RELAY BASICS - OEN India Ltd.

RELAY BASICS
Relays
Relays are electro magnetically operated switches. An actuating current on a coil operates one or more galvanically
separated contacts or load circuits.
The electro mechanical relay is a remote controlled switch capable of switching multiple circuits, either individually,
simultaneously, or in sequence.
The primary functions of a relay are:
l
The galvanic separation of the primary or actuating circuit and the load circuits
l
Single input/multiple output capability
l
Separation of dif ferent load circuits for multi-pole relays
l
Separation of AC and DC circuits
l
Interface between electronic and power circuits
l
Multiple switching functions, e.g. delay, signal conditioning
l
Amplifier function.
Applications of Relay
Typical applications for relays include laboratory instruments, telecommunication systems, computer interfaces,
domestic appliances, air conditioning and heating, automotive electrics, traf fic control, lighting control, building
control, electric power control, business machines, control of motors and solenoids, tooling machines, production
and test equipment.
Electromechanical Relays
In electromechanical relays the switching element is a mechanical contact, actuated by an electromagnet. This is
the most widely used type of relay design. The principal internal functions of the electromechanical relay are:
l
Conversion of electrical current (input, coil current) to a magnetic field
l
Conversion of the magnetic field into a mechanical force
l
This force operates the contacts (secondary side)
l
Contacts switch and conduct electrical current (output, load current).
Electromechanical Relay Design
The most important components are:
Contact system or secondary side
l
Fixed contacts
l
Moving contacts (contacts being moved by the magnetic system to switch the load circuit)
l
Contact springs (holding the contacts but suf ficiently flexible to allow the contacts to move)
Magnetic system
l
Coil (to generate the necessary magnetic field to actuate the armature and the contacts)
l
Core (highly magnetic permeable - concentrates the magnetic field)
l
Yoke (to establish the magnetic circuit)
l
Armature (the moving part of the magnetic system which closes and opens the magnetic circuit and acts via
an actuator o the moving relay contacts)
l
Return spring (For quick return of the moving contact to normal condition on removal of the coil power)
Mechanical components
l
Case & Base (to protect the relay against ex ternal influences and for protection against electric shock)
Insulation (within the relay to separate the primary circuit from the secondary side and to provide the required
l
Actuator (used in some relay designs to translate the motion of the magnetic system to the contact system
(Moving contacts). Must have insulation properties to isolate the primary circuit (coil, magnetic circuit) from the
secondary side (contact system).
l
Pins or terminals (to connect between the contact system and the load)
l
Mounting devices (sockets / built in brackets / PCB)
Basic Relay Terminologies
l
AC Coil: Relays for direct energization with AC supply. Unless otherwise specified AC coils may be used with
50Hz supply.
l
Ambient Temperature: Temperature measured directly near the relay. The ma ximum allowed value may not be
exceeded, otherwise there is a chance for relay failure. (e.g. Coil overheating)
l
Bounce Time: Time interval between the first and final closing (or opening) of a contact, caused by a
mechanical shock process in contact movement. These shock processes are called contact bounce.
l
Break Contact: A contact that is closed in the rest state of the relay and open in the operating state. (refer
Normally Closed Contacts)
l
Bridging Contact: Special contact assembly in which two stationary contacts are connected by a movable
bridge. In open contact condition the bridge is separated on both its sides from the stationary contacts. Due to
this double interruption a bigger contact gap can be achieved. This is of advantage especially at very high
contact loads or when there are safety requirements. (refer Form Z type contacts)
l
Change Over Contact: Compound contact consisting of a make contact and a break contact with a common
contact spring. When one contact circuit is open the other one is closed.(refer Form C type contacts)
l
Coil Current: The current (by design) drawn by the coil for generating the magnetic pull force. At the moment of
switching the coil On, the current is higher than in continuous use.
l
Coil Resistance: Electrical resistance of the relay coil at reference temperature. Coil resistance varies with
temperature. (refer Pick-up voltage change due to coil temperature rise)
l
l
Contact Forms: This denotes the contact mechanism and number of contacts in the circuit. Form A contacts
are also called NO contacts or make contacts. Form B contacts are also called NC contacts or break contacts.
Form C contacts are also called Changeover contacts
Contact Gap: Distance between the contacts in the open contact circuit condition.
l
Contact Rating: The current a relay can switch On and OFF under specified conditions of voltage and
environmental parameters.
l
Contact Resistance: Electrical resistance of a closed contact circuit, measured at the terminals of the relay
with indicated measuring current and voltage.
l
Continuous Current (Contacts): Ma ximum value of current (RMS value at AC), which a previously closed
contact can continuously carry under defined conditions.
l
Creepage Distance: Closest distance between two conductive parts, measured along the surface of
insulated parts.
l
Dielectric Strength: Voltage (RMS Value in AC Voltage, 50Hz 1 min) the insulation can withstand between relay
elements that are insulated from one another.
l
Driver Protection circuit: When the coil energization is switched of f, a very high negative peak voltage is
produced by the coil and it may reach more than 10-20 times the nominal coil voltage. Possible destruction of
the semiconductor device (Driver) the coil circuit is the result. A solution is provided by a driver protection circuit
that is a damping component, which is connected in parallel to the coil. It protects the driver but does slow the
release time of the relay. Also known as coil snubber circuit.
l
Dropout Voltage: The Voltage at or below which all the contacts of an operated relay must revert to unoperated
position. Also known as release voltage.
l
Dust Proof Relays / Solder Proof Relay: Relay with case for protection against dust and touch. With specified
solder conditions are kept, no harmful amounts of flux or solder vapor penetrate into the relay.
l
l
Electrical Endurance (Electrical Life): Number of operations until switching failure of a relay under defined
Conditions of load and of ambient influences. The reference value specified for the life apply, unless otherwise
specified, to a resistive load. At lower contact loads a substantially longer electrical life is achieved. At higher
loads the electrical life is reduced substantially.
Hermetically Sealed Relays: Relay is equipped with metal case, its connecting pins are sealed with glass; it full
fills highest requirements regarding sealing. (Refer series 30 relays)
l
Inrush Current: This value specifies the instantaneous current that may flow on the defined conditions.
(Voltage, Power Factor, Duration) when the contact closes. Depends on type of load. (refer load inrush current
and time diagram)
l
Insulation Resistance: Electrical resistance, measured between insulated relay parts at a test voltage of
500VDC.
l
Make Contact: A contact that is open in the rest state and closed in the operating state. (refer normally
open contacts)
l
Material Transfer: During the switching procedure the arc heats up the two contacts dif ferently, depending on
the load and polarity. This result in a material transfer from the hot ter to the cooler electrode. With a higher DC
loads on the contact, a ‘pip’ is build up, the other contact looses material and it creates a crater.
l
Maximum Carrying Current: The ma ximum current which af ter closing or prior to opening, the contacts can
safely pass without being subject to temperature rise in excess of their design limit.
l
Maximum Continuous Voltage: The ma ximum voltage that can be applied to relay coil continuously with out
causing damage.
l
Maximum Switching Current: The ma ximum current that can safely be switched by the contacts.
l
Maximum Switching frequency: The ma ximum switching frequency which satisfies the mechanical or
electrical life under repeated operations by applying a pulse train at the rated voltage to the operating coil
l
Maximum Switching Power: The ma ximum value that can be switched by the contacts without causing
damage.
l
Maximum Switching Voltage: The ma ximum open circuit voltage that can be safely be switched by the
contacts.
l
Mechanical Endurance (Mechanical Life): Number of switching operations without contact load during which
the relay remains within the specified characteristics.
l
Mechanical Flag Indication: Mechanical indicator in relays (mostly industrial relays) which is linked to the
contacts and shows their position. Refer series 51 relays
l
Nominal Coil Power: Power consumption of the coil at nominal voltage and nominal coil resistance. Also
known as Rated Power.
l
Nominal Coil Voltage: The voltage by design intended to be applied to the relay coil. Also known as Rated
Voltage.
l
Open Relay: Relay without case or cover.
l
Operating Power: Coil Power at which the relay operates
l
l
l
l
Operate time: The time from the initial application of power to the coil until the closure of the normally open
contacts. It is excluding bounce time.
PCB Relays: Relays designed for soldering into printed circuit boards.
Pick-up Voltage: The value of the voltage that should be applied to an un-operated relay coil at or below which
all the contacts of the relay should operate. Also known as Pull-in voltage / Must operate voltage.
Plug-in Relay: Relays that are held in the socket by flat Plug-in terminals (Round Pins for Series 1R, 2R & 51).
l
Release Time: The time from the initial removal of power from the coil until the re-closure of the normally closed
contacts. It is excluding bounce time.
l
Sealed Relay: Plastic base and cover are sealed with epoxy resin, af ter soldering into the PC board the relay
may be cleaned in liquid or coated with varnish. Provides a large measure of protection against aggressive
l
l
l
Sealing: See open relay / dust proof relay / sealed relay / Hermetically Sealed relay.
Shock Resistance: It specifies at which mechanical shock (multiple of gravitational acceleration ‘g’ at half since
wave and duration 11 ms) the closed contact has still not opened (failure criteria: contact interrupted for >10µS
is) or no damage occurs.
Test But ton: Test but ton (usually in industrial relays), which is accessible from outside: if it is actuated by hand
Or with a tool, it switches the contact circuit of a de-energized relay from Of f to On condition. Some times it can
be locked mechanically. The test but ton helps to trace the current path in a switchboard. Refer series 51 relays.
l
Vibration Resistance: It specifies the amplitude or the acceleration in a defined frequency range at which the
RELAY CONTACTS
The contacts are the most important element of relay construction. Contact performance is influenced by contact
material, voltage and current values applied to the contacts, the type of load, frequency of switching, ambient
atmosphere, form of contact, contact switching speed and of bounce.
The contacts are practically not clean because the surfaces are covered by thin layers of low conductivity,
semiconductor properties or even isolating characteristics. These layers of oxides, sulphides and other compounds
will be formed on the surface of metals by absorption of gas molecules from the ambient atmosphere within a very
short time. The grow th of these layers will be slowed down and eventually stopped as the layer itself prevents further
chemical reaction. The resistance of these layers increases with their thickness. To get a reliable electrical contact
these layers have to be destroyed. This can be done by mechanical or electro-thermal destruction.
Mechanical Cleaning
When the contacts are closing, the metal surfaces will collide and hit against each other several times (bouncing),
causing elastic deformation of the contact area and mechanical destruction of the thin layers. With high contact
pressure also this could be obtained.
The design of most of the relays allows the contact surfaces to wipe across each other destroying the non-conductive
films on the contact surfaces. This contact wipe is of ten enough to clean the surface and reduce resistance to an
acceptable level, as well as keeping the resistance stable through out the electrical life of the relay.
Electrical Cleaning
The low and non-conductive layers can also be destroyed by the ef fects of
a) electrical voltage ( frit ting)
b) current ( heating of contact points)
c) thermal ef fects (high temperature due to electrical arc)
a) Frit ting
The term frit ting describes the electrical breakdown of oxide / foreign layer when a suf ficiently high voltage is applied
across a closed contact. Due to the applied voltage and very short distance between the low potentials a high electric
field is generated. This electric field destroys the thin non-conductive layer and establishes a metal bridge electrically
linking the two surfaces. The value of frit ting voltage depends on the contact material, composition and thickness of
layers, conductivity and composition of the contact surface.
b) High Currents.
High continuous currents and increased contact resistance due to the layers causes heating of the contact. The layers
will eventually be destroyed thermally and a larger ef fective contact area is created, reducing the constriction
resistance.
c) Arc, sparks
Under certain circumstances an electric spark or arc will be generated during contact making or contact breaking
under load. The ex tremely high temperature of these arcs may destroy the contact layers and burn or disintegrate
other contaminants or particles in the vicinity of the point of contact.
Basic Contact Forms
Form A
SPST -NO
Form C
Form B
SPST -NC
Form X
Form Y
SPST -NC-DB
Form Z
SPDT -DB
(2Circuit)
SPDT
SPST -NO-DB
Dry circuits, low level switching
The term dry circuit describes applications with ex tremely low loads. In these cases the current is too low to establish
an electro-thermal cleaning ef fect and the voltage is below the frit ting voltage. Hence the non-conductive layers are not
destroyed. Also mechanical cleaning will not be suf ficient. The correct choice of contact materials is critical in such
cases for reliability.
Characteristics of Common Contact Materials
Characteristics of contact materials are given below. Refer to them when selecting a relay
Contact
Material
Silver - Nickel
AgNi 0.15
Good Electrical conductivity and thermal conductivity. Exhibits low contact
resistance, and widely used. Easily develops a sulfide film in a sulfide atmosphere.
Silver - Nickel
AgNi 80:20
Used for switching loads in the rage of >100mA upto power switching. Good
resistance to contact wear and contact welding. Slightly high contact resistance.
Mainly used in DC Switching particularly in automotive applications where high
inrush current occur.
Silver - Cadmium oxide
AgCdO
Very Good resistance to contact wear and welding. Good thermal and mechanical
stability. Used for switching inductive or high current loads like Motors, Solenoids
etc. High contact resistance and Sulphide films form easily.
Silver Tin Oxide
AgSnO2
High melting point and high thermal stability and therefore high resistance to
welding. Also contact erosion rate is lower because any arc spreads to the outside
of the contact preventing creation of a local hot spot and potential weld. High
contact life minimum material migration. AgSnO2 is mainly used for application
involving high inrush current like lamp loads or inductive DC loads.
Palladium - Copper
PdCu
Tungsten
Surface
Finish
W
Greater Hardness, low contact wear and stable contact resistance. Good corrosion
and sulphidation resistance. Very low material migration compared to other contact
materials. Expensive. Mainly used for Flasher applications in Automobiles.
Highest melting point, high wear resistance with heav y loads, lit tle transfer of
material, best suited for breaking heav y inductive loads. Not recommended
Au clad
(gold clad)
Au with its excellent corrosion resistance is pressure welded onto a base metal.
Special characteristics are uniform thickness and the nonexistence of pinholes.
Greatly ef fective especially for low level loads under relatively adverse
atmospheres. Of ten dif ficult to implement clad contacts in existing relays due to
design and installation.
Au plating
(gold plating)
Similar ef fect to Au cladding. Depending on the plating process used, supervision
is important as there is possibility of pinholes and cracks. Relatively easy to
implement gold plating in existing relays.
Au flash plating
(gold thin-film plating)
Purpose is to protect the contact base metal during storage of the switch or device
with built-in switch.
However, a certain degree of contact stability can be obtained even when
switching loads.
Contact circuit voltage, current and load
Electric Arc Switching
An electric arc is a current intensive gas discharge which occurs when opening a switch or as a result of a flashover.
Under certain circumstances the air path between two contacts are ionized due to very high electric field. Ionization
causes the normally non-conducting air conductive and its conductivity is maintained if suf ficient energy is supplied.
The arc represents an additional resistive path in the load circuit. The minimum voltage and current required for
generation and maintenance of a stable arc depends on the contact material and the length of the air gap. (Ionization of
air happens if a potential of 32V or more is applied between two electrodes)
Due to extremely high temperature of the arc the surface of the contact will melt. Evaporation or sputtering of the contact
material leads to wear and material migration reducing the service life of the contacts.
Arc in DC circuits
In DC circuits it is generally during contact breaking that arc occurs. When breaking contacts move further apart and as the
gap between the contacts increases the minimum voltage to maintain the arc normally rises above source voltage and the
arc is extinguished. If however the supply voltage / current is suf ficiently high enough to maintain a stable arc across open
contacts, the relay will be destroyed.
In DC inductive circuits, the counter emf generated whose magnitude is equal to L*I*I/2 (energy stored in the inductance)
act as a secondary energy source which causes the arc to be maintained until the energy in the circuit has been converted
to heat. This leads to considerably longer arc duration. To prevent destruction of the contacts and to keep the arc duration
within limits, the switching voltage/current has to be within the maximum DC breaking capacity. (Higher the L/R ratio or
lower the power factor of the load, the arc extinguishing time increases
Arc in AC circuits
In AC circuits the supply helps to extinguish the arc as it will collapse when the current becomes zero.(every 10 ms for 50Hz
supply) The arc may however be re-established if the supply voltage is above the maximum switching voltage for a
particular relay or if the contacts at the current zero crossing are not completely opened. In this case the air gap is still
relatively small and the electric field may be strong enough to cause electrical breakdown, especially with surge voltages
associated with inductive loads. However af ter a few cycles, the contact gap will be suf ficiently large and the energy in the
circuit is too weak to re-ignite the arc.
Type of load and inrush current
The type of the load and its inrush current characteristics together with the switching frequency are important factors that
cause contact welding. Particularly for loads with inrush currents, measure the steady state current and inrush current and
select a relay that provides ample margin of safety. Table shown below illustrates the typical loads and corresponding
inrush currents.
Load Inrush Current and Time
Incandescent Lamp Load
I/IR = 10 to 15 times for
1/3 Sec approx
Mercury Lamp Load
Fluorescent Lamp Load
I/IR = 3 times for
3 to 5 minutes approx
I/IR = 5 to 10 times for
10 Sec approx
Motor Load
Solenoid Load
Coils
I/IR = 5 to 10 times for
0.2 to 0.5 Sec approx
I/IR = 10 to 20 times for
0.1 Sec approx
I/IR = 3 to 10 times
for 1/30 Sec approx
Capacitive Load
I/IR = Inrush Current / Rated Current
I/IR = 20 to 40 times
for 1/30 Sec approx
Application Advice
AC-DC Switching
The switching capacity of a relay is lower for DC loads than for AC. Due to the lack of zero voltage crossing the arc
discharge lasts longer. There is also a contact material transfer phenomena when switching DC loads, which may
cause contact locking / welding.
Polarity Switching
The contact gap in relays with C/O contacts is rather small and the response time may be shorter than the arc
ex tinction time.
This means the N/C contact could be closed before the arc to the N/O contact is ex tinguished. In this case the arc
between the opening contacts will give an electrical connection to the closing contact. The N/C contact will be
electrically connected to N/O contact causing a short circuit. Such circuits must be avoided under all circumstances.
Motor reversing
When reversing a motor by switching between two polarities, the arc between the opening contacts may short to the
closing contacts leading to a short circuit of the power supply. As there is practically no load in the circuit, the current
will be strong enough to maintain the arc and burn the relay contact system. An additional relay should be used to first
disconnect the motor from the power source and then only reversing relay switched af ter the arc has ex tinguished.
Multi Pole relays
Loads and contacts should be connected with the same polarity and potential while using multi-pole relays.
If switching dif ferent potentials within one relay is unavoidable a type with suf ficient dielectric strength has to be
selected. Alternatively a large gap between two adjacent contacts should be created by interposing an unused
contact set between the sets of switching contacts.
Connecting Contacts in Parallel
The switching capacity of a relay cannot be increased by connecting relay poles in parallel. The contacts will not switch
simultaneously. Only one contact will switch the overload and be af fected by the arc. The over load will increase
contact wear or cause welding.
Phase synchronization of AC loads
If the switching of an AC load is synchronized with AC phase, the polarity of the contacts during the switching
procedure will always be the same, leading to material migration and the mechanical locking ef fect as for DC
switching.
Dif ferent contact loads in one relay
Switching two ex tremely dif ferent loads like high loads and micro current loads in one relay should be avoided.
Contaminants generated by switching high power may be deposited on the contacts switching the low load, as there is
no electrical cleaning ef fect on these contacts, they increase the probability of contact failure, put ting the reliability of
the relay in question.
Dummy resistor
When switching low power and dry circuits there is no electrical cleaning ef fect, which may result in contact failure.
Apart from using bifurcated contacts and suitable contact material, the electrical cleaning ef fect can be increased by
adding a dummy resistor in parallel to the load increasing the switching current.
Contacts in Series
Arcs may be ex tinguished by providing a longer air path between the contacts. This can be achieved by connecting
the contacts of a multi pole relay in series thus multiplying the air gap by the number of poles.
Contact Protection Circuit
Use of contact protective devices or protection circuits can suppress the Counter emf to a low level. However, note that
incorrect use will result in an adverse ef fect. Typical contact protection circuits are given in the table below.
(O : Good x : No Good)
Application
Circuit
Features / Others
Device Selection
Contact
r
c
Contact
Diode
circuit
Diode
Contact
Diode and
zener diode
circuit
Contact
Varistor
circuit
Varistor
k
If the toad is a timer, leakage current flows
through the CR circuit causing faulty
operation
* If used with AC vot tage, be sure the
impedance of the toad is suf ficiently
smaller than that of the CR circuit.
If the load is a relay or solenoid, the release
time lengthens. Ef fective when connected
to both contacts if the power supply voltage
is 24 or 48V and the voltage across the load
is 100 to 200V.
Inductive load
c
Inductive load
r
Inductive load
CR circuit
Inductive load
Contact
Inductive load
AC DC
X
X
As a guide in selecting r and c, r: 0.5
to 10per 1V contact voltage c: 0.5 to
1µF per 1 A contact current values
vary depending on the properties of
the load and variations in relay
characteristics. Capacitor c acts to
suppress the discharge the moment
the contacts open. Resistor r acts to
limit the current when the power is
turned on the nex t time. Test to
confirm. Use a capacitor with a
breakdown voltage of 200 to 300V.
Use AC t ype capacitors (nonpolarized) for AC circuits.
The diode connected in parallel causes the
energy stored in the coil to flow to the coil in
the form of current and dissipates it as joule
heat at the resistance component of the
inductive load. This circuit further delays
the retease time compared to the CR
circuit. (2 to 5 times the release time listed
in the catalog)
Use a diode with a reverse
breakdown voltage at least 10 times
the circuit voltage and a forward
current at least as large as the load
current. In electronic circuits where
the circuit voltages are not so high, a
diode can be used with a reverse
breakdown voltage of about 2 to 3
times the power supply voltage.
Ef fective when the release time in the diode
circuit is too long.
Use a zener diode with a zener
voltage about the same as the power
supply voltage.
Using the stable voltage characteristics of
the varistor, this cir cuit pr events
excessively high voltages from being
applied across the contacts. This circuit
also slightly delays the release time.
Ef fective when connected to both contacts
if the power supply voltage is 24 or 48V and
the voltage across the load is 100 to 200V.
Magnetic system
The magnetic circuit consists of non-moving metal parts such as the core, yoke and a movable armature, and an air
gap between the armature and the pole area of the core.
How it works
The magnetic field is generated by a coil consisting of copper wire wound in layers around the bobbin in which there is
an iron core. If voltage is applied to the coil terminals a current (Ohms law I=U/R) flowing through the coil generates a
magnetic field and hence magnetic flux. This induced magnetic field/flux is directly proportional to the coil current and
the number of turns of the coil (H=n x I, H=magnetic field, n=number of turns, I=coil current).
When the magnetic field is strong enough, it will pull in the armature towards the core, closing the magnetic circuit and
actuating the armature. The moving armature directly or indirectly operates the relay contacts.
Although the current is the primary factor in generating flux and the pull force in magnetic system, it is common practice
to work with voltages to select and specif y the relay coil.
Coil energization
The coil must be energized suf ficiently by the power source to generate the required magnetic field and force to
operate the system at all times and under various conditions. Together with the magnetic system, the coil design has a
major ef fect on various parameters such as sensitivity, operating speed, power consumption, ma ximum operating
temperature, etc.
The gradually increasing method of applying rated coil voltage to the coil should not be used. Rated coil voltage should
be impressed fully by means of a switching circuit. To guarantee accurate and stable relay operation, the relay coil has
to be energized with a stabilized power source.
DC Coil The power source for DC operated relays should be in principle be either a bat tery or a DC power supply
with a ma ximum ripple of 5%. Incase where power is supplied by a rectification circuit, the operate, holding and
dropout voltage may be higher and vary with the ripple percentage. With a pulsed coil supply the coil current has to be
above the holding current at all times. If the current drops below this level, the armature will start to open and buzzing of
the relay and increased contact wear will result.
AC Coil For reliable operation of the relay, the coil voltage supply should be with I the range of +10% to –15% of the
rated voltage. Usually all voltages are given for 50Hz supply. For a 60Hz supply the coil impedance is higher, reducing
coil consumption and altering the pick-up voltage (higher than for 50Hz supply). Due to additional losses in Ac coils the
relay ef ficiency is lower and coil temperature raise is higher leading to a reduced coil operating range compared with
DC coils. The waveform of the coil supply should be a sine wave.
The variation of coil resistance is +10% for low nominal coil voltages and up to +15% for high nominal coil voltages
(e.g. 110 VDC) owing to variations in the diameter of the coil wire.
Coil inductance
As a result of the high number of turns, the sof t iron magnetic circuit, and low magnetic resistance, relay coils have a
relatively high inductance.
When switching of f the supply voltage a high voltage peak will be induced in the coil due to the back EMF, making
protection circuits necessary (such as flywheel diodes) to protect coil driving transistors and other electronic
components.
In the case of a circuit with flywheel diodes the inductance keeps the coil current flowing af ter the coil voltage has been
switched of f and the induced coil current is suf ficient to keep the relay in the pulled-in state delaying the dropout.
The AC coil impedance (resistance + reactance) is higher than the resistance and increases with the frequency of the
coil supply. Thus, the coil current at 60Hz is lower compared to a 50Hz supply.
Power consumption
The coil, while energized, consumes power. The power for actuating the relay is dependant on relay design.
The power consumption for DC coils is the product of coil voltage and coil current or according to Ohms law i.e.
P=V*I=V /R=1 R, given in Wat ts.
2
2
The power consumption for AC coils is the product of coil voltage and current and the coil power factor cosø (due to the
coil inductance) V x I x Cosø. The coil power is given in VA, usually for a 50Hz supply.
The lower the input power, lesser the heat generated. This can be particularly important in temperature critical
applications such as those where relays are densely packed on a PCB.
Sensitive Coils:
The higher the coil resistance the lower the coil current for a defined nominal coil voltage. The lower the power
consumption, the higher the sensitivity of the relay.
The advantages of high sensitivity are the possible use of smaller power supplies, lower heat generated by the relay,
and the possibility of direct control by transistors. A disadvantage might be higher sensitivity to electrical and magnetic
interference.
Equipment generating strong magnetic fields such as transformers and loudspeakers, situated near a highly sensitive
or polarized relay, can cause variations in operating voltages. Of ten these problems can be solved by careful
location/orientation of the relay or by providing shielding
Coil heating
A negative ef fect of power consumption is the heating of the coil and, in turn, the entire relay. The coil temperature is a
result of:
l
Ambient temperature
l
Self heating (Due to coil Power consumption= V*I)
l
Induced heating (Due to heat generated by contact system)
l
Magnetization losses (Due to eddy currents)
l
Other sources (Due to components in the vicinity of the relay)
Due to coil heating coil resistance increases. Resistance at elevated temperature is expressed by
Rt= R0[(1+a(T-23)]
0
Where R0 is the resistance at ambient temperature (23 C), T is the elevated temperature and a is the temperature
coef ficient on winding wire (Copper)
During circuit design, care has to be taken that calculations are made under the respective “worst case” conditions,
such as the highest possible coil temperature (ambient temperature, self heating of coil and induced heating with
applied contact load) for pick-up voltage.
Pick up voltage change due to coil temperature rise.
Usually the nominal coil resistance of relay is given for an ambient temperature of 20 deg. C. A coil at this temperature is
called cold coil. A coil heated by ef fects listed above is called a hot coil.
For a given coil, the pick-up current remains the same at any condition. The pick-up current depends on the coil
resistance and the pick-up voltage (Ipick-up= Vpick-up / Rcoil). Coils of most of the relays are made of copper wire. The
resistance of copper wire increases or decreases by 0.4% per degree C. Due to the increase in coil temperature the coil
resistance increases as per the ratio mentioned above. Hence the pick-up voltage for a hot coil should be higher to
generate required pick-up current.
For example in series 61 relays the pick up voltage for 12VDC coil is 9.6 VDC and coil resistance is 400 Ohms at 20 deg.
C. i.e. Ipick-up = 24mA
When the coil temperature is increased to 40 deg. C the coil resistance will be increased to 432 Ohms. Hence the pick
up voltage will be 10.36 VDC (Pick-up current remains the same). i.e. an increase in temperature by 20 deg. C increases
the pick up voltage by 0.76 VDC.
For relays operating with higher duty cycles, the pick-up voltage may increase slightly for each successive cycle due
coil temperature rise.
Coil Drive circuit protection
Normally DC Relays are operated through semi conductor devices. Due to the inductance of the coil, high voltage
peaks are induced (in the form of back emf) when the coil supply is switched of f. To protect the relay control transistors
or contacts of other control relays against this surge voltage, protection in the form of flywheel diodes or other more
Flywheel diodes are diodes connected parallel to the coil in reverse polarity to the coil supply. While discharging the
back emf flywheel diodes provide a low resistance path protecting the driving circuit. The back emf dies gradually by
forming loops. Using a flywheel diode increases the release time of a relay.
In automotive relays a high value resistor is connected across the coil to serve the purpose. The back emf will get
dissipated in the resistor. The impact of parallel resistor on the release time will be less compared to flywheel diode.
AC Coils
AC relays are designed to be operated by alternating current. For the operation of AC relays the power source is almost
always a commercial frequency of 50 Hz, with standard voltages of 6,12,24,48,115 and 230VAC
Since an alternating current decreases to zero every half-cycle (100 times per second for 50Hz), the relay armature
tends to release every half cycle. This continual movement of the armature causes contact chat tering and may lead to
burning or welding of the contacts.
To avoid this chat ter of the armature, part of the pole face is fit ted with a shading or short circuit ring. The flux created in
this short circuit is phase shif ted to the main flux, preventing the total armature flux from periodically decreasing to
zero.
Care is required where power source voltage fluctuations are caused by load switching. If the power source for the
relay operating circuit is connected to the same supply line as motors, solenoids, transformers, and other heav y loads,
the line voltage might drop when these loads are switched. In such cases buzzing might occur causing the relay or
contacts to fail prematurely.
It is of ten necessary to drive DC relay from an AC Voltage source. This can be done using a rectifier circuits. Ripples
caused by rectification should be kept to less than 5%. The operate and release voltage may vary depending on the
percentage of ripple. To check this ef fect, testing should be carried out.
Basics on relay handling
l
Avoid ultrasonic type cleaning of all type of relays.
l
To obtain initial performance through out life, avoid dropping or hit ting the relay
l
Case of the relays should not be removed.
l
Sealed relays should be used for installation where adverse environment conditions, presence of sulphides,
organic chemicals etc.
l
Always apply rated voltage to relay coil.
l
Do not switch voltage & Currents that exceeds the designated values
l
Use flux resistant / Sealed relays for automatic soldering.