We help ideas meet the real world DELTA Test Report TEST Reg. no. 19 Type approval testing of C6200 and C6250 Performed for Selco A/S DANAK-1910203 Project no.: A505341 Page 1 of 54 including 6 annexes 19 June 2008 DELTA Danish Electronics, Light & Acoustics Venlighedsvej 4 2970 Hørsholm Denmark Tel. (+45) 72 19 40 00 Fax (+45) 72 19 40 01 www.delta.dk This report is issued under the rules of DANAK (Danish Accreditation) and ILAC (International Laboratory Accreditation Cooperation) including its MRA (Mutual Recognition Arrangement). Further information can be found at www.danak.dk and www.ilac.org. The report must not be reproduced, except in full, without the written approval of DELTA. Version m DANAK-1910203 DELTA-A505341 Page 2 of 54 Title Type approval testing of C6200 and C6250 Test object C6200 and C6250 Detailed information is given in Section 2. The test objects were received on 25 March 2008. Report no. DANAK-1910203 Project no. A505341 Test period 25 March - 16 June 2008 Client Selco A/S Betonvej 10 4000 Roskilde Denmark Tel.: +45 70 26 11 22 Fax: +45 70 26 25 22 Contact person Mr Jesper Højland E-mail: [email protected] Manufacturer Selco A/S Specifications IACS E10: Rev. 5, Dec 2006. “Test Specification for Type Approval. Test specification applicable, but not confined to, all equipment used for: - Control, protection and safety; - internal communication”. IEC 60945: Fourth edition, 2002 “Maritime navigation and radio communication equipment and systems General requirements - Methods of testing and required test results”. IEC 60533: Second edition, 1999. “Electrical and electronic installations in ships - Electromagnetic compatibility”. Results No malfunctions were detected. The criteria for compliance are listed in Section 3.2. Test personnel Karsten Kruse Jensen Henrik Egeberg Nielsen Poul Nørgaard Poul Terkelsen Olling Truelsen HFR/lko DANAK-1910203 DELTA-A505341 Page 3 of 54 Date 19 June 2008 Project manager Henrik Funding Raun, B.Sc.E.E. DELTA Responsible Susanne Otto, B.Sc.E.E. DELTA HFR/lko DANAK-1910203 DELTA-A505341 Page 4 of 54 Table of contents Page 1. 1.1 1.2 Summary of test Test requirements Conclusion 6 6 7 2. 2.1 2.2 Test objects Test object(s) Auxiliary equipment 8 8 9 3. 3.1 3.2 3.3 3.4 3.5 General test conditions Test setup Criteria for compliance Functional test Standard environment Test sequence 10 10 10 10 11 11 4. 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 Test and results Power supply failure Power supply variations (permanent) Low temperature (cold) Dry heat Damp heat, cyclic Insulation resistance High voltage Resonance search (4 g) Endurance - random (4 grms) Electrostatic discharge Radiated radio frequency interference Conducted low frequency interference Conducted radio frequency interference Fast transients (burst) Slow transients (surge) Radiated emissions Conducted emissions Enclosure protection, IP 2X 12 12 12 13 13 14 15 15 16 16 17 18 19 19 20 21 21 22 23 Annex 1 List of instruments 24 Annex 2 Photos 26 Annex 3 Test record sheets - Conducted emissions 35 Annex 4 Test record sheets - Radiated emissions 42 Annex 5 Measurement curves - Vibration 47 HFR/lko DANAK-1910203 DELTA-A505341 Page 5 of 54 Annex 6 Functional test procedure (from Client) (This annex is informative and not part of the accredited report) HFR/lko 53 DANAK-1910203 DELTA-A505341 Page 6 of 54 1. Summary of test 1.1 Test requirements Test Power supply failure Power supply variations Low temperature (cold) Dry heat Damp heat (cyclic) Insulation resistance High voltage Vibration (resonance search) Vibration (endurance - random) Electrostatic discharges Radiated radio frequency interference Conducted low frequency interference Conducted radio frequency interference Electrical fast transients (burst) Slow transients (surge) Radiated emissions Conducted emissions Enclosure protection, IP 2X HFR/lko Test method IACS E10:2006 IEC 60945:2002, IACS E10:2006 IEC 60068-2-1:2007 IEC 60068-2-2:2007 IEC 60068-2-30:2005 IACS E10:2006 IACS E10:2006 IEC 60068-2-6:2007 IEC 60068-2-64:1993 IEC 61000-4-2:2001 IEC 61000-4-3:2006 IACS E10:2006 IEC 61000-4-6:2004 IEC 61000-4-4:2004 IEC 61000-4-5:2005 CISPR 16-1:1999, CISPR 16-2:2002, CISPR 16-1:1999, CISPR 16-2:2002, IEC 60529:2001 DANAK-1910203 DELTA-A505341 Page 7 of 54 1.2 Conclusion The test objects mentioned in this report meet the relevant requirements of the standards stated below. • IACS E10:2004 • IEC 60533:1999 • IEC 60945:2002 The test results relate only to the object tested. HFR/lko DANAK-1910203 DELTA-A505341 Page 8 of 54 2. Test objects 2.1 Test object(s) Test object 2.1.1 Name of test object Model / type Part no. Serial no. FCC ID Manufacturer Supply voltage Comments Generator Controller C6200 C6200.0010 413643 Selco A/S 24 VDC The customer states as follows, regarding modifications of the test object: “Modification 1: A capacitor of 10nF has been added to the reset pin 44 of the DSP (ADSP2184, IC8). Modification 2: A T-Filter 22nF has been added to the analogue output 1 and 2.” Test object 2.1.2 Name of test object Model / type Part no. Serial no. FCC ID Manufacturer Supply voltage Comments HFR/lko Hand Terminal for C6200 C6250 C6250.0010 409497 Selco A/S 24 VDC through CAN bus - DANAK-1910203 DELTA-A505341 Page 9 of 54 2.2 Auxiliary equipment Auxiliary equipment 2.2.1 Name of auxiliary equipment Model / type Part no. Serial no. FCC ID Manufacturer Supply voltage Comments HFR/lko Sigma UI Module S6500 S6500.0010 381405 Selco A/S 24 VDC - DANAK-1910203 DELTA-A505341 Page 10 of 54 3. General test conditions 3.1 Test setup A drawing of the test setup is enclosed in Annex 6. 3.2 Criteria for compliance No change of the actual operational states of the test objects is allowed. However, temporary change is allowed during the power supply failure test. In addition, the following generic acceptance criteria for compliance were in force during the EMC immunity testing: 3.3 • Performance Criterion A: (For continuous phenomena): The EUT shall continue to operate as intended during and after the test. No degradation of performance or loss of function is allowed as defined in the relevant equipment standard and in the technical specification published by the manufacturer. • Performance Criterion B: (For transient phenomena): The EUT shall continue to operate as intended after the tests. No degradation of performance or loss of function is allowed as defined in the technical specification published by the manufacturer. During the test, degradation or loss of function or performance which is self-recoverable is, however, allowed but no change of actual operating state or stored data is allowed. • Performance Criterion C: Temporary degradation or loss of function or performance is allowed during and after the test, provided the function is selfrecoverable, or can be restored by the operation of the controls as defined in the relevant equipment standard and in the technical specification published by the manufacturer. Functional test A functional test was performed before, during (if specified) and after each test. The functional test was carried out in accordance with the functional test procedure provided by the customer. The functional test procedure is given in Annex 6. HFR/lko DANAK-1910203 DELTA-A505341 Page 11 of 54 3.4 Standard environment Normal environmental condition: 3.5 HFR/lko Temperature : 15 °C - 35 °C Humidity : 25 %RH - 75 %RH Air pressure : 86 kPa - 106 kPa (860 mbar - 1060 mbar) Power supply voltage : Unom. ±3% Test sequence DANAK-1910203 DELTA-A505341 Page 12 of 54 4. Test and results 4.1 Power supply failure Test methods IACS E10, Test No. 3. Procedure The power supply is interrupted 3 times within 5 minutes with a break time of 60 seconds. Normal power-up procedure is to be obtained after each power break. Results No malfunction was observed during the exposure, and the function of the test objects was OK after each exposure. One of the power supply failures was made during the boot sequence. Performance criterion: C. 4.2 Power supply variations (permanent) Test method IACS E10, Test No. 4. IEC 60945, Section 5.2.2. Procedure (24 VDC input) Unom. = Nominal supply voltage = 24 VDC Exposures, each with a duration of 15 minutes, are performed at the following supply voltages: U1 = Un +30 % = 31.2 VDC U2 = Un -25 % 18.0 VDC = The test objects are observed during the exposures, and a functional test is performed at the end of each exposure. An additional power supply variations test is performed as part of the functional test during the low temperature and the dry heat test profiles. HFR/lko DANAK-1910203 DELTA-A505341 Page 13 of 54 Results No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure. Performance criterion: A. 4.3 Low temperature (cold) Test method IEC 60068-2-1:2007, Test Ad: Cold for heat-dissipating object with gradual change of temperature. Severity and procedure Temperature : -15 °C Duration : 16 hours The test objects are de-energised during the exposure. However, during the last 2 hours of the exposure, the test objects are energised and a functional test is performed. A power supply variations test ref. Section 4.2 is performed as part of the functional test during the low temperature test profile. After recovery, a functional test and an insulation resistance test are performed in standard environment. Results No malfunction was observed during the exposure and the function of the test objects was OK during the last 2 hours of the exposure and after recovery. 4.4 Dry heat Test method IEC 60068-2-2:1974, Test Bd: Dry heat for heat-dissipating object with gradual change of temperature, Amendment 1 (1993), Amendment 2 (1994). Severity and procedure HFR/lko Temperature : +70 °C Duration : 16 hours Humidity : Below 50 %RH DANAK-1910203 DELTA-A505341 Page 14 of 54 The test objects are energised and in normal operating condition during the exposure. During the last hour of the exposure, a functional test is performed. A power supply variations test ref. Section 4.2 is performed as part of the functional test during the dry heat test profile. After recovery the functional test is repeated in standard environment. Results No malfunction was observed during the exposure and the function of the test objects was OK during the last 2 hours of the exposure and after recovery. 4.5 Damp heat, cyclic Test method IEC 60068-2-30 (2005), Test Db: Damp heat cyclic (12 + 12 hours’ cycle), Variant 1. Severity and procedure Lower temperature : 25 °C Humidity at lower temperature : >95 %RH Upper temperature : 55 °C Humidity at upper temperature : 93 %RH Number of cycles : 2 During the first cycle, the test objects are energised and in normal operational mode. A functional test is performed during the first 2 hours of the 55 °C phase. During the second cycle, the test objects are de-energised. However, during the last 2 hours of the second 55 °C phase, the test objects are energised and a functional test is performed. After recovery the test objects are energised and a functional test and an insulation resistance test are performed in standard environment. Results No malfunction was observed during the exposure, and the function of the test objects was OK during the first and second cycle at 55 °C and 93 %RH and after recovery. No corrosion attack was observed after the exposure. HFR/lko DANAK-1910203 DELTA-A505341 Page 15 of 54 4.6 Insulation resistance Test method IACS E10, Test No. 9. Procedure The insulation resistance is measured between shorted supply terminals and earth with 50 VDC for 24 VDC power ports. The insulation resistance has to be above 10 MΩ initially, and above 1 MΩ after the cold, damp heat and high voltage exposures. Results Cable designation Test condition Test voltage [Vrms] Duration [sec] Insulation resistance [MΩ] Initial 50 VDC 60 sec. > 10 MΩ After Low temperature test 50 VDC 60 sec. > 1 MΩ After Damp heat test 50 VDC 60 sec. > 1 MΩ After High voltage test 50 VDC 60 sec. > 1 MΩ DC power port 4.7 High voltage Test method IACS E10, Test No. 10. Procedure 550 VAC, 50 Hz is applied between shorted supply terminals and earth for 1 minute for the 24 VDC supply line. No flashover, breakdown etc. is acceptable. Results No flashover or breakdown was observed during the exposure. The insulation resistance was OK after the exposure. HFR/lko DANAK-1910203 DELTA-A505341 Page 16 of 54 4.8 Resonance search (4 g) Test method IEC 60068-2-6:2007, Test Fc: Vibration (sinusoidal). Severity and procedure Frequency range : 2 - 100 Hz Frequency / amplitude : 2 - 25 Hz : 25 - 100 Hz : ± 1.6 mm ±4g Sweep rate : Max. 0.5 octave/min. Number of axes : 3 mutually perpendicular The test objects are de-energised during the exposure. During the resonance search, the resonance frequencies are determined by means of stroboscopic light with slow motion facility and accelerometer measurements of the amplification factors (Q). Resonance frequencies with an amplification factor above 2 are recorded. Results Amplification factor above 2 was recorded. Place of measurement C6200 C6250 4.9 Axis Frequency [Hz] Amplification factor X 2 - 100 <2 Y 2 - 100 <2 Z 75 7.8 X 2 - 100 <2 Y 2 - 100 <2 Z 100 2.7 Endurance - random (4 grms) The sinusoidal vibration test according to IACS E10 is replaced by random vibration test according to “Environmental test specification for instrumentation and automation equipment” No. 2.4, issued April 2006 by DNV. This random vibration test will cover the requirements of the sinusoidal vibration test according to IACS E10. HFR/lko DANAK-1910203 DELTA-A505341 Page 17 of 54 Test method IEC 60068-2-64:1993, Test Fh: Vibration, broadband random (digital control). Severity and procedure Frequency range : 2 - 100 Hz Acceleration spectral : 2 - 25 Hz Density : 25 - 100 Hz : Total RMS level : 4.0 g Duration : 150 minutes per axis Number of axes : 3 mutually perpendicular : +12 dB/octave 0.2 g2/Hz The test objects are energised and in normal operational mode during the exposures. A functional test is performed during and after the exposure in each axis. A visual inspection is performed after the exposure. Results No malfunction was observed during the exposure and the function of the test specimens was OK during and after the exposure in each axis. No damage was observed after the exposures. 4.10 Electrostatic discharge Test method IEC 61000-4-2:2001: Testing and measurement techniques - Electrostatic discharge immunity test. Severity and procedure Air discharge : 2, 4 and 8 kV Contact discharge : 2, 4 and 6 kV Energy storage capacitance : 150 pF Discharge resistance : 330 Ω Polarity : + and - Number of discharges : 10 per polarity at each test point The discharges are applied only to such points and surfaces of the test objects, which are accessible to personnel during normal use. HFR/lko DANAK-1910203 DELTA-A505341 Page 18 of 54 Contact discharges are applied to conductive surfaces and coupling planes. Air discharges are applied to insulating surfaces. The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure. Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure. Performance criterion: B. 4.11 Radiated radio frequency interference Test method IEC 61000-4-3:2006: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test. Severity and procedure Frequency range : 80 - 2000 MHz Field strength : 10 V/m Modulation : 80 % AM, 1000 Hz sine wave The test is performed in a semi anechoic room. The field is generated using linearly polarised broadband antennas. The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure and a functional test is performed after the exposure. Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure. Performance criterion: A. HFR/lko DANAK-1910203 DELTA-A505341 Page 19 of 54 4.12 Conducted low frequency interference Test method IACS E10:2006, Test No. 15. Severity and procedure Frequency range : 0.05 - 10 kHz Amplitude (DC-supplied) : 0.05 - 10 kHz Maximum applied power : 2.0 W : 10 % of Unom./ min. 3 Vrms The impedance of the test generator is less than 1 Ω. The test signal is superimposed on the power supply lines via a coupling transformer. The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure. Results No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure. Performance criterion: A. 4.13 Conducted radio frequency interference Test method IEC 61000-4-6:2004: Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields. Severity and procedure Frequency range : 150 kHz - 80 MHz Amplitude : 0.15 - 80 MHz Modulation : 80 % AM, 400 Hz sine wave Sweep rate : 0.15 - 80 MHz : : 10 Vrms 1.5 × 10−3 decades/s The test objects are supplied with power via a coupling / decoupling network. The test signal is coupled to the power lines and signal lines via coupling networks. The coupling impedance is 150 Ω. HFR/lko DANAK-1910203 DELTA-A505341 Page 20 of 54 The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure. Results No malfunction was observed during the exposure, and the function of the test objects was OK after the exposure. Performance criterion: A. 4.14 Fast transients (burst) Test method IEC 61000-4-4:2004: Testing and measurement techniques - Section 4: Electrical fast transient / burst immunity test. Severity and procedure Amplitude : : 2 kV on power lines 1 kV on signal lines Pulse rise time : 5 ns Pulse duration : 50 ns Generator impedance : 50 Ω Repetition rate : 5 kHz Burst duration : 15 ms Burst period time : 300 ms The test objects are supplied with power via a transient coupling network. The test signal is successively coupled to each power line and protective earth with reference to the ground plane. The test signal is injected on the signal lines using a capacitive coupling clamp. The clamp is successively used on selected signal cables. The test signal is injected on the power lines for 5 minutes, using each coupling mode and each polarity, and then on the signal lines for 5 minutes using each polarity. The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure and a functional test is performed after the exposure. HFR/lko DANAK-1910203 DELTA-A505341 Page 21 of 54 Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure. Performance criterion: B. 4.15 Slow transients (surge) Test method IEC 61000-4-5:2005: Testing and measurement techniques - Surge immunity test. Severity and procedure Amplitude power ports : 1 kV line-to-earth, 0.5 kV line-to-line Voltage rise time : 1.2 µs (open circuit) Voltage decay time : 50 µs (open circuit) The impedance of the test generator is 2 Ω for line-to-line coupling and 12 Ω for line-toearth coupling. The test objects are energised and in normal operational mode during the exposure. The test objects are observed during the exposure, and a functional test is performed after the exposure. Results No malfunction was observed during the exposure and the function of the test objects was OK after the exposure. Performance criterion: B. 4.16 Radiated emissions Test methods CISPR 16-1:1999: Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus. CISPR 16-2:2002: Specification for radio disturbance and immunity measuring apparatus and methods. Part 2: Methods of measurement of disturbances and immunity. HFR/lko DANAK-1910203 DELTA-A505341 Page 22 of 54 Severity and procedure General power distribution zone. Frequency range : 0.15 - 2000 MHz Limits (quasi-peak) : 0.15 - 30 MHz 30 - 100 MHz 100 - 2000 MHz 156 - 165 MHz : : : : 80 - 50 dBμV/m 60 - 54 dBμV/m 54 dBμV/m, except for 24 dBμV/m The electric field is measured with antennas at a distance of 3 m. The measuring bandwidth is 200 Hz in the frequency range 10 kHz - 150 kHz, 9 kHz in the frequency range 150 kHz - 30 MHz and 120 kHz in the frequency range 30 MHz 2000 MHz, except for the frequency range 156 MHz - 165 MHz where the measuring bandwidth is 9 kHz. The test objects are energised and in normal operational mode during the measurement. Results The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in Annex 4. 4.17 Conducted emissions Test methods CISPR 16-1:1999: Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus. CISPR 16-2:2002: Specification for radio disturbance and immunity measuring apparatus and methods. Part 2: Methods of measurement of disturbances and immunity. Severity and procedure General power distribution zone. Frequency range : 0.01 - 30 MHz Limits (quasi-peak) : 0.01 - 0.15 MHz : 0.15 - 0.50 MHz : 0.50 - 30 MHz : 120 - 69 dBμV 79 dBμV 73 dBμV The radio frequency voltage is measured at the power supply terminals of the test object by a receiver through an artificial mains network. HFR/lko DANAK-1910203 DELTA-A505341 Page 23 of 54 The measuring bandwidth is 200 Hz in the frequency range 10 kHz - 150 kHz and 9 kHz in the frequency range 150 kHz - 30 MHz. The test objects are energised and in normal operational mode during the measurement. Results The conducted emissions were within the specified limits. Test record sheets of the conducted emission measurements are enclosed in Annex 3. 4.18 Enclosure protection, IP 2X Test method IEC 60529:2001: Degrees of protection provided by enclosures (IP Code). Severity and procedure The test specimen was subjected to a test corresponding to IEC 60529:2001, table 1, first characteristic numeral 2 (IP 2X): “Protection against access to hazardous parts with a finger”, and thus IEC 60945:2001, clause 12.1: “Protection against access to dangerous voltages”. Results The test objects have adequate protection against access to hazardous parts with a finger, i.e. no openings greater than 12 mm Ø were measured. HFR/lko DANAK-1910203 DELTA-A505341 Page 24 of 54 Annex 1 List of instruments HFR/lko DANAK-1910203 DELTA-A505341 Page 25 of 54 List of instruments NO. Y221A Acc. 91 22617 Acc. 72 22603 22604 22585 22613 22631 22601 22616 EVFGT-19 EVFGT-28 DESCRIPTION EL.DYN SHAKER ACCELEROMETER ACCELEROMETER ACCELEROMETER ACCELEROMETER ACCELEROMETER ACC. PRE-AMP. ACC. PRE-AMP. 4-CHAN. VIBR. CONTROLLER VOLTMETER OSCILLOSCOPE CLIMATIC CHAMBER CLIMATIC CHAMBER MANUFACTURER LING DYNAMICS BRÜEL & KJÆR BRÜEL & KJÆR BRÜEL & KJÆR BRÜEL & KJÆR BRÜEL & KJÆR BRÜEL & KJÆR BRÜEL & KJÆR SIGNALSTAR HEWLETT-PACKARD ISOTECH DELTA DELTA TYPE NO. V875-440 4371 4393 4393 4393 4393 2626 2692 VECTOR U2 34401A ISR620 VKF875-3 VF 10 29223 CURRENT PROBE SINGER 91550-4 29342 REFLECTOMETER COUPLER, 600-4200 MHz ROHDE & SCHWARZ 29410 CURRENT PROBE AMPLIFIER FOR 29707 AND 49035 TEKTRONIX ZPD TM501 & AM503T 29691 0.01 - 20 GHz. SYNTH. SWEEPER HEWLETT-PACKARD 83620A 29694 1-12 GHz. HORN ANTENNA. LOGIMETRICS AN 8200 F 29696 HF CURRENT INJ. CLAMP LUTHI EM 101 29703 LF POWER AMPLIFIER BRÜEL & KJÆR 2708 29781 DIGITAL MULTIMETER W. HPIB HEWLETT-PACKARD 34401A 29800 SUHNER 6810.17.A 29806 RF ATTENUATOR, 50 OHM, 10 dB, DC-12.4 GHz BROADBAND POWER AMPLIFIER, 10 kHz-220 MHz, 75 W AMPLIFIER RESEARCH 75A220 29813 2-LINE CDN NETWORK, IEC 61000-4-6 MEB M2 29815 3-LINE CDN NETWORK, IEC 61000-4-6 MEB 29844 -40 dBc VOLTAGE SAMPLER, DC-100 MHz DELTA EMC DEPT. M3 SAMPLER_VER_ 2 29846 RF GENERATOR, 9 kHz-2.4 GHz MARCONI 2024 29864 CAPACITIVE COUPLING CLAMP DELTA EMC IEC 1000-4-4 29865 CAPACITIVE COUPLING CLAMP DELTA EMC IEC 1000-4-4 29879 DIFFERENTIAL HIGH VOLTAGE PROBE, DC-25 MHz TEKTRONIX P5200 29911 HEWLETT-PACKARD 34401A 29913 DIGITAL MULTIMETER W. HPIB ELECTRICAL FAST TRANSIENT (BURST) GENERATOR EM TEST EFT 500 29914 ELECTRONIC SURGE GENERATOR EM TEST VCS 500 29936 SAMPLING OSCILLOSCOPE, 100 MHz, 500 MS/s TEKTRONIX TDS 340A 29977 RF POWER ATTENUATOR, 50 OHM, 6 dB, 150 W NARDA 769-6 29984 RF POWER AMPLIFIER, 0.8-2.2 GHz, 200W MILMEGA 29994 ESD GENERATOR, AIR AND CONTACT DISCHARGE EM TEST AS0822-200 ESD 30, P18 & P30 49000 ROHDE & SCHWARZ NRVS 49009 SINGLE CHANNEL POWER METER DISPLAY UNIT CABLE#36, 3,25 M, 50 OHM, COAX CABLE, N(STRAIGHT)-7/16, ROOM1 SUHNER RG 214/U 49035 ACTIVE CURRENT PROBE HEAD FOR 29410 TEKTRONIX 49521 SHIELD-LINE CDN NETWORK, IEC 61000-4-6 DELTA EMC DEPT. A6302 SHIELD-LINE CDN 49526 COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST AGILENT 8471D 49527 COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST AGILENT 15 MHz FUNCTION / ARBITRARY WAVE GENERATOR HEWLETT-PACKARD 8471D 49552 HFR/lko 33120A DANAK-1910203 DELTA-A505341 Page 26 of 54 Annex 2 Photos HFR/lko DANAK-1910203 DELTA-A505341 Page 27 of 54 Photo 1. Vibration, resonance search, C6200. Photo 2. Vibration, resonance search, C6250. HFR/lko DANAK-1910203 DELTA-A505341 Page 28 of 54 Photo 3. Vibration, endurance, e.g. Z-axis. Photo 4. Radiated emissions (0.15 - 30 MHz). HFR/lko DANAK-1910203 DELTA-A505341 Page 29 of 54 Photo 5. Radiated emissions (30 - 2000 MHz). Photo 6. Conducted emissions. HFR/lko DANAK-1910203 DELTA-A505341 Page 30 of 54 Photo 7. Radiated radio frequency interference (80 - 1000 MHz). Photo 8. Radiated radio frequency interference (1000 - 2000 MHz). HFR/lko DANAK-1910203 DELTA-A505341 Page 31 of 54 Photo 9. Conducted radio frequency interference. Photo 10. Conducted low frequency interference. HFR/lko DANAK-1910203 DELTA-A505341 Page 32 of 54 Photo 11. Electrostatic discharge. Photo 12. Slow transients (surge). HFR/lko DANAK-1910203 DELTA-A505341 Page 33 of 54 Photo 13. Fast transients (burst). Photo 14. Climatic testing, in test chamber. HFR/lko DANAK-1910203 DELTA-A505341 Page 34 of 54 Photo 15. HFR/lko Climatic testing, test setup. DANAK-1910203 DELTA-A505341 Page 35 of 54 Annex 3 Test record sheets - Conducted emissions HFR/lko DANAK-1910203 DELTA-A505341 Page 36 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Line. Power input: BUSBAR Voltage, 230 VAC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 06 2008-03-28 SCAN TABLE: "CE 0.01-30 PK" Unit: Curve 1: dBµV Detector: MaxPeak Mode: ClearWrite Level [dBµV] 100 80 60 xxxxxxxxxx xxxxxx xxx xxx x xxxxx xxxxxxxxxx x x x xx xxx xxx xxxx xx x 40 20 0 x HFR/lko 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk MES CE 0.01-30 QP QPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 37 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Neutral. Power input: BUSBAR Voltage, 230 VAC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 07 2008-03-28 SCAN TABLE: "CE 0.01-30 PK" Unit: Curve 1: dBµV Detector: MaxPeak Mode: ClearWrite Level [dBµV] 100 80 60 xxxxxxxxx xxxx xxxx xx 40 20 0 x HFR/lko 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk MES CE 0.01-30 QP QPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 38 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Line. Power input: Generator Voltage, 230 VAC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 08 2008-03-28 Level [dBµV] 100 80 60 xxxxxx xxxxxxxxxxx x x xx 40 20 0 x HFR/lko 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk MES CE 0.01-30 QP QPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 39 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Neutral. Power input: Generator Voltage, 230 VAC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 09 2008-03-28 Level [dBµV] 100 80 60 x xxxxxxxxx xxxxxxx x xx xxxxxxxxx xxxx xxxx x xxx xxxx xxx 40 20 0 x HFR/lko 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk MES CE 0.01-30 QP QPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 40 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Pos. Power input: AUX Supply, 24VDC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 10 2008-03-28 Level [dBµV] 100 80 60 40 20 0 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission HFR/lko 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 41 of 54 DELTA Electronics Testing, EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Line: Neg. Power input: AUX Supply, 24VDC EMC - 4 KKJ - A505341 IEC 60945, E10 Sheet 11 2008-03-28 Level [dBµV] 100 80 60 40 20 0 10k 30k 100k 300k Frequency [Hz] MES CE 0.01-30 PK MaxPk LIM CE, IEC 60945, QP Conducted Emission LIM CE, E-10 deck bridge Conducted Emission HFR/lko 1M 2M 4M 10M 30M DANAK-1910203 DELTA-A505341 Page 42 of 54 Annex 4 Test record sheets - Radiated emissions HFR/lko DANAK-1910203 DELTA-A505341 Page 43 of 54 DELTA Electronics Testing EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Ant: Activ loop 0 Deg. Voltage: 24 VDC and 230 VAC EMC - 5 PFN - A505341 E10 & IEC 60945 & IEC 60533 Sheet 04 27-03-2008 / 13:20:40 Level [dBµV/m] 80 70 60 50 40 30 20 10 0 150k 300k 500k 1M 2M Frequency [Hz] MES ME IEC 945 (0 MaxPk LIM ME, IEC60533, QP Magnetic Emission LIM ME, IEC 60945, QP Magnetic Emission LIM ME, E10, QP Magnetic Emission HFR/lko 3M 5M 7M 10M 30M DANAK-1910203 DELTA-A505341 Page 44 of 54 DELTA Electronics Testing EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 & C6250 Selco A/S Ant: Activ loop 90 Deg. Voltage: 24 VDC and 230 VAC EMC - 5 PFN - A505341 E10 & IEC 60945 & IEC 60533 Sheet 05 27-03-2008 / 13:20:40 Level [dBµV/m] 80 70 60 50 40 x 30 20 10 0 150k x HFR/lko 300k 500k 1M 2M Frequency [Hz] MES ME IEC 945 (90 MaxPk MES mfield 0001_fin QP LIM ME, IEC 60945, QP Magnetic Emission LIM ME, E10, QP Magnetic Emission 3M 5M 7M 10M 30M DANAK-1910203 DELTA-A505341 Page 45 of 54 DELTA Electronics Testing EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 and C6250 Selco A/S Ant. 1 m vertical EMC - 5 HEN - A505341 IEC 60945, E10 and IEC 60533 Sheet 12 27-05-2008 Level [dBµV/m] 60 50 x x x x 40 30 20 x x 10 0 30M x 50M 70M 100M 200M Frequency [Hz] 300M 500M 1G MES Maximering_fin QP MES IEC945 1m 30 MaxPk 1 LIM RE, IEC 60945 Radiated Emission MEASUREMENT RESULT: "Maximering_fin QP" 27-05-2008 15:07 Frequency Level MHz dBµV/m 69.600000 160.015000 162.000000 400.050000 500.060000 550.070000 HFR/lko 41.50 15.00 18.00 49.40 49.10 48.00 Transd dB Limit dBµV/m Margin dB Height cm Azimuth deg 8.0 12.7 12.7 18.9 20.8 21.8 54.0 24.0 24.0 54.0 54.0 54.0 12.5 9.0 6.0 4.6 4.9 6.0 124.0 167.0 101.0 124.0 104.0 104.0 18.00 214.00 181.00 318.00 27.00 25.00 Polarisation VERTICAL HORIZONTAL VERTICAL VERTICAL VERTICAL VERTICAL 2G DANAK-1910203 DELTA-A505341 Page 46 of 54 DELTA Electronics Testing EMC Section EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: C6200 and C6250 Selco A/S Ant. 4 m horizontal EMC - 5 HEN - A505341 IEC 60945, E10 and IEC 60533 Sheet 13 27-05-2008 Level [dBµV/m] 60 50 x x x x 40 30 20 x x 10 0 30M x HFR/lko 50M 70M 100M 200M Frequency [Hz] MES IEC945 4m 30 MaxPk 1 MES IEC945 4m 30 MaxPk 3 MES Maximering_fin QP LIM RE, IEC 60945 Radiated Emission 300M 500M 1G 2G DANAK-1910203 DELTA-A505341 Page 47 of 54 Annex 5 Measurement curves - Vibration HFR/lko DANAK-1910203 DELTA-A505341 Page 48 of 54 CH1 100.0 Mea1/Mea5 X: 99.9553 Y : 1.83774 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 10.0 Frequency, Hz SKIB_4_RES start 09:07:13 Curve 1 100.0 test date 09-04-2008 Resonance search, X-axis (max. ampl. fact.), C6200. CH1 100.0 Mea1/Mea5 X: 99.9553 Y : 1.80966 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 10.0 Frequency, Hz SKIB_4_RES start 12:30:27 Curve 2 HFR/lko 100.0 test date 09-04-2008 Resonance search, Y-axis (max. ampl. fact.), C6200. DANAK-1910203 DELTA-A505341 Page 49 of 54 CH1 100.0 Mea1/Mea5 X: 75.4316 Y : 7.80534 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 10.0 Frequency, Hz SKIB_4_RES start 16:09:20 Curve 3 100.0 test date 09-04-2008 Resonance search, Z-axis (max. ampl. fact.), C6200. CH4 100.0 Mea4/Mea5 X: 99.9553 Y : 0.940748 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 SKIB_4_R ES start 09:07:13 10.0 Frequency, Hz Curve 4 HFR/lko test date 09-04-2008 Resonance search, X-axis (max. ampl. fact.), C6250. 100.0 DANAK-1910203 DELTA-A505341 Page 50 of 54 CH4 100.0 Mea4/Mea5 X: 99.9553 Y : 1.67339 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 SKIB_4_R ES start 09:23:51 10.0 Frequency, Hz Curve 5 100.0 test date 09-04-2008 Resonance search, Y-axis (max. ampl. fact.), C6250. CH4 100.0 Mea4/Mea5 X: 99.9553 Y : 2.71566 LogMag, Ratio 10.0 1.0 100.0m 10.0m 2.0 SKIB_4_R ES start 16:09:20 10.0 Frequency, Hz Curve 6 HFR/lko test date 09-04-2008 Resonance search, Z-axis (max. ampl. fact.), C6250. 100.0 DANAK-1910203 DELTA-A505341 Page 51 of 54 10.0 1.0 LogMag, g²/Hz 100.0m 10.0m 1.0m 100.0u RMS: 3.94583 10.0u 1.0u 2.0 10.0 100.0 Frequency, SKBDNV4GRMS start 09:36:13 test date 09-04-2008Hz Curve 7 Endurance vibration, X-axis, 4 g rms. 10.0 1.0 LogMag, g²/Hz 100.0m 10.0m 1.0m 100.0u RMS: 3.9663 10.0u 1.0u 2.0 10.0 Frequency, SKBDNV4GRMS start 12:41:53 test date 09-04-2008Hz Curve 8 HFR/lko Endurance vibration, Y-axis, 4 g rms. 100.0 DANAK-1910203 DELTA-A505341 Page 52 of 54 10.0 1.0 LogMag, g²/Hz 100.0m 10.0m 1.0m 100.0u RMS: 3.9679 10.0u 1.0u 2.0 10.0 Frequency, SKBDNV4GRMS start 16:25:01 test date 09-04-2008Hz Curve 9 HFR/lko Endurance vibration, Z-axis, 4 g rms. 100.0 DANAK-1910203 DELTA-A505341 Page 53 of 54 Annex 6 Functional test procedure (from Client) (This annex is informative and not part of the accredited report) HFR/lko DANAK-1910203 DELTA-A505341 Page 54 of 54 C6200 Test description 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. HFR/lko Attach 9VDC batteries to the 3 wire’s ALARM, PROT TRIP and PROGRAMMABLE OUTPUTS Attach 24VDC to AUX SUPPLY on C6200 and see AUX SUPPLY led light up Attach CANBUS connection between C6200 and S6500 Attach 24VDC to S6500 AUX module, after a few seconds it will show the BUS and GEN Voltage on the display. Attach C6250, after a few seconds it will show data on the display Attach 220VAC to GENERATOR VOLTAGE and BUSBAR VOLTAGE and see the GENERATOR VOLTAGE and BUSBAR VOLTAGE led’s light up, and see 220VAC in the display’s of the S6500 and the C6250 The green SYNC led on C6200 will now light up Bridge C/B and see the C/B led on the C6200 and the C/B CLOSED led on the S6500 light up Bridge PROGRAMMABLE INPUTS and see led 1 on PROGRAMMABLE INPUTS and PROGRAMMABLE OUTPUTS light up. Attach a voltmeter on PAR LINES and measure 5VDC Attach a voltmeter on ANA OUT and measure 5VDC Attach a voltmeter on GOV CONTROL and measure 5VDC Attach a voltmeter on AVR CONTROL and measure 500HZ with a duty cycle at 50% Bridge ANA IN Attach the RS485 cable from laptop to RS485 on the C6200 Run the C6200_RS485 test on the laptop push the start button on the C6200_RS485 test program on the laptop The unit are now ready for test It is consider an error if any of the led’s on the C6200 alters its state