Test Report M1000 M3000

We help ideas meet the real world
Test Report
DANAK
Reg. no. 19
Supplementary type approval testing of M1000 Alarm Annunciator
and M3000 Analog Alarm Annunciator
Performed for Selco A/S
DANAK-197639
Project no.: E502468-1
Page 1 of 9
4 annexes
04 October 2004
DELTA
Danish Electronics,
Light & Acoustics
Venlighedsvej 4
2970 Hørsholm
Denmark
Tel. (+45) 72 19 40 00
Fax (+45) 72 19 40 01
www.delta.dk
This report is issued under the rules of DANAK (Danish Accreditation).
Further information about DANAK can be found at www.danak.dk.
The report must not be reproduced, except in full, without the written approval of DELTA.
20dan-uk-k
DANAK-197639
DELTA-E502468-1
Page 2 of 9
Title
Supplementary type approval testing of M1000 Alarm
Annunciator and M3000 Analog Alarm Annunciator
Test objects
M1000 Alarm Annunciator
M3000 Analog Alarm Annunciator
Detailed information is given in sections 2.1 to 2.2
Report no.
DANAK-197639
Project no.
E502468-1
Test period
8 September 2004
Client
Selco A/S
Meterbuen 6-12
2740 Skovlunde
Denmark
Manufacturer
Selco A/S
Specifications
IEC 60945: Fourth edition, 2002 “Maritime navigation
and radio communication equipment and systems - General requirements - Methods of testing and required test
results”
IACS E10: Rev.4 May 2004. Test Specification for Type
Approval.
”Test specification applicable, but not confined, to all
equipment used for: - Control, protection and safety; internal communication.”
IEC 60533: Second edition, 1999. "Electrical and electronic installations in ships – Electromagnetic compatibility"
Results
No malfunctions were detected. The criteria for compliance are listed in section 3.2.
Test personnel
Ms. Daniela Coman
NE/AED
DANAK-197639
DELTA-E502468-1
Page 3 of 9
Date
04 October 2004
Project manager
Niels Engel
DELTA
Responsible
Kim A. Schmidt, B.Sc.M.E.
DELTA
NE/AED
DANAK-197639
DELTA-E502468-1
Page 4 of 9
Table of contents
Page
1.
1.1
1.2
Summary of test
Test requirements
Conclusion
5
5
5
2.
2.1
2.2
2.3
Test specimen(s)
Test object: M1000 Alarm Annunciator
Test object: M3000 Analog Alarm Annunciator
AUX equipment:: H0300 Event Logger
6
6
6
6
3.
3.1
3.2
3.3
3.4
General test conditions
Test set-up
Criteria for compliance
Functional test
Standard environment
7
7
7
7
7
4.
4.1
4.2
Test and results
Radiated emissions
Radiated radio frequency interference
8
8
9
Annex 1 List of instruments (1 page)
Annex 2 Photos (1 page)
Annex 3 Test set-up (from Selco A/S) (1 page)
Annex 4 Test record sheets – Radiated emissions (1 page)
NE/AED
DANAK-197639
DELTA-E502468-1
Page 5 of 9
1.
Summary of test
1.1
Test requirements
The present test report concerns the supplementary type approval testing of the M1000
Alarm Annunciator and the M3000 Analog Alarm Annunciator (named M1000 and
M3000 in the following). The M1000 and the M3000 mentioned in this test report have
been subjected to previous type approval testing ref. test reports DANAK-195378/
DELTA-K251196-3, rev. 2 and DANAK-195254/DELTA-K251196-6.
The purpose of the supplementary type approval testing is to provide the necessary
documentation for maintaining the type approval.
Consequently, the supplementary type approval testing of the M1000 and the M3000
was limited to the following tests:
Test
Radiated emissions, 1000-2000 MHz.
Radiated radio frequency interference, 1000-2000 MHz.
1.2
Test method
CISPR 16-1:1999
EN 61000-4-3:2002
Conclusion
The test objects mentioned in this report meet the selected requirements of the standards
stated below.
•
IEC 60945:2002
•
IACS E10:2004
•
IEC 60533:1999
The test results relate only to the specimens tested.
NE/AED
DANAK-197639
DELTA-E502468-1
Page 6 of 9
2.
Test specimen(s)
2.1
Test object: M1000 Alarm Annunciator
2.2
2.3
NE/AED
Manufacturer
Model
Selco A/S
M1000-24-00
Serial no.
33 60 58
Supply voltage
Operational mode
24 VDC
Normal operational mode
Test object: M3000 Analog Alarm Annunciator
Manufacturer
Selco A/S
Model
Serial no.
Supply voltage
Operational mode
M3000-30-00
33 66 37
24 VDC
Normal operational mode
AUX equipment:: H0300 Event Logger
Manufacturers
Selco A/S
Model
H0300
Serial no.
Operational mode
37 35 32
RS485 communication, logging alarms and events
DANAK-197639
DELTA-E502468-1
Page 7 of 9
3.
General test conditions
3.1
Test set-up
A drawing of the test set-up is enclosed in annex 3.
3.2
Criteria for compliance
No change of the actual operational state of the test objects is allowed.
3.3
Functional test
A functional test was performed before, during (if specified) and after each test. The
functional test was carried out in accordance with the functional test procedure provided
by the customer.
The functional test procedure is given in section 4.3 and annex 4 of the previous test
reports ref. test reports DANAK-195378/ DELTA-K251196-3, rev. 2 and
DANAK-195254/DELTA-K251196-6.
3.4
Standard environment
Normal environmental condition:
Temperature
Humidity
Air pressure
Power supply voltage
NE/AED
:
:
:
:
15°C to 35°C
25 %RH to 75 %RH
86 kPa to 106 kPa (860 mbar to 1060 mbar)
Unom. ±3%
DANAK-197639
DELTA-E502468-1
Page 8 of 9
4.
Test and results
4.1
Radiated emissions
Specifications
CISPR 16-1 (1999-10): Specification for radio disturbance and immunity measuring
apparatus and methods - Part 1: Radio disturbance and immunity measuring apparatus.
Severity and procedure
Frequency range
Limits (quasi-peak)
:
:
1000-2000 MHz
0.15-0.3 MHz
0.3-30 MHz
30-2000 MHz
156-165 MHz
:
:
:
:
80-52 dBµV/m
52-34 dBµV/m
54 dBµV/m, except for
24 dBµV/m quasi-peak or
30 dBµV/m peak
The electric field is measured with antennas at a distance of 3 m.
The test specimen is energised and in normal operational mode during the measurement.
Results
The radiated emissions were within the specified limits. Test record sheets of the radiated emission measurements are enclosed in annex 4.
NE/AED
DANAK-197639
DELTA-E502468-1
Page 9 of 9
4.2
Radiated radio frequency interference
Specifications
IEC 61000-4-3 (2002-03): Testing and measurement techniques - Radiated, radiofrequency, electromagnetic field immunity test.
Severity and procedure
Frequency range :
Field strength
:
Modulation
:
1000-2000 MHz
10 V/m
80% AM, 400 Hz sine wave
The test is performed in a semi-anechoic room. The field is generated using linearly polarised broadband antennas.
The test specimens are energised and in normal operational mode during the exposure.
The test specimens are observed during the exposure, and a functional test is performed
after the exposure.
Results
No malfunction was observed during the exposure, and the function of the test specimens was OK after the exposure.
NE/AED
DANAK-197639
DELTA-E502468-1
Annex 1
List of instruments
(1 page)
NE/AED
DANAK-197639
DELTA-E502468-1
List of instruments
MANUFACTURER
TYPE NO.
DMEAS Software
Detectus
ver. 1.0
IE-B915 EMI Test receiver 20-2000 MHz
Rohde & Schwarz
ESVS10
E-P402
Microwave amplifier
Miteq
AFS5-0010100030-10P-5
E-I839
Antenna Horn 1-18 GHz
ARA
DRG-118/A
IE-B919 LISN 2 x 10A 9k-30MHz
Rohde & Schwarz
ESH3-Z5
E-I838
Amplifier 0.8-2.2 GHz 8W
Milmega
AS0822-8B
E-H908
Signal generator 10 kHz - 2.4 GHz
Marconi
2024
NO.
NE/AED
DESCRIPTION
DANAK-197639
DELTA-E502468-1
Annex 2
Photos
(1 page)
NE/AED
DANAK-197639
DELTA-E502468-1
PHOTO 1.
Radiated radio frequency interference, 1000-2000 MHz.
PHOTO 2.
Radiated emissions, 1000-2000 MHz.
NE/AED
DANAK-197639
DELTA-E502468-1
Annex 3
Test set-up
(from Selco A/S)
(1 page)
NE/AED
DANAK-197639
DELTA-E502468-1
Test set-up
Output indicators
M1000
(E.U.T. 2.1)
Input signals (DC)
Tacho signals
Pulse simulation
24 VDC
RS485
H0300
(AUX. 2.3)
Output indicators
M3000
(E.U.T. 2.2)
Inputs (U)
Inputs (I)
24 VDC
RS485
NE/AED
H0300
(AUX. 2.3)
DANAK-197639
DELTA-E502468-1
Annex 4
Test record sheets – Radiated emissions
(1 page)
NE/AED
DANAK-197639
DELTA-E502468-1
EUT:
Manufacturer:
Operating Condition:
Test Site:
Operator:
Test Specification:
Comment:
Start of Test:
Graph 1.
NE/AED
M3000, M1000, H0300
Selco A/S
Normal operational modes
EMI
DC - E502468-1
IACS E10:2004 / IEC 60945:2002
Sheet 1 - Final max. QP scan
2004-09-08
Radiated emission 1-2 GHz.