Type approval testing of Sigma S6610, T4000 and T4400

We help ideas meet the real world
DELTA Test Report
DANAK
TEST Reg. no. 19
Type approval testing of Sigma S6610, T4000 and T4400
Performed for Selco A/S
DANAK-198449
Project no.: A503163-1
Page 1 of 75
including 6 annexes
28 July 2006
DELTA
Danish Electronics,
Light & Acoustics
Venlighedsvej 4
2970 Hørsholm
Denmark
Tel. (+45) 72 19 40 00
Fax (+45) 72 19 40 01
www.delta.dk
This report is issued under the rules of DANAK (Danish Accreditation).
Further information about DANAK can be found at www.danak.dk.
The report must not be reproduced, except in full, without the written approval of DELTA.
Version l
DANAK-198449
DELTA-A503163-1
Page 2 of 75
Title
Type approval testing of Sigma S6610, T4000 and T4400
Test objects
SIGMA S6610, Power Management Module
T4000, Auto Synchronizer
T4400. Load Sharer
Detailed information is given in Section 2.1 to 2.3.
The test objects were received on 20 September 2005.
Report no.
DANAK-198449
Project no.
A503163-1
Test period
20 September 2005 to 24 March 2006
Client
Selco A/S
Betonvej 10
4000 Roskilde
Denmark
Manufacturer
Selco A/S
Specifications
IACS E10: Rev. 4 May 2004. Test Specification for Type
Approval. ”Test specification applicable, but not confined, to all equipment used for: - Control, protection and
safety; - internal communication”.
IEC 60533: Second edition, 1999. “Electrical and electronic installations in ships - Electromagnetic compatibility”.
IEC 60945: Fourth edition, 2002 “Maritime navigation
and radio communication equipment and systems - General requirements - Methods of testing and required test
results”.
EN 61000-6-2:2001. “Electromagnetic compatibility
(EMC) - Part 6-2: Generic standards - Immunity for industrial environments”.
EN 61000-6-4:2001. “Electromagnetic compatibility
(EMC) – Part 6-4: Generic standards - Emission standard
for industrial environments”.
EN 50263:1999. "Electromagnetic compatibility
(EMC) – Product standard for measuring relays and protection equipment”
Results
NE/jh
No malfunctions were detected. The criteria for compliance are listed in Section 3.2.
DANAK-198449
DELTA-A503163-1
Page 3 of 75
Test personnel
Henrik Egeberg Nielsen
Poul Terkelsen
Bjørn Larsen
Olling Truelsen
Danielle Coman
Niels Engel
Date
28 July 2006
Project manager
Niels Engel, Project manager
DELTA
Responsible
Bjørn Baruël Petersen, M.Sc.E.E.
DELTA
NE/jh
DANAK-198449
DELTA-A503163-1
Page 4 of 75
Table of contents
Page
1.
1.1
1.2
Summary of test
Test requirements
Conclusion
6
6
7
2.
2.1
2.2
2.3
2.4
2.5
2.6
Test specimen(s)
Test object Sigma S6610, Power Management Module
Test object T4000, Auto-Synchroniser
Test object T4400, Load Sharer
AUX equipment: Sigma S6000 IO/P module
AUX equipment: Notebook
AUX equipment: Multimeter
8
8
8
8
8
8
9
3.
3.1
3.2
3.3
3.4
General test conditions
Test set-up
Criteria for compliance
Functional test
Standard environment
10
10
10
11
11
4.
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.8.1
4.8.2
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
4.19
4.20
4.21
4.22
4.23
Test and results
Visual inspection and performance test
Conducted emissions (CISPR 16-1)
Conducted emission (CISPR 11)
Radiated emissions (CISPR 16-1)
Radiated emission (CISPR 11)
Insulation resistance
High voltage
Vibration
Resonance search
Endurance vibration
Power supply variations (permanent)
Power supply variations (transient)
Power supply failure
Conducted low frequency interference
Conducted radio frequency interference
Radiated radio frequency interference
Surge voltage
Electrostatic discharge
Fast transients (burst)
Dry heat
Low temperature (cold)
Damp heat, cyclic
Reverse polarity
Enclosure protection, IP2X
1 MHz burst
12
12
13
14
15
16
17
18
19
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
33
34
NE/jh
DANAK-198449
DELTA-A503163-1
Page 5 of 75
NE/jh
Annex 1 List of instruments
35
Annex 2 Photos
38
Annex 3 Test record sheets - Conducted emissions
48
Annex 4 Test record sheets - Radiated emissions
57
Annex 5 Measurement curves - Vibration
66
Annex 6 Test set-up and functional test procedure (from Selco A/S) (This
annex is informative and not part of the accredited report)
69
DANAK-198449
DELTA-A503163-1
Page 6 of 75
1.
Summary of test
1.1
Test requirements
Test
Visual inspection & Performance test
Power supply variations
Power supply failure
Conducted low frequency interference
Conducted radio frequency interference
Electrical fast transients (burst)
Electrostatic discharges
Radiated radio frequency interference
Surge transients
Conducted emissions
Radiated emissions
Vibration (resonance search)
Vibration (endurance - random)
Insulation resistance
Dry heat
Low temperature (cold)
Damp heat (cyclic)
High voltage
Reverse polarity
Enclosure protection, IP 2X
1 MHz burst
NE/jh
Test method
IACS E10:2004
IEC 60945:2002 / IACS E10:2004
IEC 60945:2002 / IACS E10:2004
IEC 60533:1999 / IEC 61000-4-16:1998
EN 61000-4-6:2001
EN 61000-4-4:1995
EN 61000-4-2:2001
EN 61000-4-3:2002
EN 61000-4-5:2001
CISPR 16-1:1999 / IEC 60945:2002
CISPR 16-1:1999 / CISPR 11:1999
IEC 60068-2-6:1995
IEC 60068-2-64:1993
IACS E10:2004
IEC 60068-2-2:1974 + Amendments
IEC 60068-2-1:1990 + Amendments
IEC 60068-2-30 1980 + Amendments
IACS E10:2004
IEC 60945:2002
IEC 60529:2001 / IEC 60945:2002
IEC 60255-22-1:1988
DANAK-198449
DELTA-A503163-1
Page 7 of 75
1.2
Conclusion
The test objects mentioned in this report meet the relevant requirements of the standards
stated below.
•
IACS E10:2004
•
IEC 60533:1999
•
IEC 60945:2002
•
EN 61000-6-2:2001
•
EN 61000-6-4:2001
•
EN 60263:1999
The test results relate only to the specimens tested.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 8 of 75
2.
Test specimen(s)
2.1
Test object Sigma S6610, Power Management Module
Manufacturer
Type
Serial no.
Supply voltage
Operational mode
2.2
Test object T4000, Auto-Synchroniser
Manufacturer
Type
Serial no.
Supply voltage
Operational mode
2.3
Selco A/S
S6000.0010
372034
S6610 CAN bus comm.
AUX equipment: Notebook
Manufacturer
Model
Serial no.
Operational mode
NE/jh
Selco A/S
T4400-33
379852
230 VAC
Normal operational mode
AUX equipment: Sigma S6000 IO/P module
Manufacturer
Model
Serial no.
Operational mode
2.5
Selco A/S
T4000-02
360455
230 VAC
Normal operational mode
Test object T4400, Load Sharer
Manufacturer
Type
Serial no.
Supply voltage
Operational mode
2.4
Selco A/S
S6610
24 VDC
Normal operational mode
IBM
T23
Selco no: lapdkco003
S6610 RS485 comm. using monitoring software “Modbus OPC
Configurator” version 3.0.2.1
DANAK-198449
DELTA-A503163-1
Page 9 of 75
2.6
AUX equipment: Multimeter
Manufacturer
Model
Serial no.
Operational mode
NE/jh
Fluke
Fluke 37
04422264
S6610, T4000, T4400 analogue output signal monitoring
DANAK-198449
DELTA-A503163-1
Page 10 of 75
3.
General test conditions
3.1
Test set-up
A drawing of the test set-up is enclosed in Annex 6.
3.2
Criteria for compliance
No change of the actual operational states of the test specimens is allowed. However,
temporary change is allowed during the power supply failure test.
The following acceptance criteria for compliance regarding accuracy of analogue parameters were in force:
•
"Analog input": ±0.5 mA
•
"Analog input": ±0.5 V
•
"Analog output": ±0.5 mA
•
"Analog output": ±0.5 V
In addition, the following generic acceptance criteria for compliance were in force during the EMC immunity testing:
NE/jh
•
Performance Criterion A: (For continuous phenomena) : The EUT shall continue
to operate as intended during and after the test. No degradation of performance or
loss of function is allowed as defined in relevant equipment standard and the technical specification published by the manufacturer.
•
Performance Criterion B: (For transient phenomena): The EUT shall continue to
operate as intended after the tests. No degradation of performance or loss of function is allowed as defined in the technical specification published by the manufacturer. During the test, degradation or loss of function or performance which is selfrecoverable is, however, allowed but no change of actual operating state or stored
data is allowed.
•
Performance Criterion C: Temporary degradation or loss of function or performance is allowed during and after the test, provided the function is self-recoverable,
or can be restored by the operation of the controls as defined in the relevant
equipment standard and in the technical specification published by the manufacturer.
DANAK-198449
DELTA-A503163-1
Page 11 of 75
3.3
Functional test
A functional test was performed before, during (if specified) and after each test. The
functional test was carried out in accordance with the functional test procedure provided
by the customer.
The functional test procedure is given in Annex 6.
3.4
Standard environment
Normal environmental condition:
NE/jh
Temperature
:
15°C to 35°C
Humidity
:
25 %RH to 75 %RH
Air pressure
:
86 kPa to 106 kPa (860 mbar to 1060 mbar)
Power supply voltage
:
Unom. ±3%
DANAK-198449
DELTA-A503163-1
Page 12 of 75
4.
Test and results
4.1
Visual inspection and performance test
Test method
IACS E10, Test No. 1 and 2.
Procedure
The conformance to drawings and the functional performance are demonstrated to the
society surveyors present at DELTA during the type approval testing.
The functional test is also demonstrated.
Results
The conformance to drawings and the functional performance, including the functional
test procedure, are demonstrated to the society surveyors after completion of the type
approval testing, if requested.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 13 of 75
4.2
Conducted emissions (CISPR 16-1)
Test method
CISPR 16-1 (1999-10): Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus.
Severity and procedure
(IACS E10:2004 & IEC 60533:1999 - General power distribution zone)
Frequency range
:
0.01 - 30 MHz
Limits (quasi-peak)
:
0.01 - 0.15 MHz :
0.15 - 0.50 MHz :
0.50 - 30 MHz :
120 - 69 dBμV
79 dBμV
73 dBμV
(IEC 60945:2002, IEC 60533:1999 and IACS E10:2004 - Bridge and Deck Zone)
Frequency range
:
0.01 - 30 MHz
Limits (quasi-peak)
:
0.01 - 0.15 MHz :
0.15 - 0.35 MHz :
0.35 - 30 MHz :
96 - 50 dBμV
60 - 50 dBμV
50 dBμV
The radio frequency voltage is measured at the power supply terminals of the test specimen, by a receiver through an artificial mains network.
The test specimen is energised and in normal operational mode during the measurement.
Results
The conducted emissions were within the specified limits. Test record sheets of the conducted emission measurements are enclosed in Annex 3.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 14 of 75
4.3
Conducted emission (CISPR 11)
Test method
CISPR 11 (1999-08): Industrial, scientific and medical (ISM) radio-frequency equipment
- Electromagnetic disturbance characteristics - Limits and methods of measurement.
Severity and procedure
Frequency range
:
0.15 - 30 MHz
Limits (quasi-peak)
:
0.15 - 0.50 MHz :
:
0.50 - 30 MHz :
:
79 dBμV quasi-peak
66 dBμV average
73 dBμV quasi-peak
60 dBμV average
The radio frequency voltage is measured at the power supply terminals of the test specimen, by a receiver through an artificial mains network.
The test specimen is energised and in normal operational mode during the measurement.
Results
The conducted emissions were within the specified limits. Test record sheets of the conducted emission measurements are enclosed in Annex 3.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 15 of 75
4.4
Radiated emissions (CISPR 16-1)
Test method
CISPR 16-1 (1999-10): Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus.
Severity and procedure
Severity and procedure
(IACS E10:2004 and IEC 60533:1999 - General power distribution zone)
Frequency range
:
0.15 - 2000 MHz
Limits (quasi-peak)
:
0.15 - 30 MHz
30 - 100 MHz
100 - 2000 MHz
156 - 165 MHz
:
:
:
:
80 - 50 dBμV/m
60 - 54 dBμV/m
54 dBμV/m, except for
24 dBμV/m
:
:
:
:
80 - 52 dBμV/m
50 - 34 dBμV/m
54 dBμV/m, except for
24 dBμV/m
(IACS E10:2004 - Bridge and Deck Zone)
Frequency range
:
0.15 - 2000 MHz
Limits (quasi-peak)
:
0.15 - 0.3 MHz
0.3 - 30 MHz
30 - 2000 MHz
156 - 165 MHz
(IEC 60945:2002 and IEC 60533:1999 - Bridge and Deck Zone)
Frequency range
:
0.15 - 2000 MHz
Limits (quasi-peak)
:
0.15 - 0.3 MHz
0.3 - 30 MHz
30 - 2000 MHz
156 - 165 MHz
:
:
:
:
80 - 52 dBμV/m
52 - 34 dBμV/m
54 dBμV/m, except for
24 dBμV/m
The electric field is measured with antennas at a distance of 3 m.
The test specimens are energised and in normal operational mode during the measurement.
Results
The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in Annex 4.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 16 of 75
4.5
Radiated emission (CISPR 11)
Test method
CISPR 11 (1999-08): Industrial, scientific and medical (ISM) radio-frequency equipment
- Electromagnetic disturbance characteristics - Limits and methods of measurement.
Severity and procedure
Frequency range
:
30 - 1000 MHz
Limits (quasi-peak)
:
30 - 230 MHz
:
230 - 1000 MHz :
40 dBμV/m
47 dBμV/m
The electric field is measured with antennas at a distance of 10 m.
The test specimens are energised and in normal operational mode during the measurement
Results
The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in Annex 4.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 17 of 75
4.6
Insulation resistance
Test method
IACS E10, Test No. 9.
Procedure
The insulation resistance is measured between shorted supply terminals and earth with
50 VDC for 24 VDC power ports and 500 VDC for 230 VAC power ports. The insulation resistance is to be above 100 MΩ (AC power ports) and 10 MΩ (DC power ports)
initially, and above 10 MΩ (AC power ports) and 1 MΩ (DC power ports) after the low
temperature and the damp heat exposures..
Results
Cable
designation
DC power ports
of all externally
powered test
objects
AC power ports
of all externally
powered test
objects
NE/jh
Test voltage
Duration
Insulation
resistance
[Vrms]
[sec]
[MΩ]
Initial
50 VDC
60 sec.
>100 MΩ
After Low
temperature test
50 VDC
60 sec.
>100 MΩ
After Damp
heat test
50 VDC
60 sec.
>10 MΩ
Initial
500 VDC
60 sec.
>1000 MΩ
After Low
temperature test
500 VDC
60 sec.
>1000 MΩ
After Damp
heat test
500 VDC
60 sec.
>100 MΩ
Test condition
DANAK-198449
DELTA-A503163-1
Page 18 of 75
4.7
High voltage
Test method
IACS E10, Test No. 10.
Procedure
550 VAC, 50 Hz is applied between shorted supply terminals and earth for 1 minute for
the 24 VDC supply line.
1500 VAC, 50 Hz is applied between shorted supply terminals and earth for 1 minute for
the 230 VAC supply line.
No flashover, breakdown, etc. is acceptable.
Results
This test was omitted due to the presence of components for EMC protection.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 19 of 75
4.8
Vibration
4.8.1
Resonance search
Test method
IEC 60068-2-6 (1995), Test Fc: Vibration (sinusoidal).
Severity and procedure
Frequency range
:
2 - 100 Hz
Frequency/amplitude
:
2 - 25 Hz :
25 - 100 Hz :
Sweep rate
:
Max. 1 octave/min.
Number of axes
:
3 mutually perpendicular
±1.6 mm
±4.0 g
The test specimens are de-energised during the exposure.
During the resonance search, the resonance frequencies are determined by means of
stroboscopic light with slow motion facility and accelerometer measurements of the amplification factors (Q).
Resonance frequencies with an amplification factor above 2 are recorded.
Results
No amplification factors above 2 were recorded.
Place of measurement
Axis
Frequency
Amplification factor
T4000
X, Y and Z
2 - 100 Hz
<2
T4400
X, Y and Z
2 - 100 Hz
<2
S6610 PM
X, Y and Z
2 - 100 Hz
<2
Measurement curves of the maximum amplification factors and resonance frequencies
are enclosed in Annex 5.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 20 of 75
4.8.2
Endurance vibration
The sinusoidal vibration test according to IACS E10 and IEC 60945 is replaced by random vibration test according to "Environmental test specification for instrumentation and
automation equipment" No. 2.4, issued April 2001 by DNV.
This random vibration test will cover the requirements of the sinusoidal vibration test
according to IACS E10 and IEC 60945.
Test method
IEC 60068-2-64 (1993), Test Fh: Vibration, broadband random (digital control).
Severity and procedure
Frequency range
:
2 - 100 Hz
Acceleration spectral
:
2 - 25 Hz
Density
:
25 - 100 Hz
Total RMS level
:
4.0 g
Duration
:
150 minutes per axis
Number of axes
:
3 mutually perpendicular
:
+12 dB/octave
:
0.2 g2/Hz
The test specimens are energised and in normal operational mode during the exposures.
A functional test is performed after the exposure in each axis.
A visual inspection is performed after the exposure.
Results
No malfunction was observed during the exposure and the function of the test specimens
was OK after the exposure in each axis.
No damage was observed after the exposures.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 21 of 75
4.9
Power supply variations (permanent)
Test method
IACS E10, Test No. 4
IEC 60945, Section 5.2.2.
Procedure (230 VAC supplied)
Unom.
=
Nominal supply voltage
=
230 VAC
fnom.
=
Nominal supply frequency
=
50 Hz
Exposures, each with a duration of 15 minutes, are performed at the following supply
voltages and frequencies:
U
=
Unom. + 10%
=
253 VAC
U
=
Unom. - 10%
=
207 VAC
f
=
fnom. + 5%
=
52.5 Hz
f
=
fnom. - 5%
=
47.5 Hz
Procedure (24 VDC supplied)
Unom. =
Nominal supply voltage
=
24 VDC
Exposures, each with a duration of 15 minutes, are performed at the following supply
voltages:
U1
=
Un+30%
=
31.2 VDC
U2
=
Un-25%
=
18.0 VDC
The test specimens are observed during the exposures, and a functional test is performed
at the end of each exposure.
An additional power supply variations test is performed as part of the functional test during the low temperature and the dry heat test profiles.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
Performance criterion: A.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 22 of 75
4.10
Power supply variations (transient)
Test method
IACS E10, Test No. 4
IEC 60945, Section 5.2.2
Procedure
Unom.
=
Nominal supply voltage
=
230 VAC
fnom.
=
Nominal supply frequency
=
50 Hz
Ten exposures, 1/min, are carried out at each of the following combinations:
(230 VAC supplied)
•
Unom. + 20%
fnom. + 10%
=
=
276 VAC Duration
55 Hz Duration
=
=
1.5 s
5.0 s
•
Unom. - 20%
fnom. - 10%
=
=
184 VAC Duration
45 Hz Duration
=
=
1.5 s
5.0 s
The test specimen is observed during the exposures, and a functional test is performed at
the end of each combination.
Results
No malfunction was observed during the exposure, and the function of the test specimen
was OK after the exposure.
Performance criterion: A
NE/jh
DANAK-198449
DELTA-A503163-1
Page 23 of 75
4.11
Power supply failure
Test method
IACS E10, Test No. 3
IEC 60945, Section 7.4.
Procedure
The power supply is interrupted 3 times within 5 minutes with a break time of 60
seconds.
Normal power-up procedure is to be obtained after each power break.
Results
No malfunction was observed during the exposure, and the function of the test specimen
was OK after each exposure.
Performance criterion: C.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 24 of 75
4.12
Conducted low frequency interference
Test method
IEC 61000-4-16 (1998-01): Test for immunity to conducted, common mode disturbances
in the frequency range 0 Hz to 150 kHz.
Severity and procedure
Frequency range
:
0.05 - 10 kHz
Amplitude (AC-supplied)
:
50 Hz to 15th harmonic :10% of Unom.
15th to 100th harmonic :10%-1% of Unom.
100th to 200th harmonic : 1% of Unom.
Amplitude (DC-supplied)
:
0.05 - 10 kHz
Maximum applied power
:
2.0 W
: 10% of Unom. min.3 Vrms
The impedance of the test generator is less than 1 Ω.
The test signal is superimposed on the power supply lines via a coupling transformer.
The test specimen is energised and in normal operational mode during the exposure. The
test specimen is observed during the exposure, and a functional test is performed after
the exposure
Results
No malfunction was observed during the exposure, and the function of the test specimen
was OK after the exposure.
Performance criterion: A.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 25 of 75
4.13
Conducted radio frequency interference
Test method
EN 61000-4-6 (2001-04), Ed. 1.1: Testing and measurement techniques - Immunity to
conducted disturbances, induced by radio-frequency fields.
Severity and procedure
Frequency range :
150 kHz - 80 MHz
Amplitude
:
0.15 - 80 MHz
Modulation
:
80% AM, 400 Hz sine wave
80% AM, 1 kHz sine wave
:
10 Vrms
The test specimen is supplied with power via a coupling/decoupling network.
The test signal is coupled to the power lines and signal lines via coupling networks. The
coupling impedance is 150 Ω.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure, and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimen
was OK after the exposure.
Performance criterion: A.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 26 of 75
4.14
Radiated radio frequency interference
Test method
EN 61000-4-3 (2002-03): Testing and measurement techniques - Radiated, radiofrequency, electromagnetic field immunity test.
Severity and procedure
Frequency range :
80 - 2000 MHz
Field strength
:
10 V/m
Modulation
:
80% AM, 400 Hz sine wave
80% AM, 1 kHz sine wave
The test is performed in a semi-anechoic room. The field is generated using linearly polarised broadband antennas.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure, and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
Performance criterion: A.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 27 of 75
4.15
Surge voltage
Test method
EN 61000-4-5 (2001-04) Ed. 1.1: Testing and measurement techniques - Surge immunity test.
Severity and procedure
Amplitude AC power ports
:
1 & 2 kV line-to-earth, 0.5 & 1 kV line-to-line
Amplitude DC power ports
:
1 kV line-to-earth, 0.5 kV line-to-line
Amplitude signal lines
:
1 kV line-to-earth (lines >30 m)
Voltage rise time
:
1.2 µs (open circuit)
Voltage decay time
:
50 µs (open circuit)
The impedance of the test generator is 2 Ω for line-to-line coupling and 12 Ω for line-toearth coupling.
The impedance of the test generator is 2 Ω for exposures on shielded signal lines.
The test specimens are supplied with power via a transient coupling network.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure, and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
Performance criterion: B.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 28 of 75
4.16
Electrostatic discharge
Test method
EN 61000-4-2 (2001-04) Ed. 1.2: Testing and measurement techniques - Electrostatic
discharge immunity test.
Severity and procedure
Air discharge
:
2, 4 and 8 kV
Contact discharge
:
2, 4 and 6 kV
Energy storage capacitance
:
150 pF
Discharge resistance
:
330 Ω
Polarity
:
+ and -
Number of discharges
:
10 per polarity at each test point
The discharges are applied only to such points and surfaces of the test specimen, which
are accessible to personnel during normal use.
Contact discharges are applied to conductive surfaces and coupling planes, and air discharges are applied to insulating surfaces.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure, and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
Performance criterion: B.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 29 of 75
4.17
Fast transients (burst)
Test method
EN 61000-4-4 (1995-01): Testing and measurement techniques - Section 4: Electrical
fast transient/burst immunity test, Amendment 1 (2000-11), Amendment 2 (2001-07).
Severity and procedure
Amplitude
:
:
2 kV on power lines
2 kV on earth port
1 kV on signal lines
Pulse rise time
:
5 ns
Pulse duration
:
50 ns
Generator impedance
:
50 Ω
Repetition rate
:
5 kHz
Burst duration
:
15 ms
Burst period time
:
300 ms
The test specimens are supplied with power via a transient coupling network. The test
signal is successively coupled to each power line and protective earth with reference to
the ground plane.
The test signal is injected on the signal lines using a capacitive coupling clamp. The
clamp is successively used on selected signal cables.
The test signal is injected on the power lines for 5 minutes, using each coupling mode
and each polarity, and then on the signal lines for 5 minutes using each polarity.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
Performance criterion: B.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 30 of 75
4.18
Dry heat
Test method
IEC 60068-2-2 (1974), Test Bd: Dry heat for heat-dissipating specimen with gradual
change of temperature, Amendment 1 (1993), Amendment 2 (1994).
Severity and procedure
The following two exposures are performed:
1. Temperature
Duration
Humidity
: 55°C
: 16 hours
: Below 50 %RH
2. Temperature
Duration
Humidity
: 70°C
: 16 hours
: Below 50 %RH
The test specimens are energised and in normal operating condition during the exposure.
During the last hour of the exposure, a functional test is performed.
After recovery the functional test is repeated in standard environment.
Results
No malfunction was observed during the exposure and the function of the test specimen
was OK during the last hour of the exposure and after recovery.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 31 of 75
4.19
Low temperature (cold)
Test method
IEC 60068-2-1 (1990), Test Ad: Cold for heat-dissipating specimen with gradual change
of temperature, Amendment 1 (1993), Amendment 2 (1994).
Severity and procedure
Temperature
:
-15°C
Duration
:
16 hours
The test specimens are de-energised during the exposure. However, during the last hour
of the exposure the test specimen is energised and a functional test is performed. After
recovery, a functional test and an insulation resistance test are performed in standard environment.
Results
No malfunction was observed during the exposure and the function of the test specimen
was OK during the last hour of the exposure and after recovery.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 32 of 75
4.20
Damp heat, cyclic
Test method
IEC 60068-2-30 (1980), Test Db: Damp heat cyclic (12 + 12 hours' cycle), Variant 1,
Amendment 1 (1985).
Severity and procedure
Lower temperature
:
25°C
Humidity at lower temperature
:
>95 %RH
Upper temperature
:
55°C
Humidity at upper temperature
:
93 %RH
Number of cycles
:
2
During the first cycle, the test specimens are energised and in normal operational mode.
A functional test is performed during the first 2 hours of the 55°C phase.
During the second cycle, the test specimens are de-energised. However, during the last 2
hours of the second 55°C phase, the test specimens are energised and a functional test is
performed.
After recovery, the test specimens are energised and a functional test and an insulation
resistance test are performed in standard environment.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK during the first and second cycle at 55°C and 93 %RH, and after recovery.
No corrosion attack was observed after the exposure.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 33 of 75
4.21
Reverse polarity
Test method
IEC 60945:2002, Section 5.2.3.
Procedure (DC supplied)
The test specimens are subjected to an input from a power supply of reversed polarity for
a period of 5 minutes.
After completion of the test and reset of the protection of the test specimens, if required,
the power supply shall be connected normally and a performance check shall be carried
out.
Results
The test specimens are equipped with reverse polarity protection diodes. Consequently,
no current consumption or malfunction of the test specimens occurs during exposure.
During and after completion of the test, the function of the test specimens was OK.
4.22
Enclosure protection, IP2X
Test method
IEC 60529 (2001-02): Degrees of protection provided by enclosures (IP Code).
Severity and procedure
The test specimen is subjected to a test corresponding to IEC 60529:2001, table 1, first
characteristic numeral 2 (IP2X): “Protection against access to hazardous parts with a finger, and thus IEC 60945:2001, clause 12.1: “Protection against access to dangerous voltages.
Results
The test specimens have adequate protection against access to hazardous parts with a finger, i.e. no openings greater than 12 mm Ø were measured.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 34 of 75
4.23
1 MHz burst
Specifications
IEC 60255-22-1 (1988):Electrical disturbance tests for measuring relays and protection
equipment. Part 1: 1 MHz burst disturbance tests.
Severity and procedure
Amplitude
:
1 kV DM on power ports and I/O ports
2.5 kV CM on power ports and I/O ports
1 kV CM on communication ports
Frequency
:
1 MHz
Source impedance
.
200 Ohm
Rise time
:
75 ns
Repetition frequency
:
400 Hz
The test specimen is energised and in normal operational mode during the exposure. The
test specimen is observed during the exposure and a functional test is performed after the
exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 35 of 75
Annex 1
List of instruments
NE/jh
DANAK-198449
DELTA-A503163-1
Page 36 of 75
List of instruments
NO.
DESCRIPTION
MANUFACTURER
TYPE NO.
22631
VIBRATION CONTROLLER
SIGNAL STAR VECTOR
U2 Sys 5144
ACC. 91
ACCELEROMETER
BRUEL & KJÆR
4371
ACC. 93
ACCELEROMETER
BRUEL & KJÆR
4371
ACC.71A ACCELEROMETER
BRUEL & KJÆR
4393
ACC. 72
ACCELEROMETER
BRUEL & KJÆR
4393
22630
ACCELEROMETER PREAMPLIFIER
BRUEL & KJÆR
2692
22589
ACCELEROMETER PREAMPLIFIER
BRUEL & KJÆR
2626
22601
ELECTRONIC VOLTMETER
HEWLETT-PACKARD
34401A
22591
OSCILLOSCOPE
KENWOOD
CS-1025
Y221
ELECTRODYNAMIC SHAKER
LING DYNAMIC SYS.
V 875-440T
U2501
SWITCHING POWER AMPLIFIER
LING DYNAMIC SYS.
SPA 50/30KCE
DELTA
VKF10
EVFGT-27 CLIMATIC TEST CHAMBER
EVFGT-28 CLIMATIC TEST CHAMBER
DELTA
VF10
29223
CURRENT PROBE
SINGER
91550-4
29342
REFLECTOMETER COUPLER, 600-4200 MHz ROHDE & SCHWARZ
ZPD
29347
RF GENERATOR , 10 kHz-1 GHz
MARCONI
2022
29461
ARTIFICIAL MAINS NETWORK
ROHDE & SCHWARZ
ESH2/Z5
29680
IMPULSE VOLTAGE LIMITER
ROHDE & SCHWARZ
ESH3/Z2
29691
0.01 - 20 GHz. SYNTH. SWEEPER
HEWLETT-PACKARD
83620A
29694
1-12 GHz. HORN ANTENNA.
LOGIMETRICS
AN 8200 F
29703
LF POWER AMPLIFIER
BRUEL & KJÆR
2708
29754
RF POWER ATTENUATOR, 50 OHM, 6 dB,
150 W
NARDA
769-6
29781
DIGITAL MULTIMETER W. HPIB
HEWLETT-PACKARD
34401A
29786
HIGH POWER RF AMPLIFIER, 80-1000 MHz
AMPLIFIER RESEARCH
500W1000M5
29797
BILOG ANTENNA, 30-1000 MHz
CHASE ELECTRICS LTD
CBL 6111A
29815
3-LINE CDN NETWORK,
IEC 61000-4-6
MEB
M3
29749
SHIELD-LINE CDN NETWORK,
IEC 61000-4-6
DELTA EMC DEPT.
SHIELD LINE
CDN
29827
ELECTRONIC SURGE GENERATOR
EM TEST
VCS 500
29832
DIFFERENTIAL HIGH VOLTAGE PROBE,
DC-25 MHz
TEKTRONIX
P5200
29838
ESD GENERATOR, AIR AND CONTACT DIS- KEYTEK
CHARGE
MZ-15EC
29844
-40 dBc VOLTAGE SAMPLER, DC-100 MHz
DELTA EMC DEPT.
SAMPLER
VER. 2
29846
RF GENERATOR, 9 kHz-2.4 GHz
MARCONI
2024
29861
EMI-SOFTWARE Ver. 1.60
ROHDE & SCHWARZ
ES-K1, PART:
1026.6790.02
29865
CAPACITIVE COUPLING CLAMP
DELTA EMC
IEC 1000-4-4
NE/jh
DANAK-198449
DELTA-A503163-1
Page 37 of 75
NO.
DESCRIPTION
MANUFACTURER
TYPE NO.
29866
LF INJECTION TRAFO, 6 x 6 TURNS
KNUD OVERGAARD
14311
29880
CURRENT PROBE AMPLIFIER FOR 29907
AND 29707
TEKTRONIX
AM503B
29884
PULSE / FUNCTION GENERATOR,
50 MHz
WAVETEK
81
29904
BROADBAND POWER AMPLIFIER, 10 kHz250 MHz, 75 W
AMPLIFIER RESEARCH
75A250
29906
15 MHz FUNCTION / ARBITRARY WAVE
GENERATOR
HEWLETT-PACKARD
33120A
29907
ACTIVE CURRENT PROBE HEAD FOR 29880 TEKTRONIX
A6302
29913
ELECTRICAL FAST TRANSIENT (BURST)
GENERATOR
EFT 500
29915
DC COUPLED POWER AMPLIFIER / POWER HEWLETT-PACKARD
SUPPLY
467A
29916
AUTOMATIC TEST RECEIVER, 9 kHz-2.75
GHz
ROHDE & SCHWARZ
ESCS 30
1102.4500.30
29936
SAMPLING OSCILLOSCOPE, 100 MHz, 500
MS/s
TEKTRONIX
TDS 340A
29967
COAX RF DIODE DETECTOR, NEG. OUTPUT, ROOM 5
HEWLETT-PACKARD
8471D
29975
DIGITAL MULTIMETER w. GPIB
HEWLETT-PACKARD
34401A
29984
RF POWER AMPLIFIER, 0.8-2.2 GHz, 200W
MILMEGA
AS0822-200
29985
BILOG ANTENNA 26-2000 MHz
SCHAFFNER/CHASE
6140A
49002
SINGLE CHANNEL POWER METER DISPLAY UNIT
ROHDE & SCHWARZ
NRVS
49003
THERMAL POWER SENSOR, DC-18 GHz
ROHDE & SCHWARZ
NRV-Z51
49024
COAX RF DIODE DETECTOR, NEG. OUTPUT, CS TEST
HEWLETT-PACKARD
8471D
49034
"CABLE#42", 3 M, 50 OHM COAX CABLE, N- CELLFLEX
N (STRAIGHT)
29332
ACTIVE LOOP ANTENNA
ROHDE & SCHWARZ
HFH-Z2
43028
MEGGER
AVO INTERNATIONAL
BM 80
30344
HIGH VOLTAGE APPARATUS
WILLY NIELSEN
W5
NE/jh
EM TEST
DANAK-198449
DELTA-A503163-1
Page 38 of 75
Annex 2
Photos
NE/jh
DANAK-198449
DELTA-A503163-1
Page 39 of 75
Photo 1.
1 MHz burst, e.g T4400.
Photo 2.
Power supply variations & failure, e.g. T4400.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 40 of 75
Photo 3.
Vibration, resonance search, e.g. S6610.
Photo 4.
Vibration, resonance search, e.g. T4000.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 41 of 75
Photo 5.
Vibration, resonance search, e.g. T4400.
Photo 6.
Vibration, endurance.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 42 of 75
Photo 7.
Climatic testing.
Photo 8.
Radiated emissions (0.15 - 30 MHz). 3 m.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 43 of 75
Photo 9.
Radiated emissions (30 - 2000 MHz). 3 m.
Photo 10.
Conducted emissions, e.g. S6610.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 44 of 75
Photo 11.
Conducted radio frequency interference, e.g. S6610.
Photo 12.
Conducted radio frequency interference, e.g. T4000.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 45 of 75
Photo 13.
Conducted low frequency interference, e.g. S6610.
Photo 14.
Fast transients (burst), e.g. T4000.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 46 of 75
Photo 15.
Electrostatic discharge, e.g. T4400.
Photo 16.
Surge, e.g. T4400.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 47 of 75
Photo 17.
Radiated radio frequency interference (80-1000 MHz), e.g. S6610 & T4000.
Photo 18.
Radiated radio frequency interference (1000-2000 MHz), e.g. T4400.
NE/jh
DANAK-198449
DELTA-A503163-1
Page 48 of 75
Annex 3
Test record sheets - Conducted emissions
NE/jh
DANAK-198449
DELTA-A503163-1
Page 49 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Line no.: 24 VDC. (PIN 3,4) 24 VDC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533.
Sheet 17
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
LIM CE, IEC 60533, B
Bridge & deck zone
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 50 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Line no.: 0 VDC. (PIN 3,4) 24 VDC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533.
Sheet 18
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
LIM CE, IEC 60533, B
Bridge & deck zone
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 51 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Line no.: 0 VDC. (PIN 1,2) 24 VDC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533.
Sheet 15
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
LIM CE, IEC 60533, B
Bridge & deck zone
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 52 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Line no.: 24 VDC. (PIN 1,2) 24 VDC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533.
Sheet 16
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
LIM CE, IEC 60533, B
Bridge & deck zone
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 53 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4000
Selco A/S
Line no.: Neutral. 230 VAC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533. EN 55011 A
Sheet 13
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, EN 55011 A, QP Conducted Emission
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 54 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4000
Selco A/S
Line no.: Line 1. 230 VAC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533. EN 55011 A
Sheet 14
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, EN 55011 A, QP Conducted Emission
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 55 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4400
Selco A/S
Line no.: Neutral. 230 VAC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533. EN 55011 A
Sheet 11
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, EN 55011 A, QP Conducted Emission
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 56 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4400
Selco A/S
Line no.: Line 1. 230 VAC
EMC-5
HEN - A503163
IEC 60945. IACS E10. IEC 60533. EN 55011 A
Sheet 12
2005-07-04
Level [dBµV]
100
80
60
40
20
0
-10
10k
30k
100k
300k
Frequency [Hz]
MES CE 0.01-30 PK MaxPk
LIM CE, EN 55011 A, QP Conducted Emission
LIM CE, IEC 60945, QP Conducted Emission
LIM CE, E-10 deck bridge Conducted Emission
NE/jh
1M
2M
4M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 57 of 75
Annex 4
Test record sheets - Radiated emissions
NE/jh
DANAK-198449
DELTA-A503163-1
Page 58 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Peakscan 1mV and final QP measurements
EMC-5
HEN - A503163
IEC 60945:2005,IACS E10:2004 IEC 60533:1999
Sheet 24
2005-09-30
Level [dBµV/m]
60
50
xx
40
x
x
30
x
20
x
10
0
x
30M
50M
70M
100M
200M
Frequency [Hz]
300M
500M
1G
MES Maximering_fin QP
MES IEC945 1m 30 MaxPk 1
LIM RE, IEC 60945
Radiated Emission
MEASUREMENT RESULT: "Maximering_fin QP"
2005-09-30 15:52
Frequency
Level
MHz
dBµV/m
35.000000
36.700000
40.000000
85.000000
159.990000
427.400000
NE/jh
43.00
42.40
39.90
35.70
18.00
23.50
Transd
dB
Limit
dBµV/m
Margin
dB
Height
cm
Azimuth
deg
Polarisation
18.4
17.5
15.8
11.3
13.1
20.3
54.0
54.0
54.0
54.0
24.0
54.0
11.0
11.6
14.1
18.3
6.0
30.5
101.0
101.0
101.0
123.0
111.0
150.0
358.00
337.00
227.00
8.00
74.00
358.00
VERTICAL
VERTICAL
VERTICAL
VERTICAL
VER BW 10 KH
VERTICAL
2G
DANAK-198449
DELTA-A503163-1
Page 59 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610
Selco A/S
Peakscan 3mH
EMC-5
HEN - A503163
IEC 60945:2005,IACS E10:2004 IEC 60533:1999
Sheet 25
2005-09-30
Level [dBµV/m]
60
50
xx
40
x
x
30
x
20
x
10
0
x
NE/jh
30M
MES
MES
MES
MES
50M
70M
100M
IEC945 4m 30 MaxPk 1
IEC945 4m 30 MaxPk 2
IEC945 4m 30 MaxPk 3
Maximering_fin QP
200M
Frequency [Hz]
300M
500M
1G
2G
DANAK-198449
DELTA-A503163-1
Page 60 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4000, T4400
Selco A/S
Peakscan 1mV andfinal QP measurements
EMC-5
HEN - A503163
IEC 60945:2002 IACS E10:2004 IEC 60533:1999
Sheet 7
2005-07-04
Level [dBµV/m]
60
50
40
30
20
10
0
30M
50M
70M
100M
200M
Frequency [Hz]
MES IEC945 1m 30 MaxPk 1
LIM RE, IEC 60945
Radiated Emission
NE/jh
300M
500M
1G
2G
DANAK-198449
DELTA-A503163-1
Page 61 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
T4000, T4400
Selco A/S
Peakscan 3mH
EMC-5
HEN - A503163
IEC 60945:2002 IACS E10:2004 IEC 60533:1999
Sheet 8
2005-07-04
Level [dBµV/m]
60
50
40
30
20
10
0
30M
50M
70M
100M
200M
Frequency [Hz]
MES IEC945 4m 30 MaxPk 1
MES IEC945 4m 30 MaxPk 2
MES IEC945 4m 30 MaxPk 3
LIM RE, IEC 60945
Radiated Emission
NE/jh
300M
500M
1G
2G
DANAK-198449
DELTA-A503163-1
Page 62 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610, T4000, T4400
Selco A/S
Ant : 90 Deg. Peakscan & final QP
EMC-5
KKJ - A503163
IEC 60945:2002 IACS E10:2004 IEC 60533:1999
Sheet 1
2005-11-09
Level [dBµV/m]
80
70
60
50
40
30
x
xx
20
10
0
x
150k
300k
500k
1M
2M
Frequency [Hz]
3M
5M
Loop
Azimuth
deg
MES mfield_0001_fin QP
MES ME IEC 945 (90 MaxPk
LIM ME, IEC 60945, QP Magnetic Emission
MEASUREMENT RESULT: "mfield_0001_fin QP"
2005-11-09 15:58
Frequency
Level
MHz
dBµV/m
23.965000
24.900000
25.005000
NE/jh
24.10
24.80
28.40
Transd
dB
Limit
dBµV/m
Margin
dB
21.8
21.9
21.9
34.9
34.7
34.7
10.8
10.0
6.3
90 deg 40.00
90 deg 93.00
90 deg 250.00
7M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 63 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610, T4000, T4400
Selco A/S
Ant : 0 Deg. Peakscan & final QP
EMC-5
KKJ - A503163
IEC 60945:2002 IACS E10:2004 IEC 60533:1999
Sheet 2
2005-11-09
Level [dBµV/m]
80
70
60
50
40
30
x
20
10
0
x
150k
300k
500k
1M
2M
Frequency [Hz]
3M
5M
Loop
Azimuth
deg
MES mfield_0001_fin QP
MES ME IEC 945 (0 MaxPk
LIM ME, IEC 60945, QP Magnetic Emission
MEASUREMENT RESULT: "mfield_0001_fin QP"
2005-11-09 16:49
Frequency
Level
MHz
dBµV/m
12.440000
NE/jh
24.10
Transd
dB
Limit
dBµV/m
Margin
dB
20.2
37.4
13.3
0 deg
1.00
7M
10M
30M
DANAK-198449
DELTA-A503163-1
Page 64 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610, T4000, T4400
Selco A/S
Peakscan 1mV & final QP
EMC-5
HEN - A503163
EN 55011 A (10m)
Sheet 3
2005-07-04
Level [dBµV/m]
50
40
30
20
10
0
30M
50M
70M
100M
200M
Frequency [Hz]
MES RE 1mv 30-1000 MaxPk
LIM RE, EN 55011 A, QP Radiated Emission
NE/jh
300M
500M
700M
1G
DANAK-198449
DELTA-A503163-1
Page 65 of 75
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
S6610, T4000, T4400
Selco A/S
Peakscan 4mH
EMC-5
HEN - A503163
EN 55011 A (10m)
Sheet 4
2005-07-04
Level [dBµV/m]
50
40
30
20
10
0
30M
50M
70M
100M
200M
Frequency [Hz]
MES RE 4mh 30-1000 MaxPk
LIM RE, EN 55011 A, QP Radiated Emission
NE/jh
300M
500M
700M
1G
DANAK-198449
DELTA-A503163-1
Page 66 of 75
Annex 5
Measurement curves - Vibration
NE/jh
DANAK-198449
DELTA-A503163-1
Page 67 of 75
Ch1
100.0
LogMag, Ratio
10.0
1.0
100.0m
10.0m
2.0
Mea1/Mea5
X: 3.29978
Y : 0.820513
10.0
SKIB40 start 14:22:57
Frequency, Hz
Curve 01.
100.0
test date 06-07-2005
Resonance search, Y-Axis (max. ampl. fact.) T4000.
Ch2
100.0
LogMag, g
10.0
1.0
100.0m
10.0m
2.0
Mea2/Mea5
X: 2.23017
Y : 0.888889
10.0
SKIB40 start 14:22:57
Frequency, Hz
Curve 02.
NE/jh
100.0
test date 06-07-2005
Resonance search, Y-Axis (max. ampl. fact.) T4400.
DANAK-198449
DELTA-A503163-1
Page 68 of 75
Ch 3
100.0
LogMag, g
10.0
1.0
100.0m
10.0m
2.0
Mea2/Mea5
X: 4.15033
Y : 0.933333
10.0
SKIB40 start 14:22:57
Frequency, Hz
Curve 03.
100.0
test date 06-07-2005
Resonance search, Y-Axis (max. ampl. fact.) S6610.
10.0
1.0
LogMag, g²/Hz
100.0m
10.0m
1.0m
100.0u
RMS: 3.97978
10.0u
1.0u
2.0
10.0
Frequency
, Hz
SKBDN V4GRMS start 09:16:51 test date
07-07-2005
Curve 04.
NE/jh
Endurance, e.g. X-axis.
100.0
tim e at m ax lev el 02:30:01
DANAK-198449
DELTA-A503163-1
Page 69 of 75
Annex 6
Test set-up and functional test procedure (from Selco A/S)
(This annex is informative and
not part of the accredited report)
NE/jh
DANAK-198449
DELTA-A503163-1
Page 70 of 75
Test set-up S6610
24 VDC
Alarm relay
LC req. inputs
S6610
LC ack. outputs
LC analog inputs
RS485
Relay status Indicator
Dig.inp.
sim.
DVM 3
Analog
inp. sim.
Notebook
Modbus
CAN bus
S6000
IO/P
Analog output, U
DVM 1
Analog output, I
DVM 2
NE/jh
DANAK-198449
DELTA-A503163-1
Page 71 of 75
Functional test procedure S6610
General performance verification is performed as follows:
1. Apply 24VDC to the powersupply 1 and 2
2. Apply 9VDC batteri to LC analog input 1
3. Measure 9VDC on Analog output 1
4. Measure 12mA on Analog output 2
5. Apply GND to LC REQ. INPUT 1
6. Measure LC ACK. OUTPUT 1 is on
7. Apply a PC with a RS485 communication to the RS485 input
8. Open the modbus server on the pc and see that the communication is OK
9. Attach a S6000 module to the CAN BUS
10. See the S6000 module on the display
11. Attach a relay boks on the alarm relay
12. Disconnect powersupply 1 and see the relay alter its state
NE/jh
DANAK-198449
DELTA-A503163-1
Page 72 of 75
Test set-up T4000
Auto reset
Close enable
T4000
Forv./Inv.
Output to Governor
DVM 1
Gen 230 VAC
Bus 230 VAC
NE/jh
DANAK-198449
DELTA-A503163-1
Page 73 of 75
Functional test procedure T4000
General performance verification is performed as follows:
1. Apply 220VAC to the BUS input
2. Bus led goes on
3. Apply 220VAC to the GEN input (same phase as BUS input)
4. Gen led goes on
5. Relay led goes on
6. Close relay goes on
7. Measure 0VDC on terminal 21 and 22
8. Reverse the voltage on the BUS input
9. Relay led goes off
10. Close relay goes off
11. Measure 6VDC on terminal 21 and 22
NE/jh
DANAK-198449
DELTA-A503163-1
Page 74 of 75
Test set-up T4400
230 VAC
Unload Trip Rel.
C/B
Relay status Indicator
Freq. In
T4400
Unload
Watt in
Parallel lines
Breakout Box
Output
DVM 1
NE/jh
DVM 2
DANAK-198449
DELTA-A503163-1
Page 75 of 75
Functional test procedure T4400
General performance verification is performed as follows:
1. Apply 220VAC to Un
2. Un led goes on
3. Connect terminal 31 and 32 together
4. C/B led goes on
5. Apply 1 VDC to WATT IN with terminal 12 as GND
6. Measure 6VDC on Test OUT with teminal 12 as GND
NE/jh