A-Series Circuit Breaker Datasheet

A-Series
Circuit Breaker
Well known for their proven reliability, the A-Series hydraulic/
magnetic circuit breakers are compact, temperature stable and
designed for precision operation in OEM markets requiring
general purpose as well as full load amp applications. The A-Series
circuit breakers are offered with ratings from 0.02 to 50 amps,
up to 277VAC or 80VDC and are available with several choices of
pole configurations, time delays, terminals, with a wide range of
standard colors, imprinting and actuator styles.
Actuator styles include handle for 1-6 poles and rocker for 1-3 pole
construction. When front panel operation and aesthetics demand
a clean, contemporary design, a two-color or solid color Visi-Rocker
actuator, indicating either the ON mode or the TRIPPED/OFF mode,
is ideally suitable. The new Rockerguard bezel and push-to-reset
bezel, which help prevent inadvertent actuation, is also available.
Features:
ŠŠ Specially constructed version available for applications
requiring CE markings
ŠŠ The metal toggle option was tested to MIL-PRF-55629C for
ingress protection when mounted in a panel, and also meets
IP68 requirement.
Applications:
ŠŠ Marine
ŠŠ Telecommunications
ŠŠ Military
ŠŠ Renewable Energy Systems
ŠŠ Generators & Welder
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: [email protected] • www.carlingtech.com
1 POLE - PUSH TO RESET
2 POLE - HANDLE
1 POLE - TOGGLE
Agency Certifications:
ŠŠ UL Recognized – UL Standard 508, 1077, 1500
ŠŠ UL Listed – UL Standard 489A
ŠŠ CSA Accepted
ŠŠ TUV Certified
ŠŠ VDE Certified
2 | A-Series Circuit Breaker - General Specifications
Electrical
Mechanical
Maximum Voltage
Current Ratings
Standard Voltage Coils
Auxiliary Switch Rating
Insulation Resistance
Dielectric Strength
Resistance, Impedance
277VAC 50/60 Hz, 80VDC
Standard current coils: 0.100, 0.250, 0.500, 0.750, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0, 20.0, 25.0, 30.0, 35.0, 40.0, 50.0. Other ratings
available - consult ordering scheme.
DC-6V, 12V; AC-120V, Other ratings available, consult ordering scheme.
SPDT; 10.1 A - 250VAC,
1.0 A-65VDC/0.5 A - 80 VDC,
0.1A - 125VAC (with gold contacts).
Minimum: 100 Megohms at 500 VDC
UL, CSA - 1500V 60 Hz for one minute between all electrically isolated terminals. A-Series rocker circuit breakers comply with the 8mm spacing & 3750V dielectric requirements from hazardous voltage to operator accessible surfaces per EN 60950 and VDE 0805.
Values from Line to Load Terminal - based on Series Trip Circuit Breaker.
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Endurance
Trip Free
Trip Indication
10,000 ON-OFF operations @ 6 per minute; with rated Current & Voltage.
All A-Series Circuit Breakers will trip on overload, even when the actuator is forcibly held in the ON position.
The operating actuator moves positively to the OFF position when an overload causes the circuit breaker to trip. When mid-trip handle is specified, the handle moves to the mid position on electrical trip of the circuit breaker. When mid-trip handle with alarm switch is specified, the handle moves to the mid position & the alarm switch actuates when the circuit breaker is electrically tripped.
Physical
Number of Poles
Internal Circuit Config.
Weight
Standard Colors
1 - 6 Poles (handle) and 1-3 poles (rocker) at 30 Amps or less. 1 and 2 poles at 31 Amps thru 50 Amps.
Series, (with or without auxiliary switch), Shunt and Relay with current or voltage trip coils, Dual Coil, Switch Only with or without auxiliary switch.
Approximately 65 grams/pole. (Approximately 2.32 ounces/pole)
Housing - Black; Actuator- See Ordering Scheme.
Environmental
Pulse Tolerance Curves
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth while carrying rated current per Method 213, Test Condition “I”. Instantaneous and ultra-short curves tested @ 90% of rated current.
Vibration
Withstands 0.060” excursion from 10-55 Hz, and 10 Gs 55-500 Hz, at rated current per Method 204C, Test Condition A. Instantaneous and ultrashort curves tested at 90% of rated current.
Moisture Resistance
Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56 days @ +85°C, 85% RH.
Salt Spray
Method 101, Condition A (90-95% RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock
Method 107D, Condition A (Five cycles @ -55°C to +25°C to +85°C to +25°C).
Operating Temperature -40° C to +85° C
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Table A: Lists UL Recognized & CSA Accepted configurations and performance capabilities as a Component Supplementary Protector.
Handle
Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
2 Same as note 1, except that backup fuse is limited to 80 A maximum.
3 2 pole protector required (with one pole per power line) for: 125/250 VAC, 1 pole protector required for : 125 VAC, 1Ø Power System.
4 Satisfies the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
4 | A-Series Circuit Breaker - General Specifications
Electrical Tables
Table B: Lists UL Recognized, CSA Accepted, VDE & TUV Certified configurations & performance capabilities as a Component
Supplementary Protector.
1
3
2
3
2
3
2
Notes:
1 General Purpose Ratings for UL/CSA Only.
2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
3 Same as note 2, except that backup fuse is limited to 80 A maximum.
4 Satisfies the requirements of clause 11.2.8.2.5 of CSA STD C22.2 No 100 for the use of supplementary protectors with portable generators.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Circuit Breaker - General Specifications | 5
Electrical Tables
Table C: Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for Marine
Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft Electrical Devices,
Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
A-SERIES TABLE C: UL1500 (Marine Ignition Protected)
VOLTAGE
CIRCUIT
CONFIGURATION
CURRENT
RATING
SHORT CIRCUIT
CAPACITY (AMPS)
APPLICATION CODES
MAX. RATING
FREQUENCY
PHASE
FULL LOAD AMPS
WITHOUT BACKUP
FUSE
UL
CSA
14 1
DC
---
0.02 - 50
5000
TC1,OL1,U1
TC1,OL1,U1
32 1
65
DC
---
0.02 - 50
5000
TC1,OL1,U2
TC1,OL1,U2
DC
---
0.02 - 50
3000
TC1,OL1,U1
TC1,OL1,U1
125
50 / 60
1
0.02 - 50
3000
TC1,OL1,U2
TC1,OL1,U2
125 / 250
50 / 60
12
0.02 - 50
3000
TC1,OL1,U2
TC1,OL1,U2
250
50 / 60
1
0.02 - 30
1500
TC1,OL1,U1
TC1,OL1,U1
SERIES
Notes:
Notes:
1 Available with
special catalog number only (consult factory).
2 2 pole protector required
(with one
per Special
power line)
for 125 /Number
250 VAC.Only
1 pole(consult
protectorfactory)
required for 125 VAC 1 phase power system
1 Available
with
Catalog
2 2 pole protector required (with one per power line) for 125 / 250 VAC. 1 pole protector required for 125 VAC 1 phase power system
Table D: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A.
Notes:
1 Parallel Pole Construction
Agency Certifications
UL Recognized
UL Standard 1077
Component Recognition Program as Protectors Supplementary
(Guide CCN/QVNU2, File E75596)
CSA Accepted
Component Supplementary
Protector under Class 3215 30, File 047848 0 000 CSA Standard C22.2 No. 235
UL Standard 508
Switches, Industrial Control
(Guide CCN/NRNT2, File E148683)
TUV Certified
EN60934, under License No. R72040875
UL Standard 1500
Protectors, Supplementary for Marine Electrical & Fuel Systems (Guide PEQZ2, File E75596) Ignition Protection
VDE Certified
EN60934, VDE 0642 under File
No. 10537
UL Listed
UL Standard 489A
Communications Equipment
(Guide CCN/DITT, File E189195)
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
6 | A-Series Handle UL Recognized – Ordering Scheme
A A 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
10
5
Aux/Alarm
Switch
6
Frequency
& Delay
1 SERIES
A
2 ACTUATOR
A
B
S
T
1
Handle, one per pole
Handle, one per multipole unit
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
3
4
One
Two
5
6
Three
Four
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
F3
G3
H3,4
K3,4
Five
Six
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
5 AUXILIARY/ALARM SWITCH5
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03 10 11 12 14 16 20 21
22 24 26 DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
5
7
8
9
S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
30
31
32
34
36
427
447 467 527 547 567
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole
3 pole - center pole
4 pole - two handles at center poles
5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the
breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a
protected pole (Circuit Code B, C, D or H.), For .02 to 30 amps,
select Current Code 630. For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 50A amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require 30VA minimum power to trip and are rated for intermittent duty only.
5 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A - supplied with
standard half shells. 35-50A - supplied with extended boat (B-Style) half shells.
On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA Accepted & TUV Certified to 50 amps.
8 VDE Certification available with single pole breakers with DC Delay only. UL Recognition and CSA Accepted available in one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q..
10 Terminal Code 1: VDE Certification up to 25 amps and UL Recognition and CSA
Certification up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5, E and H (Bus Type) with VDE, are supplied with Lock Washers,
and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat
Washers. These breakers are only VDE Certified when the washers are used.
12 Terminal Code L: VDE Certified available up to 12A. UL Recognized & CSA Accepted available up to 30A.
13 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL Recognition and CSA Accepted, with Circuit
Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are
available up to 40 amps with UL Recognition and CSA Accepted with Circuit Codes A, B and C.
14 Terminal Code Q not available with VDE certification.
15 Single pole only.
AMPERES
0200.020
0250.025
0300.030
0350.035
0400.040
0450.045
0500.050
0550.055
0600.060
0650.065
0700.070
0750.075
0800.080
0850.085
0900.090
0950.095
2100.100
2150.150
2200.200
8
9
Terminal Actuator
Color
10
Mounting/
Barriers
C
11
Agency
Approval
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635835.000
640840.000
645845.000
650850.000
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12
J18
J24
J48
J65 65 AC
K20 120 AC
L40 240 AC
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)6
CODE
0
1
2
4
1 B 1
7 CURRENT RATING (AMPERES)
4 CIRCUIT
A 2
B
C
D 3
E3
7
Current Rating
CODE
3 POLES
1
2
450
AMPERES
A06 6 DC
A12 12 DC
A18 18 DC
A24 24 DC
8 TERMINAL9
110
2
311
4
511
6
7
8
9
B
C
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
12 AC
18 AC
24 AC
48 AC
E11 Screw M4 (Bus Type)
F
Screw M5 w/upturned lugs and 30° bend
G
Screw M5 (Bus Type)
and 30° bend
H11 Screw M5 (Bus Type)
L12 0.250 Q.C./ Solder Lug
M11 M6 Threaded Stud
Q14 Push-In Stud
R
Screw M4 w/upturned lugs and 30° bend
11
T Screw M4 (Bus Type)
and 30° bend
P13 Printed Circuit Board Terminals
S13 Push-On 0.110 Tab (Q.C.)
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
ON-OFF
White
AB
Black
CD
Red
FG
Green
HJ
Blue
KL
Yellow
MN
Gray
PQ
Orange
RS
15
Black (short handle) TU
Dual
Legend Color
1Black
2White
3White
4White
5White
6Black
7Black
8Black
9White
10 MOUNTING/BARRIERS
1
A
2
B
5
6
7
8
MOUNTING STYLEBARRIERS
Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multipole only)
yes
Front panel Snap-In, 0.75” wide bezel
without Handleguardno
without Handleguard (multipole only)
yes
Front panel Snap-In, 0.96” wide bezel
without Handleguard, 1-pole 0.96” wide;
no
multipole units have .105” bezel overhang on all sides
without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
11 AGENCY APPROVAL
C
UL Recognized & CSA Accepted
D
VDE Certified, UL Recognized & CSA Accepted
E
TUV Certified, UL Recognized & CSA Accepted
I
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Handle UL489A – Ordering Scheme | 7
A A 1
1
Series
2
Actuator
3
Poles
B 0
4
Circuit
5
Aux/Alarm
Switch
14
6
Frequency
& Delay
2 ACTUATOR1
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
3 POLES2
1
2
3
4
One
Two
Three
Four
Series Trip (Current)
5 AUXILIARY/ALARM SWITCH2
0
1
2
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
6 FREQUENCY & DELAY
11 12 14 16 DC Ultra Short
DC Short
DC Medium
DC Long
7
8
9
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
523 DC, Short,Hi-Inrush
543 DC, Medium, Hi-Inrush
563 DC, Long, Hi-Inrush
AMPERES
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
8 TERMINAL5
16
2
37
4
57
6
7
8
10
Mounting/
Barriers
M T
11
Max. Appl.
Rating
12
Agency
Approval
1
A
2
B
5
6
7
8
MOUNTING STYLEBARRIERS
Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multipole only)
yes
Front panel Snap-In, 0.75” wide bezel
without Handleguardno
without Handleguard (multipole only)
yes
Front panel Snap-In, 0.96” wide bezel
without Handleguard, 1-pole 0.96” wide;
no
multipole units have .105” bezel overhang on all sides
without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
11 MAXIMUM APPLICATION RATING
M
7 CURRENT RATING (AMPERES)
CODE
9
Actuator
Color
10 MOUNTING/BARRIERS
4 CIRCUIT
B
1 B 1
8
Terminal
9 ACTUATOR COLOR & LEGEND
Actuator Color
ON-OFF
Dual
Legend Color
White
B1 Black
Black
D2 White
Red
G3White
Green
J4White
Blue
L5White
Yellow
N6Black
Gray
Q7Black
Orange
S8Black
Black (short handle)10
U9White
1 SERIES
A
A
S
T
450
7
Current Rating
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
9
B
F
G
H
M7 P8
Q9
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635335.000
640340.000
645345.000
650350.000
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
M6 Threaded Stud
Printed Circuit Board Terminals
Push-In Stud
80 DC
12 AGENCY APPROVAL
T
K
J
UL489A LISTED
UL489A LISTED, VDE CERTIFIED
UL489A LISTED, TUV CERTIFIED
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided un-assembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker.
2 On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
3 VDE Certified to 30 amps. UL489A Listed to 50 amps.
4 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9 G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
30 amps with VDE Certification and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certification.
10 Single pole only.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
8 | A-Series Handle WORLD – Ordering Scheme
A A 3
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
14
5
Aux/Alarm
Switch
6
Frequency
& Delay
2 ACTUATOR1
Handle, one per pole
Handle, one per multi-pole unit
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
3 POLES
1
2
3
4
One
Two
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
5 AUXILIARY/ALARM SWITCH5
0
2
w/o Aux Switch
S.P.D.T., 0.110 Q.C. Term.
6 FREQUENCY & DELAY
03 10 11 12 14 16 20 21
22 24 26 5
6
Three
Four
4 CIRCUIT
A 2
B
C
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
D 3
E3
H3,4
Five
Six
Shunt Trip (Current)
Shunt Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
4
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
30
31
32
34
36
427
447 467 527 547 567
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE
AMPERES
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635835.000
640840.000
645845.000
650850.000
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12
J18
J24
J48
J65 65 AC
K20 120 AC
L40 240 AC
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)6
CODE
AMPERES
A06 6 DC
A12 12 DC
A18 18 DC
A24 24 DC
1 A 1
8
Terminal
8 TERMINAL9
1 SERIES
A
A
B
S
T
450
7
Current Rating
12 AC
18 AC
24 AC
48 AC
110
2
311
4
511
6
7
8
9
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
Screw 10-32 (Bus Type) and 30° bend
9
Actuator
Color
10
Mounting/
Barriers
B
C
E11
F
G
H11
R
T11
P
11
Agency
Approval
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
Screw M4 (Bus Type)
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
Screw M4 w/upturned lugs and 30° bend
Screw M4 (Bus Type)
and 30° bend
9 ACTUATOR COLOR & LEGEND
Actuator Color
I-O
Dual
Legend Color
White
A1 Black
Black
C2 White
Red
F3White
Green
H4White
Blue
K5White
Yellow
M6Black
Gray
P7Black
Orange
R8Black
10 MOUNTING/BARRIERS
1
A
2
B
5
6
7
8
MOUNTING STYLEBARRIERS
Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multipole only)
yes
Front panel Snap-In, 0.75” wide bezel
without Handleguardno
without Handleguard (multipole only)
yes
Front panel Snap-In, 0.96” wide bezel
without Handleguard, 1-pole 0.96” wide;
no
multipole units have .105” bezel overhang on all sides
without Handleguard, 1-pole 0.96” wide; yes
(multipole only) .105” bezel overhang on all sides
11 AGENCY APPROVAL
P
TUV Certified, UL Recognized & CSA Accepted
Q
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
Notes:
1 Actuator Code:
A: Handle tie pin spacer(s) and retainers provided unassembled with multi-pole units.
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with circuit codes B, C, D, E, and H.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of the breaker. Available with circuit codes B & C.
2 Switch Only circuits, rated up to 50 amps and 6 poles, and only available when tied to a
protected pole (Circuit Code B, C, D or H.), For .01 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils
require
30VA minimum power to trip and are rated for intermittent duty only.
5 On multi-pole breakers, one auxilary switch is supplied, mounted in the extreme right pole.
6 Separate pole type voltage coils not rated for continuous duty. Available only with delay
codes 10, 20 & 30.
7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA
Accepted & TUV Certified to 50 amps.
8 Available up to two poles with AC or DC delays.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30
amps are only available with Terminal Codes 5, 9, G and H.
10 Terminal Code 1: TUV Certification up to 30 amps, but not recommended over 20 amps.
11 Terminal Codes 3, 5 , 7, 9, E, G and H (Bus Type) are supplied with Lock Washers.
These breakers are only TUV Certified when the washers are used.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Rocker UL 489A – Ordering Scheme | 9
A F 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
14
5
Aux/Alarm
Switch
6
Frequency
& Delay
1 SERIES
A
450
7
Current Rating
1 3 1
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
8 TERMINAL5
2 ACTUATOR1
Two Color Visi-Rocker
C
Indicate ON, vertical legend
D
Indicate ON, horizontal legend
F
Indicate OFF, vertical legend
G
Indicate OFF, horizontal legend
Single color
J
Vertical legend
K
Horizontal legend
Push-To-Reset, Visi-Rocker
N
Indicate OFF,
vertical legend
O
Indicate OFF,
horizontal legend
Push-To-Reset , Single color
R
Vertical legend
U
Horizontal legend
16
2
37
4
57
6
7
8
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
9
B
F
G
H
M7
P8
Q9
M T
11
Max. Appl.
Rating
12
Agency
Approval
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
M6 Threaded Stud
Printed Circuit Board Terminals
Push-In Stud
9 ACTUATOR COLOR & LEGEND
Actuator or
Visi-Color10
White
Black
Red
Green
Blue
Yellow
Gray
Orange
10 MOUNTING/BARRIERS11
3 POLES2
1
2
One
3
Two
Three
4 CIRCUIT
B
Series Trip (Current)
5 AUXILIARY/ALARM SWITCH3
0
1
2
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
6 FREQUENCY & DELAY
11 12 14 16 DC Ultra Short
DC Short
DC Medium
DC Long
7
8
9
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
52 54 56
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
AMPERES
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
1
A
2
B
3
C
4
D
8
H
9
J
STANDARD ROCKER BEZEL BARRIERS
Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 X 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
ROCKERGUARD & PUSH-TO-RESET BEZEL
Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
FRONT PANEL SNAP-IN BRACKET, 0.744” [18.90mm] wide bezel
without Rockerguard (single pole units only)
no
with Rockerguard (single pole units only)
no
FRONT PANEL SNAP-IN BRACKET, 0.96” [24.48mm] wide bezel
without Rockerguard (single pole units only)
no
with Rockerguard (single pole units only)
no
11 MAXIMUM APPLICATION RATING
M
7 CURRENT RATING (AMPERES)
CODE
Marking:
Marking Color
ON-OFFDual10 Single Color
Visi-Rocker
B1Black White
D2White n/a
G3White Red
J4White Green
L5White Blue
N6Black Yellow
Q7Black Gray
S8Black Orange
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635435.000
640440.000
645445.000
650450.000
80 DC
12 AGENCY APPROVAL
T
K
J
UL489A LISTED
UL489A LISTED, VDE CERTIFIED
UL489A LISTED, TUV CERTIFIED
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or
mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and
Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certified when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certification.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U.
Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes
N & O. Rockerguard available with actuator codes C through K
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
10 | A-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Alarm Switch available with .110 x .020 Q.C. & Solder Lug Terminals Only.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Handle – Circuit & Terminal Diagrams | 11
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Alarm Switch available with .110 x .020 QC & solder lug terminals only.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
12 | A-Series Handle – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ± 0.20 [.51] unless otherwise specified.
3 For agency code P = .150 [3.81].
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Handle – Front Panel Snap-In Mounting Style 5 | 13
Notes:
1 All dimensions are in inches [millimeters].
2 Recommended panel thickness: .040 [1.02] to .100 [2.54].
3 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
14 | A-Series Handle – Front Panel Snap-In Mounting Style 7
Notes:
1 All dimensions are in inches [millimeters].
2 Recommended panel thickness: .040 [1.02] to .100 [2.54].
3 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Sealed Toggle UL Recognized – Ordering Scheme | 15
A M 1
1
Series
2
Actuator
3
Poles
B 0
4
Circuit
5
Aux/Alarm
Switch
10
2 ACTUATOR1
Sealed Toggle, one per unit
3 POLES
1
2
3
One
Two
Three
4 CIRCUIT
A 2
B
C
D 3
E3
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
5 AUXILIARY/ALARM SWITCH5
0
1
2
4
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03 10 11 12 14 16 20 21
22 24 26 DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
F3
G3
H3,4
K3,4
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
5
7
8
9
S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
30
31
32
34
36
427
447 467 527 547 567
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE
AMPERES
0200.020
0250.025
0300.030
0350.035
0400.040
0450.045
0500.050
0550.055
0600.060
0650.065
0700.070
0750.075
0800.080
0850.085
0900.090
0950.095
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635835.000
640840.000
645845.000
650850.000
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12
J18
J24
J48
J65 65 AC
K20 120 AC
L40 240 AC
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)6
CODE
AMPERES
A06 6 DC
A12 12 DC
A18 18 DC
A24 24 DC
7
Current Rating
1 0 1
8
Terminal
8 TERMINAL9
1 SERIES
A
M
450
6
Frequency
& Delay
12 AC
18 AC
24 AC
48 AC
110
2
3
4
5
6
7
8
9
B
C
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
9
Actuator
Color
10
Mounting/
Barriers
C
11
Agency
Approval
E
Screw M4 (Bus Type)
F
Screw M5 w/upturned lugs and 30° bend
G
Screw M5 (Bus Type)
and 30° bend
H
Screw M5 (Bus Type)
L12 0.250 Q.C./ Solder Lug
M
M6 Threaded Stud
Q
Push-In Stud
R
Screw M4 w/upturned lugs and 30° bend
T
Screw M4 (Bus Type)
and 30° bend
P12 Printed Circuit Board Terminals
S
Push-On 0.110 Tab (Q.C.)
9 LEGEND PLATE
0
No legend plate
10 MOUNTING/BARRIERS
1
A
MOUNTING STYLEBARRIERS
Standard Hex Nut
no
Standard Hex Nut (multipole only)
yes
11 AGENCY APPROVAL
C
I
UL Recognized & CSA Accepted
UL Recognized, CSA Accepted, UL1500 Ignition Protected
Notes:
1 Actuator Code M: Handle location as viewed from front of panel:
2 pole - right pole
3 pole - center pole
2 Switch Only circuits, rated up to 50 amps and 3 poles. Only available when tied to a
protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps,
select Current Code 650.
3 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
4 Consult factory for available Dual Coil options, as special catalog number is required. With
Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only.
5 Auxiliary Switch available on Series Trip & Switch Only circuits, limited to 30 amps.
On multi-pole breakers, one auxiliary switch is supplied, mounted in the extreme right pole.
6 Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
7 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA
Accepted & TUV Certified to 50 amps.
8 UL Recognition and CSA Certification available on one and two pole breakers.
9 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over
30 amps are only available with Terminal Codes 5, 9, B, F, G, H, M and Q.
10 Terminal Code 1: UL Recognition and CSA Certification up to 30 amps, but not
recommended over 20 amps.
11 Terminal Code L : available up to 30A.
12 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to
50 amps, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P
(Printed Circuit Board) are available up to 40 amps with Circuit Codes A, B and C.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
16 | A-Series Sealed Toggle – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Rocker UL Recognized – Ordering Scheme | 17
A F 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
24
5
Aux/Alarm
Switch
6
Frequency
& Delay
2 ACTUATOR1
Push-To-Reset , Single color
R
Vertical legend
U
Horizontal legend
V
No legend
Two Color Visi-Rocker
C
Indicate ON, vertical legend
D
Indicate ON, horizontal legend
E
Indicate ON, no legend
F
Indicate OFF, vertical legend
G
Indicate OFF, horizontal legend
H
Indicate OFF, no legend
Push-To-Reset, Visi-Rocker
N
Indicate OFF,
vertical legend
O
Indicate OFF,
horizontal legend
P
Indicate OFF,
no legend
Single color
J
Vertical legend
K
Horizontal legend
L
No legend
3 POLES
2
One
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03 10 11 12 14 16 20 21
22 24 26 3
Two
5 AUXILIARY/ALARM
SWITCH6,7
0
1
2
4
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
F4
G4
H4,5
K4,5
Three
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
5
S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
7
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
8
S.P.S.T., 0.187 Q.C. Term.
9
S.P.D.T., 0.187 Q.C. Term.
30
31
32
34
36
429
449 469 529 549 569
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE
AMPERES
112
2
313
4
513
6
7
8
9
B
C
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
9
Actuator
Color
E13
F
G
H13
L14
M13
P15
Q16
R
S17
T
10
Mounting/
Barriers
D
11
Agency
Approval
Screw M4 (Bus Type)
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
0.250 Q.C./ Solder Lug
M6 Threaded Stud
Printed Circuit BoardTerminals
Push-In Stud
Screw M4 w/upturned lugs and 30° bend
Push-On 0.110 Tab (Q.C.)
Screw M4 (Bus Type)
and 30° bend
9 ACTUATOR COLOR & LEGEND
4 CIRCUIT
A 3
B
C
D 4
E4
2 3 1
8
Terminal
8 TERMINAL11
1 SERIES
A
1
630
7
Current Rating
0200.020
0250.025
0300.030
0350.035
0400.040
0450.045
0500.050
0550.055
0600.060
0650.065
0700.070
0750.075
0800.080
0850.085
0900.090
0950.095
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
6351035.000
6401040.000
6451045.000
6501050.000
A06 6 DC
A12 12 DC
A18 18 DC
A24 24 DC
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12
J18
J24
J48
J65 65 AC
K20 120 AC
L40 240 AC
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)8
12 AC
18 AC
24 AC
48 AC
Actuator or
Visi-Color12
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Marking:
Marking Color
I-OON-OFF Dual12 Single Color
Visi-Rocker
AB 1Black
White
CD 2White
n/a
FG 3White
Red
HJ 4White
Green
KL 5White
Blue
MN 6Black
Yellow
PQ 7Black
Gray
RS 8Black
Orange
10 MOUNTING/BARRIERS20
1
A
2
B
3
C
4
D
8
H
9
J
STANDARD ROCKER BEZEL,Threaded Insert, 2 per poleBARRIERS
6-32 x 0.195 inches
no
6-32 X 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
ROCKERGUARD & PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
FRONT PANEL SNAP-IN BRACKET, 0.744” wide bezel
without Rockerguard (single pole units only)
no
with Rockerguard (single pole units only)
no
FRONT PANEL SNAP-IN BRACKET, 0.96” wide bezel
without Rockerguard (single pole units only)
no
with Rockerguard (single pole units only)
no
11 AGENCY APPROVAL
C
D
E
I
UL Recognized & CSA Accepted
VDE Certified, UL Recognized & CSA Accepted
TUV Certified, UL Recognized & CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles, are available only when tied to a protected
pole (Circuit Code B, C, D or H.), For .02 to 30 amps, select Current Code 630.
For 35 - 50 amps, select Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required.
With Shunt construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes
10 and 20.
9 Available with Circuit Codes B & D only. VDE Certified to 30 amps. UL Recognized, CSA
Accepted & TUV Certified to 50 amps.
10 Series Trip current ratings: VDE Certification available with single pole breakers with DC Delay only. UL Recognition & CSA Accepted available in one and two pole breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: VDE Certification up to 25 amps and UL Recognition and CSA Accepted up to 30 amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with VDE, are supplied with Lock Washers; Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only VDE Certified when the washers are used.
14 VDE Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL Recognition and CSA Accepted, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL Recognition and CSA Certification with Circuit Codes A, B and C.
16 Terminal Code Q not available with VDE.
17 Terminal Code S used on voltage coil circuit constructions only.
18 Color shown is visi and legend with remainder of rocker black.
19 Dual = ON-OFF/I-O legend with actuator. None = no legend on actuator
20 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R, & U. Legend on Push-to-reset bezel/shroud matches Visi-color of rocker with actuator codes N & O.
Rockerguard available with actuator codes C through L.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
18 | A-Series Flat Rocker UL Recognized – Ordering Scheme
A 1 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
24
5
Aux/Alarm
Switch
6
Frequency
& Delay
112
2
313
4
513
6
7
8
9
B
C
2 ACTUATOR1
Two Color Visi-Rocker
1
Indicate OFF, vertical legend
2
Indicate OFF, horizontal legend
Single color
3
Vertical legend
4
Horizontal legend
Push-To-Reset, Visi-Rocker
5
Indicate OFF, vertical legend
6
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
Vertical legend
8
Horizontal legend
2
One
Switch Only (No Coil)
Series Trip (Current)
Series Trip (Voltage)
Shunt Trip (Current)
Shunt Trip (Voltage)
5 AUXILIARY/ALARM
SWITCH6,7
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
(Gold Contacts)
6 FREQUENCY & DELAY
03 106 11 12 14 16 206 21
22 24 26 3
Two
4 CIRCUIT
0
1
2
4
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
50/60Hz Long
Three
F4
G4
H4,5
K4,5
Relay Trip (Current)
Relay Trip (Voltage)
Dual Coil with Shunt Trip Voltage Coil
Dual Coil with Relay Trip Voltage Coil
5
7
8
9
S.P.S.T., 0.093 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
AMPERES
E13
F
G
H13
L14
M13
P15
Q
R
S16
T
10
Mounting/
Barriers
E
11
Agency
Approval
Screw M4 (Bus Type)
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
0.250 Q.C./ Solder Lug
M6 Threaded Stud
Printed Circuit Board Terminals
Push-In Stud
Screw M4 w/upturned lugs and 30° bend
Push-On 0.110 Tab (Q.C.)
Screw M4 (Bus Type)
and 30° bend
30
31
32
34
36
429
449 469 529 549 56
DC, 50/60Hz Instantaneous
DC, 50/60Hz Ultra Short
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
Actuator or
Visi-Color17
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Marking:
Marking Color
I-OON-OFF Dual17 Single Color
Visi-Rocker
AB 1Black
White
CD 2White
n/a
FG 3White
Red
HJ 4White
Green
KL 5White
Blue
MN 6Black
Yellow
PQ 7Black
Gray
RS 8Black
Orange
10 MOUNTING/BARRIERS18
7 CURRENT RATING (AMPERES)
CODE
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M4 w/upturned lugs
9
Actuator
Color
9 ACTUATOR COLOR & LEGEND
3 POLES2
A 3
B
C
D 4
E4
2 3 1
8
Terminal
8 TERMINAL11
1 SERIES
A
1
630
7
Current Rating
0200.020
0250.025
0300.030
0350.035
0400.040
0450.045
0500.050
0550.055
0600.060
0650.065
0700.070
0750.075
0800.080
0850.085
0900.090
0950.095
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
6351035.000
6401040.000
6451045.000
6501050.000
A06 6 DC
A12 12 DC
A18 18 DC
A24 24 DC
A32 32 DC
A48 48 DC
A65 65 DC
J06 6 AC
J12
J18
J24
J48
J65 65 AC
K20 120 AC
L40 240 AC
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)8
12 AC
18 AC
24 AC
48 AC
1
A
2
B
5
E
6
F
3
C
4
D
STANDARD ROCKER BEZEL,Threaded Insert, 2 per poleBARRIERS
FLAT ROCKER ACTUATOR
6-32 x 0.195 inches
no
6-32 X 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
RECESSED OFF SIDE ROCKER ACTUATOR19
6-32 x 0.195 inches
no
6-32 x 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
6-32 x 0.195 inches
no
6-32 x 0.195 inches (multi-pole units only)
yes
ISO M3 x 5mm no
ISO M3 x 5mm (multi-pole units only)
yes
11 AGENCY APPROVAL
C
E
I
UL Recognized & CSA Accepted
TUV Certified, UL Recognized & CSA Accepted
UL Rec. STD 1077, UL Rec. 1500 (ignition protected), & CSA Accepted
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or mixed poles, and have one rocker per breaker.
3 Switch Only circuits, rated up to 50 amps & 3 poles. Only available when tied to a protected pole. For .02 to 30 amps, select Current Code 630. For 35 - 50 amps, select Current Code 650.
4 Available with terminal Codes 1, 2 and 3. Current Rating limited to 30 amps maximum.
5 Consult factory for Dual Coil options, as special catalog number is required. With Shunt
construction, Dual Coils will trip instantaneously on line voltage. Dual coils require 30VA
minimum power to trip and are rated for intermittent duty only.
6 Auxiliary Switch breakers with Series Trip & Switch Only circuits: ≤ 30A, are supplied with
standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
7 On multi-pole breakers, one aux. switch is supplied, mounted in the extreme right pole.
8 Separate pole type voltage coils not rated for continuous duty. Available only with delay codes 10 & 20.
9 Available with Circuit Codes B & D only. UL Recognized, CSA Accepted & TUV Certified to
50 amps.
10 UL Recognition, CSA Acceptance & TUV Certification available in one and two pole breakers.
11 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
12 Terminal Code 1: Available up to 30 amps, but not recommended over 20 amps.
13 Terminal Codes 3, 5 E & H (Bus Type) with TUV, are supplied with Lock Washers; Terminal Code M (M6 Threaded Stud) with TUV is supplied with Lock and Flat Washers. These breakers are only TUV Certified when the washers are used.
14 TUV Cert. available up to 12 amps. UL Rec. & CSA Accepted available up to 30 amps.
15 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 50 amps with UL Recognition, CSA Accepted & TUV Certification, with Circuit Codes A, B and C. Two pole breakers with Terminal Code P (Printed Circuit Board) are available up to 40 amps with UL
Recognition and CSA Accepted with Circuit Codes A, B and C.
16 Terminal Code S used on voltage coil circuit constructions only.
17 Color shown is visi and legend with remainder of rocker black, Dual = ON-OFF/I-O legend.
18 Legend on Push-to-reset bezel/shroud is white with single color actuator codes 7 & 8. Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator codes 5 & 6.
19 Recessed “off-side” available with actuator codes 1, 2, 3 & 4. Legends on rocker are available in ink stamping only.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Flat Rocker UL 489A – Ordering Scheme | 19
A 1 1
1
Series
2
Actuator
B 0
4
Circuit
3
Poles
14
5
Aux/Alarm
Switch
6
Frequency
& Delay
1 SERIES
A
16
2
37
4
57
6
7
8
Two Color Visi-Rocker
1
Indicate OFF, vertical legend
2
Indicate OFF, horizontal legend
Single color
3
Vertical legend
4
Horizontal legend
Push-To-Reset, Visi-Rocker
5
Indicate OFF, vertical legend
6
Indicate OFF, horizontal legend
Push-To-Reset , Single color
7
Vertical legend
8
Horizontal legend
3 POLES2
2
One
3
Two
Three
Series Trip (Current)
5 AUXILIARY/ALARM SWITCH3
0
1
2
w/o Aux Switch
S.P.D.T., 0.093 Q.C. Term.
S.P.D.T., 0.110 Q.C. Term.
6 FREQUENCY & DELAY
11 12 14 16 DC Ultra Short
DC Short
DC Medium
DC Long
7
8
9
S.P.S.T., 0.110 Q.C. Term.
(Gold Contacts)
S.P.S.T., 0.187 Q.C. Term.
S.P.D.T., 0.187 Q.C. Term.
52 54 56
DC, Short,Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
7 CURRENT RATING (AMPERES)
CODE
AMPERES
2100.100
2150.150
2200.200
2250.250
2300.300
2350.350
2400.400
2450.450
2500.500
2550.550
2600.600
2650.650
2700.700
2750.750
2800.800
8
Terminal
9
Actuator
Color
10
Mounting/
Barriers
2850.850
2900.900
2950.950
4101.000
5121.250
4151.500
517 1.750
4202.000
5222.250
5272.750
4303.000
4353.500
4404.000
4454.500
4505.000
Push-On 0.250 Tab (Q.C.)
Screw 8-32 w/upturned lugs
Screw 8-32 (Bus Type)
Screw 10-32 w/upturned lugs
Screw 10-32 (Bus Type)
Screw 8-32 w/upturned lugs and 30° bend
Screw 8-32 (Bus Type) and 30° bend
Screw 10-32 w/upturned lugs and 30° bend
9
B
F
G
H 7
M7
P8
Q9
M T
11
Max. Appl.
Rating
12
Agency
Approval
Screw 10-32 (Bus Type) and 30° bend
Screw M5 w/upturned lugs
Screw M5 w/upturned lugs and 30° bend
Screw M5 (Bus Type)
and 30° bend
Screw M5 (Bus Type)
M6 Threaded Stud
Printed Circuit Board Terminals
Push-In Stud
9 ACTUATOR COLOR & LEGEND
4 CIRCUIT
B
7
Current Rating
2 3 1
8 TERMINAL5
2 ACTUATOR1
1
630
4555.500
4606.000
4656.500
4707.000
4757.500
4808.000
4858.500
4909.000
4959.500
610 10.000
71010.500
611 11.000
71111.500
61212.000
71212.500
61313.000
61414.000
61515.000
61616.000
61717.000
61818.000
62020.000
62222.000
62424.000
62525.000
63030.000
635435.000
640440.000
645445.000
650450.000
Actuator or
Visi-Color11
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Marking:
Marking Color
ON-OFFDual11 Single Color
Visi-Rocker
B1Black White
D2White n/a
G3White Red
J4White Green
L5White Blue
N6Black Yellow
Q7Black Gray
S8Black Orange
10 MOUNTING/BARRIERS12
1
A
2
B
5
E
6
F
3
C
4
D
STANDARD ROCKER BEZEL,Threaded Insert, 2 per pole
FLAT ROCKER ACTUATOR
6-32 x 0.195 inches
6-32 X 0.195 inches (multi-pole units only)
ISO M3 x 5mm ISO M3 x 5mm (multi-pole units only)
RECESSED OFF SIDE ROCKER ACTUATOR 13
6-32 x 0.195 inches
6-32 x 0.195 inches (multi-pole units only)
ISO M3 x 5mm ISO M3 x 5mm (multi-pole units only)
PUSH-TO-RESET BEZEL,Threaded Insert, 2 per pole
6-32 x 0.195 inches
6-32 x 0.195 inches (multi-pole units only)
ISO M3 x 5mm ISO M3 x 5mm (multi-pole units only)
BARRIERS
no
yes
no
yes
no
yes
no
yes
no
yes
no
yes
11 MAXIMUM APPLICATION RATING
M
80 DC
12 AGENCY APPROVAL
T
J
UL489A LISTED
UL489A LISTED, TUV CERTIFIED
Notes:
1 Push-To-Reset actuators have OFF portion of rocker shrouded.
2 Multi-pole breakers have all breakers identical except when specifying Aux. switch and/or
mixed poles, and have one rocker per breaker.
3 Auxiliary Switch breakers with Series Trip circuits: ≤ 30A, are supplied with standard half shells. 30-50A are supplied with extended boat (B-Style) half shells.
4 VDE Certification available with single pole breakers only. UL489A Listing available with one and two pole breakers.
5 Screw Terminals are recommended on ratings greater than 20 amps. Ratings over 30 amps are only available with Terminal Codes 5, 9, G, H, M and Q.
6 Terminal Code 1 (Push-On) available up to 25 amps with TUV or VDE Certification and 30 amps with UL489A Listing, but is not recommended over 20 amps.
7 Terminal Codes 3, 5 and H (Bus Type) with TUV or VDE, are supplied with Lock Washers, and Terminal Code M (M6 Threaded Stud) with VDE is supplied with Lock and Flat Washers. These breakers are only TUV or VDE Certified when the washers are used.
8 Single pole breakers with Terminal Code P (Printed Circuit Board) are available up to 30 amps with VDE Certification and 50 amps with UL489A Listing.
9 Terminal Code Q not available with VDE certification.
10 Color shown is Visi and Legend with remainder of rocker black. Dual = ON-OFF/I-O legend.
11 Legend on Push-to-reset bezel/shroud is white with single color actuator codes R & U.
Legend on Push-To-Reset bezel/shroud matches Visi-Color of rocker with actuator
codes N & O. Rockerguard available with actuator codes C through K
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
20 | A-Series Rocker – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specified.
3 Schematic shown represents current trip circuit.
4 Circuits shown for >30 amps / VDE.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Rocker – Form & Fit Drawings | 21
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line & load
terminal orientation on indicate OFF is opposite of indicate ON.
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 All dimensions are in inches [millimeters].
4 Tolerance ± 0.20 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
22 | A-Series Rocker Snap-In Bracket – Form & Fit Drawings
Notes:
1 Dimensions apply to all variations shown. Notice that circuit breaker line
& load terminal
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
Orientation on indicate “OFF” is opposite of indicate “ON”
3 Recommended panel thickness: .04 0 [1.02] to .100 [2.54]
4 All dimensions are in Inches [millimeters].
5 Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
A-Series Flat Rocker – Form & Fit Drawings | 23
Notes:
1 All dimensions are in inches [millimeters].
2 For pole orientation with horizontal legend, rotate front view clockwise 90°.
3 Tolerance ± 0.20 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com
24 | A-Series PC Terminal Diagrams
Notes:
1 Drawing illustrates A-Series with VDE certification.
2 All dimensions are in inches [millimeters].
3 Tolerance ± 0.20 [.51] unless otherwise specified
REV_CB_A_04_2014
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: [email protected] • www.carlingtech.com