32-00005-01 - R8001A1001 SLATE™ Base Module

SLATE
™
Base Module
R8001A1001
INSTALLATION INSTRUCTIONS
Scan for more information
Application
SLATE™ brings configurable safety and programmable logic
together into one single platform. The platform can easily be
customized for almost any requirement or application—offering
virtually limitless development opportunities with far less
complexity.
The R8001A1001 base module provides communications
and power supply for the SLATE system, configurable safety
for Burner Control, Flame Amps, Fuel Air Ratio, and Limit
modules, and programmable logic for Digital and Analog I/O, and
Annunciation. SLATE is a combustion system with configurable
safety and programmable logic. The system is modular in format
and DIN rail mountable. Modules include:
• Base
• Burner Control Module
• Flame Amp Modules
• Fuel Air Ratio Control Module
• Limit Module
• Analog I/O Module
• Digital I/O Module
• Annunciator Module
SLATE™ BASE MODULE
R8001A1001
3
Features
Within the SLATE system, the base module provides:
• Power to all modules with multiple voltage options
• External communication protocols Modbus/TCP, BACnet
MSTP or IP, and web services
• Overall health of the system
• The ability to do remote troubleshooting
• Network identification of the system as a single device
• Web-based pages (both Honeywell provided and designer
customized) for Web browser access to the system
• Module identification for the system
• Event log storage for user lockouts, fault history, and user
requested events
• Trend logging for user specified data
Specifications
Electrical Ratings:
Input Voltage and Frequency:
24 VDC (± 15%),
24 VAC (± 15%), 50/60 Hz,
85-264 VAC, 50/60 Hz
Output Voltage:
18 VDC (± 1 VDC)
Power Dissipation:
38W max @ 24V (approx. 12 modules),
45W max @ 85-264V (approx. 14 modules)
Fusing Total Connected Modules: 5A, slow type, non-replaceable
Terminal Ratings: See Table 1.
Terminal
Description
Rating
E100-1
L1 - line voltage hot
---
E100-2
L2 - line voltage common
---
E100-3
PE - Earth Ground
---
432-00005—01
a
Terminal
Description
Rating
E200-1
Alarm (dry contacts)
120 / 240 VAC, 1A
pilot duty
E200-2
Alarm (dry contacts)
120 / 240 VAC, 1A
pilot duty
E200-3
Unused
---
E200-4
A (BACnet MS/TP)
---
E200-5
B (BACnet MS/TP)
---
E200-6
GND (BACnet MS/TP)
---
E200-7
VAUX +
3.3-24 VDC output,
250mA max
E200-8
VAUX - a
3.3-24 VDC output,
250mA max
Do not connect to earth ground.
Table 1. Terminal Ratings.
Environmental Ratings
Ambient Temperature:
Operating: -20°F to +150°F (-29°C to +66°C).
LCD Operating: 32°F to +150°F (0°C to +66°C).
Shipping: -40°F to +150°F (-40°C to +66°C)
Humidity: 95% continuous, noncondensing.
Vibration: 0.5G environment
Dimensions:See Fig. 1
Weight: 2
lb 1 oz (0.94 Kg)
Approvals:
Underwriters Laboratories Inc. Listed, File: MP268.
IRI acceptable.
Federal Communications Commission: Part 15, Class A
Emissions.
Must be mounted inside a grounded metal enclosure.
Mounting:DIN Rail (See Fig. 4)
SLATE™ BASE MODULE
R8001A1001
5
7-3/32
(180)
6-3/32 (155)
5-19/64 (135)
M35389
Fig. 1. Dimensions in in. (mm).
632-00005—01
Principal Technical Features
The R8001A1001 base module provides communications
and power supply for the SLATE system, configurable safety
for Burner Control, Flame Amps, Fuel Air Ratio, and Limit
modules, and programmable logic for Digital and Analog I/O, and
Annunciation.
Communications
The base module provides communications via Modbus IP
RS485, BACNet IP/MSTP (RS-485), and Web Services.
User Interface
The menu-driven user interface provides system status and alerts
via a dot matrix display on the front of the module. It is controlled
by a 7-button keypad.
LED Array
There are three LEDs on the front of the base module that
provide quick identification of system status and problems. This
status is broadcast to other modules on the platform bus in case
they are affected by the inoperable module(s).
LED
Color
Power No light
Green
CPU
Fault
Description
System does not have power
System has power
Red
No wire sheet or problem with the
wire sheet
Green
Running
Red
Fault
No light
Running
Table 2. LED Descriptions.
SLATE™ BASE MODULE
R8001A1001
7
LCD Screen
The base module LCD screen will show information about various
modules and other parts of the combustion system. Use the
arrow keys to navigate the items on the LCD screen, then press
OK to select one.
In Fig. 2, Burner6 is in Lockout. For additional information,
navigate to that menu item and press OK.
Light Sensor
>
>
Slate
_____________________________
_
_
_
Application:
Running
_
_
_
_
m6 Burner6:
Lockout >_
_
1FM-VU-Achk
Running
m1 Base:
Running
m2 Burner:
Hold
>
_____________________________
scroll
8:07 am OK:select
Power
CPU
Fault
Status
Main
Power
OK
Menu
M35422
Fig. 2. LCD display showing a fault (Burner6 is in Lockout).
Additional information, as shown in Fig. 3, is displayed. Use this
information to troubleshoot the combustion system.
832-00005—01
<
m6 Burner6: FAULT
_____________________________
Fault code: 35
Flame is OFF
Date:
4 Nov 2014
Time:
3:30 PM
Power
CPU
Fault
Light Sensor
>
>
_____________________________
scroll
<back
Status
Main
Power
OK
Menu
M35423
Fig. 3. Additional lockout information.
Light Sensor
SLATE contains a light sensor that is used when the system is
exposed to light. This is a power saving feature.
Installation
WARNING
Fire or Explosion Hazard
Can cause severe injury, death, or property damage.
Verification of safety requirements must be performed
each time a control is installed on a burner to prevent
possible hazardous burner operation.
SLATE™ BASE MODULE
R8001A1001
9
When Installing This Product
1. Read these instructions carefully. Failure to follow them could
damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product
to make sure the product is suitable for your application.
3. After installation is complete, check out the product operation
as provided in these instructions.
Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death, or equipment damage.
1. Disconnect the power supply before beginning installation to
prevent electrical shock and equipment damage. More than
one power supply disconnect can be involved.
M35390
Fig. 4. Installing the Base Module on DIN Rail.
1032-00005—01
2. Wiring must comply with all applicable codes, ordinances
and regulations. See Table 1, Table 3, and “Recommended
Grounding Practices” on page 13 for connections and
terminals. For DIP switch settings, see “DIP Switches” on
page 15.
Note: MS/TP must be wired in a straight line without spurs­—no
star wiring.
Status
Main
Power
INTERNAL
SD CARD
REMOVEABLE
SD CARD
USB
ETHERNET
INPUT
POWER
L1 L2(N)
DIP
SWITCHES
OK
Menu
INTERNAL
CLOCK
BATTERY
BACnet AND
PROGRAMMABLE
POWER SUPPLY
ALARM
A BG
M35391
Fig. 5. Base Module inputs and terminals.
SLATE™ BASE MODULE
R8001A1001
11
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. The R8001A1001 should not interfere with the proper safety
operation of the controls, limits, and interlocks it is monitoring.
After installation, check each control, limit, and interlock to
ensure that it is operating properly. DO NOT PLACE JUMPER
WIRES ACROSS THE INSTALLATION CONTROLS, LIMITS,
AND INTERLOCKS.
Application
Recommended Wire
Size
Recommended
Part Numbers
Line voltage
terminals
14, 16, or 18 AWG
copper conductor, 600
volt insulation, moistureresistant wire.
TTW60C,
THW75C,
THHN90C
Communication
linesa
22 AWG two-wire
twisted pair with ground,
or five-wire.
Belden 8723
shielded cable or
equivalent.
Other terminals
18 AWG wire insulated
for voltages and
temperatures for given
application.
TTW60C,
THW75C,
THHN90C
BACnet MS/TP connections must be wired in daisy chain
configuration, 1(a)-1(a), 2(b)-2(b), 3(c)-3(c). The order of
interconnection of all the devices is not important. Be aware that
the termination DIP switch (number 3) must be used if the SLATE
system is at the end of connections over 100 feet.
a
Table 3. Recommended Wire Sizes and Part Numbers.
1232-00005—01
Recommended Grounding Practices
Use an Earth ground or a signal ground as described below.
Earth ground (Base, Rectification Flame Amp
Module, other modules optional)
1. Use to provide a connection between the base and the
control panel of the equipment. Earth ground must be capable
of conducting enough current to blow the breaker in the event
of an internal short circuit.
2. Use wide straps or brackets to provide minimum length,
maximum surface area ground conductors. If a leadwire is
required, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the ground
path are free of nonconductive coatings and protected against
corrosion on mating surfaces.
Signal ground
Note the 18V system ground is not electrically connected to earth
ground. Follow local codes and appliance recommendations to
determine if this should be connected to earth ground.
Recommended wire routing of leadwires
• Do not run high voltage ignition transformer wires in the same
conduit with the flame detector or data lines.
• Do not route flame detector or data lines in conduit with line
voltage circuits.
• Enclose flame detector leadwires without armor cable in metal
cable or conduit.
• Follow directions in flame detector instructions.
Be sure loads do not exceed the terminal ratings. Refer to the
labels or terminal ratings in Table 1.
The SLATE system must be mounted in an electrical enclosure.
When mounting in an electrical enclosure, provide adequate
clearance for servicing, installation and removal of SLATE
modules.
SLATE™ BASE MODULE
R8001A1001
13
IMPORTANT
1.This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance
with these instructions, may cause interference for radio
communications. It has been tested and found to comply
with the limits of a Class A computing device of part 15
of FCC rules, which are designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in a
residential area may cause interference; in which case, the
user, at their own expense, may be required to take whatever
measures are required to correct this interference.
2.This digital apparatus does not exceed the Class A limits for
radio noise, set out in the Radio Interference Regulations of
the Canadian Department of Communications.
3.For straight gas burner applications, the oil limit and interlock
inputs DO NOT need to be jumpered.
4.For straight oil burner applications, the gas limit and interlock
inputs DO NOT need to be jumpered.
5.For combination gas-oil burner applications, a double pole,
double throw (dpdt) fuel select switch is required.
6.Cable shield must be terminated to ground at both ends. If
shielded cable is NOT used, use three-wire twisted cable.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or equipment
damage.
Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect can
be required.
1432-00005—01
DIP Switches
The SLATE Base Module has three DIP switches. DIP switches 1
and 2 should be On only if no other MS/TP device providing bias
resistors is connected.
DIP switch 3 should be On only if SLATE is the last device in the
communication chain.
SLATE™ BASE MODULE
R8001A1001
15
32-00005-01
For more information and detailed instructions on the SLATE display
please refer to the SLATE User Guide document located on our
website at http://combustion.honeywell.com/SLATE