMMON
Fig. 3—R8285B typical hookup in two-speed
fan motor Total Comfort application.
2
BLACK
208V
PRIMARY
240V
3
RED
1
R882A ISOLATION
RELAY
SECONDARY
HEATING
CONTROL
ORANGE
T87F
THERMOSTAT
120/208/240 VAC MODELS
2
WHITE
240V
RED
1
SECONDARY
B
3
PRIMARY
HEATING
CONTROL
W
BLACK
W
R
COIL
BLACK
G
BLACK IS COMMON WITH RESPECT TO THE TRANSFORMER
WINDING ONLY AND NOT THE EXTERNAL CIRCUIT.
RED/
YELLOW
2
SECONDARY CONNECTIONS ARE SCREW TERMINALS, 1/4 INCH
QUICK-CONNECTS OR BLUE AND YELLOW LEADWIRES.
BROWN
1
R
GY
R8285B
ORANGE
VIOLET
3
W
BLACK
208V
YELLOW
120V
PRIMARY
RED
COMMON
2
F50 OR F51
AIR CLEANER
WHITE
Y
C
L1
(HOT)
1
L2
SOME MODELS AVAILABLE WITH 1/4 INCH QUICK-CONNECTS.
LO
M21020
HI
R8243
CONTACTOR OR
COMPRESSOR
CONTROL PANEL
COM
FAN
SWITCH
H808A
HUMIDISTAT
IMPORTANT: Only use Underwriters Laboratories Inc.
listed connectors when making external circuit connections to the line voltage leadwires of this device.
HUMIDIFIER
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2 USE OPTIONAL HOOKUP WITH ISOLATING RELAY (DASHED LINE) IF
HEATING CONTROL HAS A SEPARATE POWER SUPPLY. ISOLATION
OF THE POWER SUPPLIES MAY ALSO BE ACCOMPLISHED BY USING
SPECIAL THERMOSTAT SUBBASE COMBINATIONS WITH ISOLATED
CIRCUITS (SUCH AS T87F-Q539A1147, T834A, T822A).
M1153C
REFER TO SPECIFICATION SHEETS FOR DETAILS.
69-0482—2
2
Checkout
Fig. 4—Replacing R8285 relay.
Always conduct a thorough checkout when installation
is complete. Operate the system through at least one complete cycle to assure that the system equipment and the
R8285 operate as intended.
RETAINING BAIL
Service
CAUTION
Disconnect the power supply before servicing to
prevent electrical shock and equipment damage.
RECEPTACLE
The R8285 relay is field replaceable. Replace the relay
as follows:
1. Refer to Table 1 for the appropriate replacement
relay.
2. Remove the plug-in relay from the receptacle and
replace with the new relay. See Fig. 4.
R8222 RELAY
3
M1298
69-0482—2
Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
69-0482—2
Printed
in U.S.A.