Installation Manual Type:LED Power Supply (Families:APC, APV, CEN, CLG, ELN, GSC, HBG, HLG, HLN, HLP, HSG, HVG, LCM, LPC, LPF, LPH, LPHC, LPL, ,PLC, LPV, NPF, OWA, PCD, PLC, PLD, PLM, PLN, PLP, PWM, ULP) Introduction The LED power supply is a dedicated LED driving device that delivers a constant current/voltage or generates an adjustable current controlled by an external dimmer to LEDs. Depending on its types or design concept, some of them not only have PFC capability but also can be located in a harsh environment such as dusty, humid places. Mean Well’s LED power supplies include metal case, plastic case, and PCB types. Installation (1)Before commencing any installation or maintenance work, please disconnect the power supply from the utility. Ensure that it cannot be re-connected inadvertently! (2)Keep proper ventilation around the unit and do not stack any object on it. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source. (3)Mounting orientations other than standard orientation or operate under high ambient temperature may increase the internal component temperature and will require a de-rating in output current. Please refer to the specification sheet to receive the optimum mounting position and information about the de-rating curve. (4)Current rating of an approved primary /secondary cable should be greater than or equal to that of the unit. Please refer to its specification. (5)For LED power supplies with waterproof connectors, verify that the linkage between the unit and the lighting fixture is tight so that water cannot intrude into the system. (6)For dimmable LED power supplies, make sure that your dimming controller is capable of driving these units. For ELN series, either “D” or “P” type, require 40mA each unit; for those with “3 in 1” dimming function, e.g. HLG and LPF series, require 0.15mA each unit. (7)Wiring: The wire color will vary by country, please refer to the table below. North America European Harmonized Live and ACL Black Brown Neutral and ACN white Blue PE and FG (Class I only) Green Green/yellow (a)Connect the FG wire (green or green/yellow) of the LED power supply to PE (green or green/yellow), this step can be skipped when the unit is marked class II, ungrounded. (b)Connect the ACL wire (black or brown) of the LED power supply to Live (black or brown). (c)Connect the ACN wire (white or blue) of the LED power supply to Neutral (white or blue). Installation Manual (8)The maximum number of the LED PSUs that can be connected to a circuit breaker at 230V is shown as below. Model APC-12 APC-16 APC-25 APC-35 APV-12 APV-16 APV-25 APV-35 CEN-60 CEN-75 CEN-100 CLG-60 CLG-100 CLG-150 ELN-30 ELN-60 GSC18 GSC25 GSC40 HBG-60 HBG-100 HBG-160 HBG-240 HLG-40H HLG-60H HLG-80H HLG-100H HLG-120H HLG-150H HLG-185H HLG-240H HLG-320H HLG-600H HLG-60H-C HLG-80H-C HLG-120H-C HLG-185H-C HLN-40H HLN-60H HLN-80H B10 11 8 5 3 11 8 5 4 20 16 11 20 1 1 3 2 26 26 22 18 3 2 1 7 6 2 3 3 2 2 1 1 1 5 3 2 1 7 6 2 B16 17 13 9 5 17 13 9 6 32 25 19 32 3 3 4 3 42 42 36 28 4 4 2 12 9 3 4 5 4 4 2 1 1 8 4 4 2 12 9 3 C10 C16 D10 D16 18 29 37 59 14 23 28 46 9 15 18 30 6 9 12 19 18 29 37 59 14 22 28 44 9 15 18 30 6 10 13 21 20 32 20 32 16 25 16 25 11 19 11 19 20 32 20 32 3 5 6 10 3 5 6 10 5 8 10 16 3 5 7 11 26 42 26 42 26 42 26 42 22 36 22 36 20 32 20 32 5 8 10 16 4 7 8 12 2 3 4 7 13 20 26 41 10 16 20 32 3 6 7 12 5 8 10 16 5 9 10 17 4 7 8 13 4 7 6 11 3 4 5 8 1 2 3 5 1 2 2 3 8 13 16 26 5 8 10 16 4 6 8 13 2 3 4 7 13 20 26 41 10 16 20 32 3 6 7 12 Installation Manual Model HLP-40H HLP-60H HLP-80H HSG-70 HVG-65 (480V) HVG-100 (480V) HVG-150 (480V) HVGC-65 (480V) HVGC-100 (480V) HVGC-150 (480V) LCM-25DA LCM-40 LCM-40DA LCM-60 LCM-60DA LPC-20 LPC-35 LPC-60 LPC-100 LPC-150 LPF-16 LPF-16D LPF-25 LPF-25D LPF-40 LPF-40D LPF-60 LPF-60D LPF-90 LPF-90D LPH-18 LPHC-18 LPL-18 (115V) LPLC-18 (115V) LPV-20 LPV-35 LPV-60 LPV-100 LPV-150 NPF-40 NPF-40D NPF-60 B10 7 6 2 4 7 3 2 7 3 2 16 16 15 15 15 5 2 2 1 2 9 9 8 8 7 7 5 5 2 2 10 8 10 7 5 2 2 1 1 6 6 6 B16 12 9 3 6 12 5 4 12 5 4 26 26 26 25 25 8 4 3 1 3 14 14 12 12 12 12 8 8 4 4 17 13 16 12 8 4 3 2 2 9 9 9 C10 C16 D10 D16 13 20 26 41 10 16 20 32 3 5 6 10 7 11 14 22 12 20 25 40 5 8 10 17 4 6 8 13 12 20 25 40 5 8 10 17 4 6 8 13 27 44 50 80 27 44 29 47 27 44 29 47 20 32 20 32 20 32 20 32 9 14 18 29 4 7 9 15 3 6 7 12 1 2 3 5 4 6 5 8 15 24 30 48 15 24 30 48 13 21 27 46 13 21 27 46 13 20 26 41 13 20 26 41 9 14 18 29 9 14 18 29 4 6 8 13 4 6 8 13 18 28 36 57 14 22 28 44 16 27 20 32 12 20 20 32 9 14 18 29 4 7 9 14 4 6 8 12 2 3 4 7 2 3 4 7 10 16 20 32 10 16 20 32 10 16 20 32 Installation Manual Model NPF-60D NPF90 NPF90D NPF-120 NPF-120D OWA-60U OWA-90U OWA-120U PCD-16A(115V) PCD-16B PCD-25A(115V) PCD-25B PCD-40B PCD-60B PLC- 30 PLC- 45 PLC- 60 PLC- 100 PLD-16A(115V) PLD-16B PLD-25 PLD-40B PLD-60B PLM-12 PLM-25 PLM-40 PLN-20 PLN-30 PLN-45 PLN-60 PLN-100 PLP-20 PLP-30 PLP-45 PLP-60 PWM-40 PWM-60 PWM-90 PWM-120 ULP-150 B10 6 2 2 2 2 1 2 2 36 80 23 50 29 20 40 26 20 1 36 80 45 29 20 100 50 29 61 40 26 20 1 57 40 26 20 6 6 2 2 2 B16 9 3 3 4 4 2 3 4 58 128 37 80 47 32 64 42 32 3 58 128 72 47 32 160 80 47 98 64 42 32 3 92 64 42 32 9 9 3 4 4 C10 C16 D10 10 16 20 3 6 7 3 6 7 4 6 8 4 6 8 2 4 5 3 6 7 4 6 8 36 58 36 80 128 80 23 37 23 50 80 50 29 47 29 20 32 20 40 64 40 26 42 26 20 32 20 3 5 6 36 58 36 80 128 80 50 80 50 29 47 29 20 32 20 100 160 100 50 80 50 29 47 29 61 98 61 40 64 40 26 42 26 20 32 20 3 5 6 61 98 61 40 64 40 26 42 26 20 32 20 10 16 20 10 16 20 3 6 7 4 6 8 4 6 8 D16 32 12 12 13 13 8 12 13 58 128 37 80 47 32 64 42 32 10 58 128 80 47 32 160 80 47 98 64 42 32 10 98 64 42 32 32 32 12 13 13 Installation Manual Note: These calculated values are based on MCB S200 series manufactured by ABB except for HVG/HVGC series, which are calculated by using MCB S260 series of the same manufacturer. (9)For other information about the products, please refer to www.meanwell.com for details. Warning / Caution !! (1)Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do not remove the case of the power supply by yourself! (2)Risk of irreparable damage. LED power supplies with IP64 to IP66 rating must be located indoors or in a location where these units can be sheltered from the rain if outdoors. (3)Please do not install LED power supplies in places with high ambient temperature or close to fire source. Please refer to the specifications about the maximum ambient temperature limitations. (4)Output current and output wattage must not exceed the rated values on the specifications. (5)The FG ( ) must be well connected to PE(protective earth) if the unit equips with it. (6)All MW’s PSUs are designed in accordance with EMC regulations and the related test reports are available by request. Since they are belong to component power supplies and will be installed inside system enclosure, when they are integrated into a system, the EMC characteristics of the end system must be re-verified again. Manufacturer: MEAN WELL ENTERPRISES Co., Ltd. No.28, Wuquan 3rd Road, Wugu District, New Taipei City, Taiwan, 24891 Tel: +886-2-2299-6100 Web: www.meanwell.com