We help ideas meet the real world Test Report DANAK Reg. no. 19 Supplementary type approval testing of M1000 Alarm Annunciator and M3000 Analog Alarm Annunciator Performed for Selco A/S DANAK-197639 Project no.: E502468-1 Page 1 of 9 4 annexes 04 October 2004 DELTA Danish Electronics, Light & Acoustics Venlighedsvej 4 2970 Hørsholm Denmark Tel. (+45) 72 19 40 00 Fax (+45) 72 19 40 01 www.delta.dk This report is issued under the rules of DANAK (Danish Accreditation). Further information about DANAK can be found at www.danak.dk. The report must not be reproduced, except in full, without the written approval of DELTA. 20dan-uk-k DANAK-197639 DELTA-E502468-1 Page 2 of 9 Title Supplementary type approval testing of M1000 Alarm Annunciator and M3000 Analog Alarm Annunciator Test objects M1000 Alarm Annunciator M3000 Analog Alarm Annunciator Detailed information is given in sections 2.1 to 2.2 Report no. DANAK-197639 Project no. E502468-1 Test period 8 September 2004 Client Selco A/S Meterbuen 6-12 2740 Skovlunde Denmark Manufacturer Selco A/S Specifications IEC 60945: Fourth edition, 2002 “Maritime navigation and radio communication equipment and systems - General requirements - Methods of testing and required test results” IACS E10: Rev.4 May 2004. Test Specification for Type Approval. ”Test specification applicable, but not confined, to all equipment used for: - Control, protection and safety; internal communication.” IEC 60533: Second edition, 1999. "Electrical and electronic installations in ships – Electromagnetic compatibility" Results No malfunctions were detected. The criteria for compliance are listed in section 3.2. Test personnel Ms. Daniela Coman NE/AED DANAK-197639 DELTA-E502468-1 Page 3 of 9 Date 04 October 2004 Project manager Niels Engel DELTA Responsible Kim A. Schmidt, B.Sc.M.E. DELTA NE/AED DANAK-197639 DELTA-E502468-1 Page 4 of 9 Table of contents Page 1. 1.1 1.2 Summary of test Test requirements Conclusion 5 5 5 2. 2.1 2.2 2.3 Test specimen(s) Test object: M1000 Alarm Annunciator Test object: M3000 Analog Alarm Annunciator AUX equipment:: H0300 Event Logger 6 6 6 6 3. 3.1 3.2 3.3 3.4 General test conditions Test set-up Criteria for compliance Functional test Standard environment 7 7 7 7 7 4. 4.1 4.2 Test and results Radiated emissions Radiated radio frequency interference 8 8 9 Annex 1 List of instruments (1 page) Annex 2 Photos (1 page) Annex 3 Test set-up (from Selco A/S) (1 page) Annex 4 Test record sheets – Radiated emissions (1 page) NE/AED DANAK-197639 DELTA-E502468-1 Page 5 of 9 1. Summary of test 1.1 Test requirements The present test report concerns the supplementary type approval testing of the M1000 Alarm Annunciator and the M3000 Analog Alarm Annunciator (named M1000 and M3000 in the following). The M1000 and the M3000 mentioned in this test report have been subjected to previous type approval testing ref. test reports DANAK-195378/ DELTA-K251196-3, rev. 2 and DANAK-195254/DELTA-K251196-6. The purpose of the supplementary type approval testing is to provide the necessary documentation for maintaining the type approval. Consequently, the supplementary type approval testing of the M1000 and the M3000 was limited to the following tests: Test Radiated emissions, 1000-2000 MHz. Radiated radio frequency interference, 1000-2000 MHz. 1.2 Test method CISPR 16-1:1999 EN 61000-4-3:2002 Conclusion The test objects mentioned in this report meet the selected requirements of the standards stated below. • IEC 60945:2002 • IACS E10:2004 • IEC 60533:1999 The test results relate only to the specimens tested. NE/AED DANAK-197639 DELTA-E502468-1 Page 6 of 9 2. Test specimen(s) 2.1 Test object: M1000 Alarm Annunciator 2.2 2.3 NE/AED Manufacturer Model Selco A/S M1000-24-00 Serial no. 33 60 58 Supply voltage Operational mode 24 VDC Normal operational mode Test object: M3000 Analog Alarm Annunciator Manufacturer Selco A/S Model Serial no. Supply voltage Operational mode M3000-30-00 33 66 37 24 VDC Normal operational mode AUX equipment:: H0300 Event Logger Manufacturers Selco A/S Model H0300 Serial no. Operational mode 37 35 32 RS485 communication, logging alarms and events DANAK-197639 DELTA-E502468-1 Page 7 of 9 3. General test conditions 3.1 Test set-up A drawing of the test set-up is enclosed in annex 3. 3.2 Criteria for compliance No change of the actual operational state of the test objects is allowed. 3.3 Functional test A functional test was performed before, during (if specified) and after each test. The functional test was carried out in accordance with the functional test procedure provided by the customer. The functional test procedure is given in section 4.3 and annex 4 of the previous test reports ref. test reports DANAK-195378/ DELTA-K251196-3, rev. 2 and DANAK-195254/DELTA-K251196-6. 3.4 Standard environment Normal environmental condition: Temperature Humidity Air pressure Power supply voltage NE/AED : : : : 15°C to 35°C 25 %RH to 75 %RH 86 kPa to 106 kPa (860 mbar to 1060 mbar) Unom. ±3% DANAK-197639 DELTA-E502468-1 Page 8 of 9 4. Test and results 4.1 Radiated emissions Specifications CISPR 16-1 (1999-10): Specification for radio disturbance and immunity measuring apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus. Severity and procedure Frequency range Limits (quasi-peak) : : 1000-2000 MHz 0.15-0.3 MHz 0.3-30 MHz 30-2000 MHz 156-165 MHz : : : : 80-52 dBµV/m 52-34 dBµV/m 54 dBµV/m, except for 24 dBµV/m quasi-peak or 30 dBµV/m peak The electric field is measured with antennas at a distance of 3 m. The test specimen is energised and in normal operational mode during the measurement. Results The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in annex 4. NE/AED DANAK-197639 DELTA-E502468-1 Page 9 of 9 4.2 Radiated radio frequency interference Specifications IEC 61000-4-3 (2002-03): Testing and measurement techniques - Radiated, radiofrequency, electromagnetic field immunity test. Severity and procedure Frequency range : Field strength : Modulation : 1000-2000 MHz 10 V/m 80% AM, 400 Hz sine wave The test is performed in a semi-anechoic room. The field is generated using linearly polarised broadband antennas. The test specimens are energised and in normal operational mode during the exposure. The test specimens are observed during the exposure, and a functional test is performed after the exposure. Results No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure. NE/AED DANAK-197639 DELTA-E502468-1 Annex 1 List of instruments (1 page) NE/AED DANAK-197639 DELTA-E502468-1 List of instruments MANUFACTURER TYPE NO. DMEAS Software Detectus ver. 1.0 IE-B915 EMI Test receiver 20-2000 MHz Rohde & Schwarz ESVS10 E-P402 Microwave amplifier Miteq AFS5-0010100030-10P-5 E-I839 Antenna Horn 1-18 GHz ARA DRG-118/A IE-B919 LISN 2 x 10A 9k-30MHz Rohde & Schwarz ESH3-Z5 E-I838 Amplifier 0.8-2.2 GHz 8W Milmega AS0822-8B E-H908 Signal generator 10 kHz - 2.4 GHz Marconi 2024 NO. NE/AED DESCRIPTION DANAK-197639 DELTA-E502468-1 Annex 2 Photos (1 page) NE/AED DANAK-197639 DELTA-E502468-1 PHOTO 1. Radiated radio frequency interference, 1000-2000 MHz. PHOTO 2. Radiated emissions, 1000-2000 MHz. NE/AED DANAK-197639 DELTA-E502468-1 Annex 3 Test set-up (from Selco A/S) (1 page) NE/AED DANAK-197639 DELTA-E502468-1 Test set-up Output indicators M1000 (E.U.T. 2.1) Input signals (DC) Tacho signals Pulse simulation 24 VDC RS485 H0300 (AUX. 2.3) Output indicators M3000 (E.U.T. 2.2) Inputs (U) Inputs (I) 24 VDC RS485 NE/AED H0300 (AUX. 2.3) DANAK-197639 DELTA-E502468-1 Annex 4 Test record sheets – Radiated emissions (1 page) NE/AED DANAK-197639 DELTA-E502468-1 EUT: Manufacturer: Operating Condition: Test Site: Operator: Test Specification: Comment: Start of Test: Graph 1. NE/AED M3000, M1000, H0300 Selco A/S Normal operational modes EMI DC - E502468-1 IACS E10:2004 / IEC 60945:2002 Sheet 1 - Final max. QP scan 2004-09-08 Radiated emission 1-2 GHz.