A-Series – General Specifications Compact size and well known for its proven reliability, the A-Series utilizes the hydraulic magnetic principle which provides precise operation and performance even when exposed to extremely hot and/or cold application environments. When aesthetics demand a clean contemporary and functional design, the visi-rocker two-color actuator can be specified. A rockerguard and push-to-reset bezel help prevent inadvertent actuation. A specially constructed version is now available for applications requiring CE markings. The A-Series is used in many telecommunications and marine applications. In addition, these breakers meet CSA Standard 22.2 No. 100 for the Generator & Welder markets. 1-6 poles (handle), 1-3 poles (rocker). 0.02 - 50 amps, up to 277 VAC or 80 VDC, with a choice of time delays, terminals and actuator colors. Agency Certifications UL Recognized UL Standard 1077 Component Recognition Program as Protectors Supplementary (Guide CCN/QVNU2, File E75596) UL Standard 508 Switches, Industrial Control (Guide CCN/NRNT2, File E148683) UL Standard 1500 Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection 34 UL Listed UL Standard 489A Communications Equipment (Guide CCN/DITT, File E189195) CSA Accepted Component Supplementary Protector under Class 3215 30, File 047848 0 000 CSA Standard C22.2 No. 235 TUV Certified EN60934, under License No. R72040875 VDE Certified EN60934, VDE 0642 under File No. 10537 www.carlingtech.com A-Series – General Specifications Electrical Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary Protector. Notes for Table A: 1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 2 Same as note 1, except that backup fuse is limited to 80 A maximum. 3 2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System. 4 Meets the requirements of CSA 22.2 No. 100-04 - Motors and Generators. www.carlingtech.com 35 A-Series – General Specifications Electrical Table B: Lists UL Recognized, CSA Accepted, VDE & TUV Certified configurations & performance capabilities as a Component Supplementary Protector. Notes for Table B: 1 General Purpose Ratings for UL/CSA Only. 2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector. 3 Same as note 2, except that backup fuse is limited to 80 A maximum. 4 Meets the requirements of CSA 22.2 No. 100-04 - Motors and Generators. Table C: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors. A-SERIES TABLE C: UL1500 (Marine Ignition Protected) CIRCUIT CONFIGURATION SERIES MAX. RATING VOLTAGE CURRENT RATING SHORT CIRCUIT CAPACITY (AMPS) WITHOUT BACKUP FUSE APPLICATION CODES FREQUENCY PHASE FULL LOAD AMPS 14 1 DC --- 0.02 - 50 5000 TC1,2,OL1,U1 TC1,2,OL1,U1 32 1 DC --- 0.02 - 50 5000 TC1,2,OL1,U2 TC1,2,OL1,U2 65 DC --- 0.02 - 50 3000 TC1,2,OL1,U1 TC1,2,OL1,U1 125 / 250 50 / 60 12 0.02 - 50 1500 TC1,2,OL1,U1 TC1,2,OL1,U1 250 50 / 60 1 0.02 - 30 1000 TC1,2,OL1,U1 TC1,2,OL1,U1 UL CSA Notes for Table C: 1 Available with special catalog number only (consult factory). 2 2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System. Table D: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment (Guide DITT, File E189195), under UL489A. Notes for Table C: 1 Parallel Pole Construction 36 www.carlingtech.com A-Series – General Specifications Electrical Maximum Voltage Current Ratings Standard Voltage Coils Auxiliary Switch Rating Insulation Resistance Dielectric Strength Resistance, Impedance Mechanical 277VAC 50/60 Hz, 80VDC Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0, 40.0, 50.0. Other ratings available consult ordering scheme. DC-6V, 12V; AC-120V, Other ratings available, consult ordering scheme. SPDT; 10.1 A - 250VAC, 1.0 A-65VDC/0.5 A - 80 VDC, 0.1A - 125VAC (with gold contacts). Minimum: 100 Megohms at 500 VDC UL, CSA - 1500V 60 Hz for one minute between all electrically isolated terminals. A-Series rocker circuit breakers comply with the 8mm spacing & 3750V dielectric requirements from hazardous voltage to operator accessible surfaces per EN 60950 and VDE 0805. Values from Line to Load Terminal based on Series Trip Circuit Breaker. Endurance Trip Free Trip Indication 10,000 ON-OFF operations @ 6 per minute; with rated Current & Voltage. All A-Series Circuit Breakers will trip on overload, even when the actuator is forcibly held in the ON position. The operating actuator moves positively to the OFF position when an overload causes the circuit breaker to trip. When mid-trip handle is specified, the handle moves to the mid position on electrical trip of the circuit breaker. When mid-trip handle with alarm switch is specified, the handle moves to the mid position & the alarm switch actuates when the circuit breaker is electrically tripped. Physical Number of Poles 1 - 6 Poles (handle) and 1-3 poles (rocker) at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps. Internal Circuit Configurations Series, (with or without auxiliary switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only with or without auxiliary switch. Weight Approximately 65 grams/pole. (Approximately 2.32 ounces/pole) Standard Colors Housing - Black; Actuator- See Ordering Scheme. Environmental Pulse Tolerance Curves www.carlingtech.com Designed and tested in accordance with requirements of specification MIL-PRF-55629 & MIL-STD-202 as follows: Shock Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Test Condition “I”. Instantaneous and ultra-short curves tested @ 90% of rated current. Vibration Withstands 0.060" excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Instantaneous and ultrashort curves tested at 90% of rated current. Moisture Resistance Method 106D; ten 24-hour cycles @ + 25°C to +65°C, 80-98% RH.56 days @ +85°C, 85% RH. Salt Spray Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs). Thermal Shock Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C). Operating Temperature -40° C to +85° C 37 A-Series Handle UL Recognized – Ordering Scheme A A 3 – B 0 – 10 – 450 – 1 B 1 – C 1 Series 2 Actuator 3 Poles 4 Circuit 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES A 2 ACTUATOR 1 A Handle, one per pole B Handle, one per multipole unit S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES 1 One 2 Two 3 4 Three Four 4 CIRCUIT A2 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) 3 D Shunt Trip (Current) E3 Shunt Trip (Voltage) F3 G3 H3,4 5 AUXILIARY/ALARM SWITCH 5 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 5 6 FREQUENCY & DELAY 03 DC 50/60Hz, Switch Only 106 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 6 50/60Hz Instantaneous 20 21 50/60Hz Ultra Short 22 50/60Hz Short0 24 50/60Hz Medium 26 50/60Hz Long K3,4 5 6 Five Six Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 8 9 S.P.S.T., 0.093 Q.C. Term.(Gold Contacts) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 30 31 32 34 36 427 447 467 527 547 567 DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush 6 7 Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. B: Handle location as viewed from front of breaker: 2 pole - left pole 3 pole - center pole 4 pole - two handles at center poles 5 pole - three handles at center poles 6 pole - four handles at center poles S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A - supplied with standard half shells. 35-50A - supplied with extended boat (B-Style) half shells. On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA Accepted & TUV Certified to 50 amps. 8 VDE Certification available with single pole breakers with DC Delay only. UL Recognition and CSA Accepted available in one and two pole breakers. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.. 10 Terminal Code 1: VDE Certification up to 25 amps and UL Recognition and CSA Certification up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5, E and H (Bus Type) with VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used. 12 Terminal Code L: VDE Certified available up to 12A. UL Recognized & CSA Accepted available up to 30A. 13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B and C. 14 Terminal Code Q not available with VDE certification. 15 Single pole only. 38 7 Current Rating 8 Terminal 9 Actuator Color 7 CURRENT RATING (AMPERES) 020 0.020 225 0.250 025 0.025 230 0.300 030 0.030 235 0.350 035 0.035 240 0.400 040 0.040 245 0.450 045 0.045 250 0.500 050 0.050 255 0.550 055 0.055 260 0.600 060 0.060 265 0.650 065 0.065 270 0.700 070 0.070 275 0.750 075 0.075 280 0.800 080 0.080 285 0.850 085 0.085 290 0.900 090 0.090 295 0.950 095 0.095 410 1.000 210 0.100 512 1.250 215 0.150 415 1.500 220 0.200 517 1.750 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 710 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE)6 A06 6 DC A32 32 DC J12 12 AC A12 12 DC A48 48 DC J18 18 AC A18 18 DC A65 65 DC J24 24 AC A24 24 DC J06 6 AC J48 48 AC 8 TERMINAL9 110 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 11 Screw 8-32 (Bus Type) 3 4 Screw 10-32 w/upturned lugs 11 Screw 10-32 (Bus Type) 5 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend B Screw M5 w/upturned lugs C Screw M4 w/upturned lugs 9 ACTUATOR COLOR & LEGEND Actuator Color I-O ON-OFF White A B Black C D Red F G Green H J Blue K L Yellow M N Gray P Q Orange R S U Black (short handle)15 T 11 Agency Approval 10 Mounting/ Barriers 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 6358 6408 6458 6508 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) 0.250 Q.C./ Solder Lug M6 Threaded Stud Push-In Stud Screw M4 w/upturned lugs and 30° bend Screw M4 (Bus Type) and 30° bend Printed Circuit Board Terminals Push-On 0.110 Tab (Q.C.) E11 F G H11 L12 M11 Q14 R T11 P13 S13 Dual 1 2 3 4 5 6 7 8 9 Legend Color Black White White White White Black Black Black White 10 MOUNTING/BARRIERS MOUNTING STYLE Threaded Inserts, 2 per pole 1 6-32 x 0.195 inches A 6-32 X 0.195 inches 2 ISO M3 x 5mm B ISO M3 x 5mm (multipole only) Front panel Snap-In, 0.75” wide bezel 5 without Handleguard 6 without Handleguard (multipole only) Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96" wide; multipole units have .105" bezel overhang on all sides 8 without Handleguard, 1-pole 0.96" wide; (multipole only) .105" bezel overhang on all sides BARRIERS no yes no yes no yes no yes 11 AGENCY APPROVAL C UL Recognized & CSA Accepted D VDE Certified, UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted www.carlingtech.com A-Series Handle UL489A – Ordering Scheme A A 1 – B 0 – 14 – 450 – 1 B 1 – M T 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES A 2 ACTUATOR1 A Handle, one per pole S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES2 1 One 2 Two 3 Three 4 Four 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH2 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 7 8 9 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 523 543 563 DC, Short,Hi-Inrush DC, Medium, Hi-Inrush DC, Long, Hi-Inrush 7 CURRENT RATING (AMPERES) 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280 285 290 295 410 512 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 1.250 415 517 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 1.500 1.750 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 710 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 6354 6404 6454 6504 10.500 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 7 Current Rating 8 Terminal 9 Actuator Color 8 TERMINAL5 16 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 37 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 57 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 ACTUATOR COLOR LEGEND ON-OFF White B Black D Red G Green J Blue L Yellow N Gray Q Orange S 10 Black (short handle) U Dual 1 2 3 4 5 6 7 8 9 10 Mounting/ Barriers 9 B F G H M7 P8 Q9 11 Max. Appl. Rating 12 Agency Approval Screw 10-32 (Bus Type) and 30° bend Screw M5 w/upturned lugs Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) M6 Threaded Stud Printed Circuit Board Terminals Push-In Stud Legend Color Black White White White White Black Black Black White 10 MOUNTING/BARRIERS MOUNTING STYLE Threaded Insert, 2 per pole 1 6-32 x 0.195 inches A 6-32 X 0.195 inches 2 ISO M3 x 5mm B ISO M3 x 5mm (multipole only) Front panel Snap-In, 0.75” wide bezel 5 without Handleguard 6 without Handleguard (multipole only) Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96" wide; multipole units have .105" bezel overhang on all sides 8 without Handleguard, 1-pole 0.96" wide; (multipole only) .105" bezel overhang on all sides BARRIERS no yes no yes no yes no yes 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL T UL489A LISTED K UL489A LISTED, VDE CERTIFIED J UL489A LISTED, TUV CERTIFIED Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. 2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole. 3 VDE Certified to 30 amps. UL489A Listed to 50 amps. 4 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers. 5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9 G, H, M and Q. 6 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps. 7 Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used. 8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing. 9 Terminal Code Q not available with VDE certification. 10 Single pole only. www.carlingtech.com 39 A-Series Handle WORLD – Ordering Scheme A A 3 – B 0 – 14 – 450 – 1 A 1 – P 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES A 2 ACTUATOR 1 A Handle, one per pole S Mid-Trip Handle, one per pole T Mid-Trip Handle, one per pole & Alarm Switch 3 POLES 1 One 2 Two 3 4 Three Four 4 CIRCUIT A2 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) 5 AUXILIARY/ALARM SWITCH 0 w/o Aux Switch 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY 03 DC 50/60Hz, Switch Only 106 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 206 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short0 24 50/60Hz Medium 26 50/60Hz Long D3 E3 H3,4 5 6 Five Six Shunt Trip (Current) Shunt Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil 5 4 30 31 32 34 36 427 447 467 527 547 567 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush 7 Current Rating 8 Terminal 7 CURRENT RATING (AMPERES) 210 0.100 285 0.850 215 0.150 290 0.900 220 0.200 295 0.950 225 0.250 410 1.000 230 0.300 512 1.250 235 0.350 415 1.500 240 0.400 517 1.750 245 0.450 420 2.000 250 0.500 522 2.250 255 0.550 527 2.750 260 0.600 430 3.000 265 0.650 435 3.500 270 0.700 440 4.000 275 0.750 445 4.500 280 0.800 450 5.000 40 455 460 465 470 475 480 485 490 495 610 710 611 711 612 712 8 TERMINAL9 110 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 11 Screw 8-32 (Bus Type) 3 4 Screw 10-32 w/upturned lugs 11 Screw 10-32 (Bus Type) 5 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend B C E11 F G H11 R T11 11 Agency Approval 10 Mounting/ Barriers 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 11.500 12.000 12.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE)6 A06 6 DC A32 32 DC J12 12 AC A12 12 DC A48 48 DC J18 18 AC A18 18 DC A65 65 DC J24 24 AC A24 24 DC J06 6 AC J48 48 AC 9 ACTUATOR COLOR & LEGEND Actuator Color I-O Dual White A 1 Black C 2 Red F 3 Green H 4 Blue K 5 Yellow M 6 Gray P 7 Orange R 8 Notes: 1 Actuator Code: A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units. S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, and H. T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C. 2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole. 6 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10, 20 & 30. 7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA Accepted & TUV Certified to 50 amps. 8 Available up to two poles with AC or DC delays. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G and H. 10 Terminal Code 1: TUV Certification up to 30 amps, but not recommended over 20 amps. 11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers. These breakers are ONLY TUV Certified when the washers are used. 9 Actuator Color 613 614 615 616 617 618 620 622 624 625 630 6358 6408 6458 6508 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M5 w/upturned lugs Screw M4 w/upturned lugs Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) Screw M4 w/upturned lugs and 30° bend Screw M4 (Bus Type) and 30° bend Legend Color Black White White White White Black Black Black 10 MOUNTING/BARRIERS MOUNTING STYLE Threaded Inserts, 2 per pole 1 6-32 x 0.195 inches A 6-32 X 0.195 inches 2 ISO M3 x 5mm B ISO M3 x 5mm (multipole only) Front panel Snap-In, 0.75” wide bezel 5 without Handleguard 6 without Handleguard (multipole only) Front panel Snap-In, 0.96” wide bezel 7 without Handleguard, 1-pole 0.96" wide; multipole units have .105" bezel overhang on all sides 8 without Handleguard, 1-pole 0.96" wide; (multipole only) .105" bezel overhang on all sides BARRIERS no yes no yes no yes no yes 11 AGENCY APPROVAL P TUV Certified, UL Recognized & CSA Accepted Q UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted www.carlingtech.com A-Series Sealed Toggle UL Recognized – Ordering Scheme A M 1 – B 0 – 10 – 450 – 1 0 1 – C 1 Series 2 Actuator 3 Poles 4 Circuit 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES A 2 ACTUATOR 1 M Sealed Toggle, one per unit 3 POLES 1 One 2 Two 3 Three 4 CIRCUIT A2 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) D3 Shunt Trip (Current) E3 Shunt Trip (Voltage) F3 G3 H3,4 5 AUXILIARY/ALARM SWITCH 5 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 5 6 FREQUENCY & DELAY 03 DC 50/60Hz, Switch Only 106 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 206 50/60Hz Instantaneous 21 50/60Hz Ultra Short 22 50/60Hz Short0 24 50/60Hz Medium 26 50/60Hz Long K3,4 Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 8 9 S.P.S.T., 0.093 Q.C. Term.(Gold Contacts) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 30 31 32 34 36 427 447 467 527 547 567 DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush 6 7 Notes: 1 Actuator Code M: Handle location as viewed from front of panel: 2 pole - right pole 3 pole - center pole 2 Switch Only circuits, rated up to 50 amps and 3 poles. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 4 Consult factory for available Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 5 Auxiliary Switch available on Series Trip & Switch Only circuits, limited to 30 amps. On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole. 6 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA Accepted & TUV Certified to 50 amps. 8 UL Recognition and CSA Certification available on one and two pole breakers. 9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.. 10 Terminal Code 1: UL Recognition and CSA Certification up to 30 amps, but not recommended over 20 amps. 11 Terminal Code L : available up to 30A. 12 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 50 amps, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with Circuit Codes A, B and C. www.carlingtech.com 7 Current Rating 8 Terminal 7 CURRENT RATING (AMPERES) 020 0.020 225 0.250 025 0.025 230 0.300 030 0.030 235 0.350 035 0.035 240 0.400 040 0.040 245 0.450 045 0.045 250 0.500 050 0.050 255 0.550 055 0.055 260 0.600 060 0.060 265 0.650 065 0.065 270 0.700 070 0.070 275 0.750 075 0.075 280 0.800 080 0.080 285 0.850 085 0.085 290 0.900 090 0.090 295 0.950 095 0.095 410 1.000 210 0.100 512 1.250 215 0.150 415 1.500 220 0.200 517 1.750 9 Legend Plate 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 710 10 Mounting/ Barriers 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE)6 A06 6 DC A32 32 DC J12 12 AC A12 12 DC A48 48 DC J18 18 AC A18 18 DC A65 65 DC J24 24 AC A24 24 DC J06 6 AC J48 48 AC 8 TERMINAL9 110 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 3 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 5 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend B Screw M5 w/upturned lugs C Screw M4 w/upturned lugs E F G H L11 M Q R T P12 S12 11 Agency Approval 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 6358 6408 6458 6508 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) 0.250 Q.C./ Solder Lug M6 Threaded Stud Push-In Stud Screw M4 w/upturned lugs and 30° bend Screw M4 (Bus Type) and 30° bend Printed Circuit Board Terminals Push-On 0.110 Tab (Q.C.) 9 LEGEND PLATE 0 No legend plate 10 MOUNTING/BARRIERS MOUNTING STYLE 1 Standard Hex Nut A Standard Hex Nut (multipole only) BARRIERS no yes 11 AGENCY APPROVAL C UL Recognized & CSA Accepted 41 A-Series Rocker UL Recognized – Ordering Scheme A F 1 – B 0 – 24 – 630 – 2 3 1 – D 1 Series 2 Actuator 3 Poles 4 Circuit 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES A 2 ACTUATOR Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend E Indicate ON, no legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend H Indicate OFF, no legend Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend P Indicate OFF, no legend Single color J Vertical legend K Horizontal legend L No legend 1 3 POLES 2 1 One 2 Push-To-Reset , Single color R Vertical legend U Horizontal legend V No legend Two 3 4 CIRCUIT A3 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) D4 Shunt Trip (Current) E4 Shunt Trip (Voltage) F4 G4 H 4, 5 5 AUXILIARY/ALARM SWITCH 6, 7 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 5 6 FREQUENCY & DELAY 03 DC 50/60Hz, Switch Only 10 8 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 8 50/60Hz Instantaneous 20 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long K 4, 5 Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil S.P.S.T., 0.093 Q.C. Term.(Gold Contacts) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 6 7 8 9 30 31 32 34 36 42 44 46 52 54 56 Three 9 9 9 9 9 DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 3 Switch Only circuits, rated up to 50 amps & 3 poles, are available with VDE Certification when tied to a protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 7 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 and 20. 9 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA Accepted & TUV Certified to 50 amps. 10 Series Trip current ratings: VDE Certification available with single pole breakers with DC Delay only. UL Recognition & CSA Accepted available in one and two pole breakers. 11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 12 Terminal Code 1: VDE Certification up to 25 amps and UL Recognition and CSA Accepted up to 30 amps, but not recommended over 20 amps. 13 Terminal Codes 3, 5 E & H (Bus Type) with VDE, are supplied with Lock Washers; Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used. 14 VDE Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps. 15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Certification with Circuit Codes A, B and C. 16 Terminal Code Q not available with VDE. 17 Terminal Code S used on voltage coil circuit constructions only. 18 Color shown is visi and legend with remainder of rocker black. 19 Dual = ON-OFF/I-O legend with actuator. None = no legend on actuator 20 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R, & U. Legend on Push-to-reset bezel/shroud matches Visi-color of rocker with actuator codes N & O. Rockerguard available with actuator codes C through L. 42 7 Current Rating 8 Terminal 9 Actuator Color 10 Mounting/ Barriers 7 CURRENT RATING (AMPERES) 420 2.000 225 0.250 020 0.020 522 2.250 230 0.300 025 0.025 527 2.750 235 0.350 030 0.030 430 3.000 240 0.400 035 0.035 435 3.500 245 0.450 040 0.040 440 4.000 250 0.500 045 0.045 445 4.500 255 0.550 050 0.050 450 5.000 260 0.600 055 0.055 455 5.500 265 0.650 060 0.060 460 6.000 270 0.700 065 0.065 465 6.500 275 0.750 070 0.070 470 7.000 280 0.800 075 0.075 475 285 0.850 080 0.080 7.500 290 0.900 085 0.085 480 8.000 295 0.950 090 0.090 485 8.500 410 1.000 095 0.095 490 9.000 512 1.250 210 0.100 495 9.500 415 1.500 215 0.150 610 10.000 517 1.750 220 0.200 710 10.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE) J12 12 AC A32 32 DC A06 6 DC J18 18 AC A48 48 DC A12 12 DC J24 24 AC A65 65 DC A18 18 DC J48 48 AC J06 6 AC A24 24 DC 8 TERMINAL 11 112 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs Screw 8-32 (Bus Type) 313 4 Screw 10-32 w/upturned lugs Screw 10-32 (Bus Type) 513 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend B Screw M5 w/upturned lugs C Screw M4 w/upturned lugs 9 ACTUATOR COLOR & LEGEND Actuator or _______Marking: _______ Visi-Color 12 I-O ON-OFF Dual12 White A B 1 Black C D 2 Red F G 3 Green H J 4 Blue K L 5 Yellow M N 6 Gray P Q 7 Orange R S 8 E13 F G H13 L14 M13 P15 Q16 R S17 T 11 Agency Approval 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 635 10 640 10 645 10 650 10 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) 0.250 Q.C./ Solder Lug M6 Threaded Studs Printed Circuit Board Terminals Push-In Stud Screw M4 w/upturned lugs and 30° bend Push-On 0.110 Tab (Q.C.) Screw M4 (Bus Type) and 30° bend ____Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange 10 MOUNTING/BARRIERS20 BARRIERS STANDARD ROCKER BEZEL,Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes ROCKERGUARD & PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes FRONT PANEL SNAP-IN BRACKET, 0.744” wide bezel 8 without Rockerguard (single pole units only) no H with Rockerguard (single pole units only) no FRONT PANEL SNAP-IN BRACKET, 0.96” wide bezel 9 without Rockerguard (single pole units only) no J with Rockerguard (single pole units only) no 11 AGENCY APPROVAL C UL Recognized & CSA Accepted D VDE Certified, UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted www.carlingtech.com A-Series Rocker UL489A – Ordering Scheme A F 1 – B 0 – 14 – 450 – 1 3 1 – M T 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 1 SERIES A 2 ACTUATOR 1 Two Color Visi-Rocker C Indicate ON, vertical legend D Indicate ON, horizontal legend F Indicate OFF, vertical legend G Indicate OFF, horizontal legend Push-To-Reset, Visi-Rocker N Indicate OFF, vertical legend O Indicate OFF, horizontal legend Single color J Vertical legend K Horizontal legend Push-To-Reset , Single color R Vertical legend U Horizontal legend 3 POLES2 1 One 2 Two 3 Three 6 FREQUENCY & DELAY 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 7 8 9 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 52 54 56 DC, Short,Hi-Inrush DC, Medium, Hi-Inrush DC, Long, Hi-Inrush 7 CURRENT RATING (AMPERES) 210 215 220 225 230 235 240 245 250 255 260 265 270 275 280 285 290 295 410 512 0.100 0.150 0.200 0.250 0.300 0.350 0.400 0.450 0.500 0.550 0.600 0.650 0.700 0.750 0.800 0.850 0.900 0.950 1.000 1.250 www.carlingtech.com 415 517 420 522 527 430 435 440 445 450 455 460 465 470 475 480 485 490 495 610 1.500 1.750 2.000 2.250 2.750 3.000 3.500 4.000 4.500 5.000 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 710 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 6355 6405 6455 6505 8 Terminal 9 Actuator Color 8 TERMINAL5 16 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 37 Screw 8-32 (Bus Type) 4 Screw 10-32 w/upturned lugs 57 Screw 10-32 (Bus Type) 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 ACTUATOR COLOR & LEGEND Actuator or Marking Visi-Color 10 ON-OFF Dual 10 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH3 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 7 Current Rating 10.500 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 10 Mounting/ Barriers 9 B F G H M7 P8 Q9 11 Max. Appl. Rating 12 Agency Approval Screw 10-32 (Bus Type) and 30° bend Screw M5 w/upturned lugs Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) M6 Threaded Stud Printed Circuit Board Terminals Push-In Stud Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange 10 MOUNTING/BARRIERS 11 STANDARD ROCKER BEZEL BARRIERS Threaded Insert, 2 per pole 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes ROCKERGUARD & PUSH-TO-RESET BEZEL Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel 8 without Rockerguard (single pole units only) no H with Rockerguard (single pole units only) no FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel 9 without Rockerguard (single pole units only) no J with Rockerguard (single pole units only) no 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL T UL489A Listed K UL489A Listed, VDE Certified J UL489A Listed, TUV Certified Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 4 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers. 5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps. 7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certified when the washers are used. 8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing. 9 Terminal Code Q not available with VDE certification. 10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I-O legend. 11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes N & O. Rockerguard available with actuator codes C through K. 43 A-Series Flat Rocker UL Recognized – Ordering Scheme A 1 1 – B 0 – 24 – 630 – 2 3 1 – E 1 Series 2 Actuator 3 Poles 4 Circuit 5 Aux/Alarm Switch 6 Frequency & Delay 1 SERIES A 2 ACTUATOR Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend 1 3 POLES 2 1 One 2 Two 3 4 CIRCUIT A3 Switch Only (No Coil) B Series Trip (Current) C Series Trip (Voltage) D4 Shunt Trip (Current) E4 Shunt Trip (Voltage) F4 G4 H 4, 5 5 AUXILIARY/ALARM SWITCH 6, 7 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 4 S.P.D.T., 0.110 Q.C. Term. (Gold Contacts) 5 6 FREQUENCY & DELAY 03 DC 50/60Hz, Switch Only 10 8 DC Instantaneous 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 8 50/60Hz Instantaneous 20 21 50/60Hz Ultra Short 22 50/60Hz Short 24 50/60Hz Medium 26 50/60Hz Long K 4, 5 Three Relay Trip (Current) Relay Trip (Voltage) Dual Coil with Shunt Trip Voltage Coil Dual Coil with Relay Trip Voltage Coil 8 9 S.P.S.T., 0.093 Q.C. Term.(Gold Contacts) S.P.S.T., 0.139 Solder Lug S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 30 31 32 34 36 42 44 46 52 54 56 DC, 50/60Hz Instantaneous DC, 50/60Hz Ultra Short DC, 50/60Hz Short DC, 50/60Hz Medium DC, 50/60Hz Long 50/60Hz Short, Hi-Inrush 50/60Hz Medium, Hi-Inrush 50/60Hz Long, Hi-Inrush DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush 6 7 9 9 9 9 9 Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 3 Switch Only circuits, rated up to 50 amps & 3 poles. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650. 4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum. 5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only. 6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells. 7 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20. 9 Available with Circuit Codes B & D only. UL Recognized, CSA Accepted & TUV Certified to 50 amps. 10 UL Recognition, CSA Acceptance & TUV Certification available in one and two pole breakers. 11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q. 12 Terminal Code 1: Available up to 30 amps, but not recommended over 20 amps. 13 Terminal Codes 3, 5 E & H (Bus Type) with TUV, are supplied with Lock Washers; Terminal Code M (M6 Threaded Stud) with TUV is supplied with Lock and Flat Washers. These breakers are only TUV Certified when the washers are used. 14 TUV Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps. 15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 50 amps with UL Recognition, CSA Accepted & TUV Certification, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B and C. 16 Terminal Code S used on voltage coil circuit constructions only. 17 Color shown is visi and legend with remainder of rocker black, Dual = ON-OFF/I-O legend. 18 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6. 19 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are available in ink stamping only. 44 7 Current Rating 8 Terminal 9 Actuator Color 10 Mounting/ Barriers 7 CURRENT RATING (AMPERES) 420 2.000 225 0.250 020 0.020 522 2.250 230 0.300 025 0.025 527 2.750 235 0.350 030 0.030 430 3.000 240 0.400 035 0.035 435 3.500 245 0.450 040 0.040 440 4.000 250 0.500 045 0.045 445 4.500 255 0.550 050 0.050 450 5.000 260 0.600 055 0.055 455 5.500 265 0.650 060 0.060 460 6.000 270 0.700 065 0.065 465 6.500 275 0.750 070 0.070 470 7.000 280 0.800 075 0.075 475 285 0.850 080 0.080 7.500 290 0.900 085 0.085 480 8.000 295 0.950 090 0.090 485 8.500 410 1.000 095 0.095 490 9.000 512 1.250 210 0.100 495 9.500 415 1.500 215 0.150 610 10.000 517 1.750 220 0.200 710 10.500 OR VOLTAGE COIL (NOMINAL RATED VOLTAGE) J12 12 AC A32 32 DC A06 6 DC J18 18 AC A48 48 DC A12 12 DC J24 24 AC A65 65 DC A18 18 DC J48 48 AC J06 6 AC A24 24 DC 8 TERMINAL 11 112 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 13 Screw 8-32 (Bus Type) 3 4 Screw 10-32 w/upturned lugs 13 Screw 10-32 (Bus Type) 5 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend B Screw M5 w/upturned lugs C Screw M4 w/upturned lugs 9 ACTUATOR COLOR & LEGEND Actuator or _______Marking: _______ Visi-Color 17 I-O ON-OFF Dual17 White A B 1 Black C D 2 Red F G 3 Green H J 4 Blue K L 5 Yellow M N 6 Gray P Q 7 Orange R S 8 E13 F G H13 L14 M13 P15 Q R S16 T 11 Agency Approval 611 711 612 712 613 614 615 616 617 618 620 622 624 625 630 635 10 640 10 645 10 650 10 11.000 11.500 12.000 12.500 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 J65 65 AC K20 120 AC L40 240 AC Screw M4 (Bus Type) Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) 0.250 Q.C./ Solder Lug M6 Threaded Studs Printed Circuit Board Terminals Push-In Stud Screw M4 w/upturned lugs and 30° bend Push-On 0.110 Tab (Q.C.) Screw M4 (Bus Type) and 30° bend ____Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange 10 MOUNTING/BARRIERS18 BARRIERS STANDARD ROCKER BEZEL,Threaded Insert, 2 per pole FLAT ROCKER ACTUATOR 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes RECESSED OFF SIDE ROCKER ACTUATOR 19 5 6-32 x 0.195 inches no E 6-32 x 0.195 inches (multi-pole units only) yes 6 ISO M3 x 5mm no F ISO M3 x 5mm (multi-pole units only) yes PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes 11 AGENCY APPROVAL C UL Recognized & CSA Accepted E TUV Certified, UL Recognized & CSA Accepted I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted www.carlingtech.com A-Series Flat Rocker UL 489A – Ordering Scheme A 1 1 – B 0 – 14 – 630 – 2 3 1 – M T 1 Series 2 Actuator 3 Poles 5 Aux/Alarm Switch 4 Circuit 6 Frequency & Delay 2 ACTUATOR 1 Two Color Visi-Rocker 1 Indicate OFF, vertical legend 2 Indicate OFF, horizontal legend Single color 3 Vertical legend 4 Horizontal legend Push-To-Reset, Visi-Rocker 5 Indicate OFF, vertical legend 6 Indicate OFF, horizontal legend Push-To-Reset , Single color 7 Vertical legend 8 Horizontal legend 2 Two 3 Three 4 CIRCUIT B Series Trip (Current) 5 AUXILIARY/ALARM SWITCH 3,4 0 w/o Aux Switch 1 S.P.D.T., 0.093 Q.C. Term. 2 S.P.D.T., 0.110 Q.C. Term. 3 S.P.D.T., 0.139 Solder Lug 6 FREQUENCY & DELAY 11 DC Ultra Short 12 DC Short 14 DC Medium 16 DC Long 7 8 9 S.P.S.T., 0.110 Q.C. Term.(Gold Contacts) S.P.S.T., 0.187 Q.C. Term. S.P.D.T., 0.187 Q.C. Term. 52 54 56 DC, Short,Hi-Inrush DC,Medium, Hi-Inrush DC, Long, Hi-Inrush Notes: 1 Push-To-Reset actuators have OFF portion of rocker shrouded. 2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker. 3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50 amps are supplied with extended boat (B-Style) half shells. 4 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole. 5 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers. 6 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9 G, H, M and Q. 7 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps. 8 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certified when the washers are used. 9 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing. 10 Terminal Code Q not available with VDE certification. 11 Color shown is visi and legend with remainder of rocker black, Dual = ON-OFF/I-O legend. 12 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6. 13 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are available in ink stamping only. www.carlingtech.com 8 Terminal 9 Actuator Color 7 CURRENT RATING (AMPERES) 285 0.850 210 0.100 290 0.900 215 0.150 295 0.950 220 0.200 410 1.000 225 0.250 512 1.250 230 0.300 415 1.500 235 0.350 517 1.750 240 0.400 420 2.000 245 0.450 522 2.250 250 0.500 527 2.750 255 0.550 430 3.000 260 0.600 435 3.500 265 0.650 440 4.000 270 0.700 445 4.500 275 0.750 450 5.000 280 0.800 1 SERIES A 3 POLES 2 1 One 7 Current Rating 8 TERMINAL 6 17 Push-On 0.250 Tab (Q.C.) 2 Screw 8-32 w/upturned lugs 8 Screw 8-32 (Bus Type) 3 4 Screw 10-32 w/upturned lugs 8 Screw 10-32 (Bus Type) 5 6 Screw 8-32 w/upturned lugs and 30° bend 7 Screw 8-32 (Bus Type) and 30° bend 8 Screw 10-32 w/upturned lugs and 30° bend 9 Screw 10-32 (Bus Type) and 30° bend 9 ACTUATOR COLOR & LEGEND Actuator or Visi-Color 11 Marking ON-OFF Dual11 White B 1 Black D 2 Red G 3 Green J 4 Blue L 5 Yellow N 6 Gray Q 7 Orange S 8 10 Mounting/ Barriers 12 11 Max. Appl. Agency Approval Rating 613 614 615 616 617 618 620 622 624 625 630 635 5 640 5 645 5 650 5 13.000 14.000 15.000 16.000 17.000 18.000 20.000 22.000 24.000 25.000 30.000 35.000 40.000 45.000 50.000 455 460 465 470 475 480 485 490 495 610 710 611 711 612 712 5.500 6.000 6.500 7.000 7.500 8.000 8.500 9.000 9.500 10.000 10.500 11.000 11.500 12.000 12.500 B C F Screw M5 w/upturned lugs Screw M4 w/upturned lugs Screw M5 w/upturned lugs and 30° bend Screw M5 (Bus Type) and 30° bend Screw M5 (Bus Type) M6 Threaded Studs Printed Circuit Board Terminals Push-In Stud G H8 M8 P9 Q10 Marking Color: Single Color Visi-Rocker Black White White n/a White Red White Green White Blue Black Yellow Black Gray Black Orange 10 MOUNTING/BARRIERS12 BARRIERS STANDARD ROCKER BEZEL,Threaded Insert, 2 per pole FLAT ROCKER ACTUATOR 1 6-32 x 0.195 inches no A 6-32 X 0.195 inches (multi-pole units only) yes 2 ISO M3 x 5mm no B ISO M3 x 5mm (multi-pole units only) yes 13 RECESSED OFF SIDE ROCKER ACTUATOR 5 6-32 x 0.195 inches no E 6-32 x 0.195 inches (multi-pole units only) yes 6 ISO M3 x 5mm no F ISO M3 x 5mm (multi-pole units only) yes PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole 3 6-32 x 0.195 inches no C 6-32 x 0.195 inches (multi-pole units only) yes 4 ISO M3 x 5mm no D ISO M3 x 5mm (multi-pole units only) yes 11 MAXIMUM APPLICATION RATING M 80 DC 12 AGENCY APPROVAL T UL489A Listed J UL489A Listed, TUV Certified 45 A-Series Handle – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only. 46 www.carlingtech.com A-Series Handle – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Alarm Switch available with .110 x .020 QC & solder lug terminals only. www.carlingtech.com 47 A-Series Handle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ± 0.20 [.51] unless otherwise specified. 3 For agency code P = .150 [3.81]. 48 www.carlingtech.com A-Series Handle – Front Panel Snap-In Mounting Style 5 Notes: 1 All dimensions are in inches [millimeters]. 2 Recommended panel thickness: .040 [1.02] to .100 [2.54]. 3 Tolerance ±.020 [.51] unless otherwise specified. www.carlingtech.com 49 A-Series Handle – Front Panel Snap-In Mounting Style 7 Notes: 1 All dimensions are in inches [millimeters]. 2 Recommended panel thickness: .040 [1.02] to .100 [2.54]. 3 Tolerance ±.020 [.51] unless otherwise specified. 50 www.carlingtech.com A-Series Sealed Toggle – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. www.carlingtech.com 51 A-Series Rocker – Circuit & Terminal Diagrams Notes: 1 All dimensions are in inches [millimeters]. 2 Tolerance ±.020 [.51] unless otherwise specified. 3 Schematic shown represents current trip circuit. 4. Circuits shown for >30 amps / VDE. 52 www.carlingtech.com A-Series Rocker – Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal orientation on indicate OFF is opposite of indicate ON. 2 For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 All dimensions are in inches [millimeters]. 4 Tolerance ± 0.20 [.51] unless otherwise specified. www.carlingtech.com 53 A-Series Rocker Snap-In Bracket – Form & Fit Drawings Notes: 1 Dimensions apply to all variations shown. Notice that circuit breaker line & load terminal 2 For pole orientation with horizontal legend, rotate front view clockwise 90°. Orientation on indicate "OFF" is opposite of indicate "ON" 3 Recommended panel thickness: .04 0 [1.02] to .100 [2.54] 4 All dimensions are in Inches [millimeters]. 5 Tolerance ±.020 [.51] unless otherwise specified. 54 www.carlingtech.com A-Series Flat Rocker – Form & Fit Drawings Notes: 1 All dimensions are in inches [millimeters]. 2 For pole orientation with horizontal legend, rotate front view clockwise 90°. 3 Tolerance ± 0.20 [.51] unless otherwise specified. www.carlingtech.com 55 A-Series PC Terminal Diagrams Notes: 1 Drawing illustrates A-Series with VDE certification. 2 All dimensions are in inches [millimeters]. 3 Tolerance ± 0.20 [.51] unless otherwise specified. 56 www.carlingtech.com