Level Switch LFFS Safety instructions This instrument is constructed and tested according to the current EUdirectives and packed in technically safe condition. In order to maintain this condition and to ensure safe operation, the user must follow the instructions and warnings given in this instruction. During the installation local standards have to be observed. Ignoring the warnings may lead to severe personal injury or substantial damage to property. The product must be operated by trained staff. Correct and safe operation of this equipment is dependent on proper transport, storage, installation and operation. All electrical wiring must conform to local standards and the connection must be made according to the connecting diagrams. R 74 - 03 Before switching on the power supply take care that other equipment is not affected. Ensure that the supply voltage and the conditions in the environment comply with the specification of the device. Before switching off the supply voltage check the possible effects on other equipment and the processing system. When the top cover is removed do not look directly at LED with unshielded eyes or damage to retina may occur !! WARNING This product contains no replaceable parts. In case of malfunction the product must be shipped to Baumer for repair Description The Level Switch LFFS designed to detect levels in tanks, media separation and provide empty-pipe detection or dry-run protection for pumps. The measurement is precise and unaffected by the mounting position in the tank. In the Flex-software a compensation for foam, bubbles and condensate as well as viscous media can be set. A high frequency sweep signal is radiated from the sensor tip into the tank. The media will act as a virtual capacitor, which together with a coil in the sensor head, will form a circuit creating the switch point signal. This virtual capacity will depend of the di-electric value of the media. The Flex-software also features an adjustment facility making the user able to adjust the sensor to a specific media. The Level Switch LFFS measures liquids such as water and beer as well as viscous, sticky fluids, such as honey, youghurt, toothpaste and ketchup. Even dry medias can be measured, eg. sugar or flour. By means of the FlexProgrammer 9701 the output can be configured The Level Switch LFFS is resistent against CIP and SIP agents. to either NPN, PNP or digital output signal. A damping of the output signal can be activated in case of a fluctuating media level, e.g. during Hygienic installation is also possible with the comprehensive range of tank filling. accessories, see the overview at page 6. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 1 Measuring principle The media acts as a virtual capacitor from the sensor tip to the metal shaft or the welding part. Mechanical Installation Welding parts / Clamps Please refer to “Accessories” data sheet. The welding part has an engraved mark or a leak hole. When the product has been mounted and correctly tightened the gland or M12 plug will align with this mark. Make sure that the gland/plug is pointing downwards to prevent fluids from penetrating into the instrument. Mounting Use only the authorised special designed accessories. The product warranty is void when installed with other adapters. Do not use teflon, paper or other gaskets. The PEEK tip against the stainless steel welding part will perform a hygienic tightening provided that the guidelines have been followed. Due to the measuring principle it is essential that the sensor tip can “see” an ample amount of the metal shaft or welding part. Tighten the union with a torque of: Std. version 20...25 Nm. Sliding connection 25...30 Nm. After Installation and Configuration R R Check the leak tightness of the sleeve. 74 - 03 74 - 03 Check the tightness of glands or M12 plugs. Check the tightness of the cover. Dimensional Drawings [mm] dia. 55 Sliding connection length, refer to ordering data Safety chain Read WARNING 58 M16 gland M12 plug AF22 G1/2 44 19 G1/2 Hygienic sliding nipple Washer ring kit, 2 items Type no. 4401 8001 included 31.5 18 G1/2 Hygienic connection 3A/DN38 Hygienic connection O-ring EPDM incl. G1/2 Hygienic, Sliding connection Warning The Level Switch LFFS with sliding connection can be mounted in installations with a static pressure up to 16 bar. To prevent personal injuries and the Level Switch LFFS to slide out of the welding part or mounting accessory it is essential that the safety chain is mounted correctly and undamaged. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 2 Washer Ring Kit for the Sliding Connection Mounting instructions: Washer ring kit for sliding connection, Type no. 4401 8001 dia. 19 1) Clean the sliding shaft. 2) Mount the smallest ring against the media as indicated. 3) Tighten the G1/2 Hygienic sliding nipple at 25...30 Nm. 4) Replace the Washer ring kit when one or both parts are permanently deformed or stick to the shaft of the sliding connection. 19 8.7 CAUTION: This end towards the mounting accessory and the media. Electrical Connection Output Teach-in Sensor 4 5 6 M12 plug: Case 3 1 2 - or (+) + or (-) 12...36 VDC 4 3 1 2 1: Brown 2: White* 3: Blue 4: Black *To avoid unintended Teach-In, be aware not to connect the Teach-In pin or expose it to any electrical noise during normal operation. M12plug Electrical Installation Normally Open PLC Active High 0 mA 50 mA LED - + + + 12.5...36 VDC - PNP Output 50 mA max. 12.5...36 VDC 12.5...36 VDC - Digital Output 50 mA max. NPN Output 50 mA max. Normally Closed PLC 50 mA 0 mA + LED - 12.5...36 VDC PNP Output 50 mA max. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden - Active Low - + 12.5...36 VDC NPN Output 50 mA max. + 12.5...36 VDC Digital Output 50 mA max. Installationsanleitung 5850-020 Seite 3 Configuration Accessories Disconnect the power supply before connecting the FlexProgrammer 9701 to the Level Switch LFFS 1 2 The FlexProgrammer 9701 is a dedicated tool to configure all Baumer configurable Flex-products. 1 2 Type No. 9701-0001 complies: FlexProgrammer Cable with 2 aligator clips Cable from FlexProgrammer to M12 plug for TE2 Cable from FlexProgrammer to M12 Plug for LFFS, LBFS, CPX USB cable CD with the FlexProgram software FlexProgrammer 9701 Red clip 1 2 Black clip Note: Ambient temperature range 0...50°C www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 4 Teach-In Using the FlexProgrammer 9701 Sophisticated settings for Teach-In as well as output type, diagnostics, data logging, tag no. and damping can be configured using the FlexProgrammer 9701. Integrated Help-menus will give full instructions. Teach-In Manually Make sure that power is on before Teach-In. For best Teach-In it is important the product is fixed in the final application. During Teach-In mode the light intensity of the LED will decrease to protect your eyes. Step To do LED Result 1 Connect terminal “Teach-In” to -VDC (T1 or T2) for 3.5 Sec. Flash 1 time per Sec. Ready for Teach-In 2 With “no media present” connect “Teach-In” to -VDC shortly Light for 2 Sec. and then flash Register “empty” state. Note. 3 With “media present” connect “Teach-In” to -VDC shortly Light for 2 Sec. Register “full” state, store and return to normal operation with the new settings If Teach-In for some reason do not succeed, the Level Switch LFFS will enter “Error State” and reload factory settings automatically. The factory settings can always be reloaded by connecting the terminal “Teach-In” to -VDC for more then 6.5 Secs. A reloaded factory settings will be confirmed by pulsing light intensity 3 times. Note. If the media is sticky, foamy, powdery or in other ways leaving parts of the media at the sensor tip this situation has to be established also during the Teach-In process. Otherwise a faulty calibration can be the result. Error State Description LED Result Error State Blinking, 3 short and 1 long blink Can normally be fixed by powering off and on. Alternatively remake the “Teach-In” procedure or make a configuration by the Flexprogrammer 9701. Note. Please observe that the Level Switch LFFS has been factory adjusted to measure liquids with DK-values > 2, such as oil. In case the media has a lower DK-value e.g. powder, a Teach-In procedure must be carried out for the media alternatively a manual adjustment using the FlexProgram software. The adjustment must be made at the medias working temperature to avoid faulty measurements due to temperature drift. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 5 Accessories - Overview R R 74 - 03 74 - 03 LFFS-xx1 LFFS-xx2 LFFS-xx3/4 R 74 - 03 R R 74 - 03 CAM023 MAM02x-xxx 74 - 03 PM023 Welding part 3A/DN38 hygienic 81 26-916 LAM020-1 PM021 VAM 023 R R 74 - 03 74 - 03 SAM020-051-1 PM022-x Welding part 3A/DN38 hygienic 81 26-928 Please refer to the data sheet “FlexBar Accessories” for this accessory. RAM020-1 PM025 RAM020-2 Please refer to the data sheet “Accessories Universal” for these accessories. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 6 The Sliding Connection (Figure 1) External length of sliding connection 1) Insulation 2) 4) Lumpy or sticky media 3) The drawing shows how the sliding connection can be used for at least 4 applications: 1) Mounted at the top of a tank to adjust to a maximum level. 2) Serving as a cooling neck in high media temperature applications. 3) Adjusted to place the sensor tip deeper inside the tank. 4) To reach in through insulation material. It is essential that the max. ambience temperature for the electronics is never exceeded. For ATEX approved products please refer to table 1. Example, how to read Curve 1: A 250 mm sliding connection is mounted in a tank with a total insert length of 150 mm. Hence the external length of the sliding connection will be 250 - 150 = 100 mm. The media temperature will be max. 160 °C. Read the x-axis at 100 mm an the y-axis at 160°C and find that the ambient temperature must be kept below 50°C. In case the radiated heat from the tank will cause a higher ambient temperature at the housing efficient insulation of the tank must be established. The working conditions for the sliding connection in different media temperatures and specified ambient temperatures can be found in curve 1. Media Temperature versus External Length of Sliding Connection (Curve 1) Media Temperature Kølehals for FLS °C Mikael Jensen / 2009-08-26 210 200 190 Tamb max. 40 °C 180 Tamb max. 60 °C 170 Tamb max. 75 °C 160 150 140 130 120 110 100 Tamb max. 85 °C 90 80 70 60 50 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 External length of sliding connection (mm) See figure 1 NB: Std. + 3A/DN38 = 35 mm extenal length www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 7 3-A Certificate The 3-A mark is valid only when the product is mounted in a 3-A marked counter part and installed according to the installation manual. Use also a 3-A marked O-ring or gasket if relevant. The 3-A marked products conforms to the 3-A Sanitary Standard criteria. Materials and surfaces fulfill the FDA demands and are certified by EHEDG. Level Switch LFFS, example EPDM O-rings supplied with 3-A marked products are conform to Sanitary Standard Class II (8% milk fat max.) R 74 - 03 EPDM gaskets supplied with 3-A marked products are conform to Sanitary Standard Class I (8% milk fat max.) PEEK natura Angle > 135 deg. Mounting of 3A Approved and EHEDG certified Products Max. ± 85° 4) 5) 1) 2) Max. ± 175° 3) Installation of 3A approved and EHEDG certified products: 1) Use only a 3A approved counter part. Refer to the data sheet “Accessories” for O-rings, gaskets and other accessories. 2) The inspection hole should be visible and drained. 3) Mount the instrument in a self drained position. 4) Level the inner surface of the pipe with the counter part. 5) Weldings should be grinded to Ra= 0.8 Ex-Configuring Warnings The FlexProgrammer 9701 configuring unit must not be connected to the Level Switch LFFS within the hazardous area. WARNING This product contains no replaceable parts. In case of malfunction the product must be shipped to Baumer for repair. Configuring procedure: a) Disconnect mains from the 4...20 mA loop circuit. b) Disconnect the Level Switch from the circuitry within the hazardous area. c) Uninstall and bring the Level Switch to the safe area. d) Connect the FlexProgrammer 9701 and perform the configuring session. e) Re-install the Level Switch in the hazardous area. f) Connect the power supply to the circuit. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 8 Conditions for Ex-Certification (Table 1) Connection Type Tamb °C Media Temp. max. °C Std. & 3A/DN38 -40...85 85 -40...60 95 {2} -40...40 115 {2} -40...85 85 -40...60 150 {2} -40...40 175 {2} -40...85 85 -40...60 195 {2} -40...40 200 {2} {3} Sliding 100 mm Sliding 250 mm Note Note {2}: Provided that the sensor tip at the instrument is the only part in contact with the media. Note {3}: Max. allowed media temperature. Ex ia IIC T5, ATEX II 1G - Installation A Level Switch LFFS-1xx is Ex ia IIC T5, ATEX II 1G approved for application in hasardous areas in accordance with the current EUdirectives. The product must be installed in accordance with prevailing guidelines for zone 0 with a barrier. A certified Ex ia or isolation barrier with the maximum values Umax = 30 VDC ; Imax = 0.1 A ; Pmax = 0.75 W must be used. Ex-data Supply range 24...30 VDC Temperature class T1...T5: Internal inductivity Li < 10 µH Internal capacity Ci < 33 nF Barrier data U < 30 VDC ; I < 0.1 A ; P < 0.75 W See table 1 Safe area Zone 0/1 PNP out 3 2 1 NO NC COM + C 22...120VDC or 90...253 VAC - B A Level Switch LFFS Isolating Module PROFSI3-B25100-ALG-LS NB: Only valid for PNP output www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 9 Ex tD A20 IP67 T100, ATEX II 1D - Installation A Level Switch LFFS-2xx is Ex tD A20 IP67 T100°C, ATEX II 1D approved for application in hasardous areas in accordance with the current EU-directives. The product must be installed in accordance with prevailing guidelines for zone 20 without a barrier. Ex-data Supply range 12,5...30 VDC, max 100 mA Temperature class T100: See table 1 Out + 12.5...30 VDC External lamp Level Switch LFFS Ex nA II T5, ATEX II 3G - Installation A Level Switch LFFS-3xx is Ex nA II T5, ATEX II 3G approved for application in hasardous areas in accordance with the current EUdirectives. The product must be installed in accordance with prevailing guidelines for zone 2 without a barrier. Ex-data Supply range 12.5...30 VDC, Max. 0.1A Temperature class T1...T5: See table 1 Remote Lamp 12.5..30 VDC Level Switch LFFS www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 10 www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 11 5850 020_EN/2011-09-14 This data sheet may only be reproduced in full. www.baumer.com/process Design und Spezifikationen können ohne Ankündigung geändert werden Installationsanleitung 5850-020 Seite 12