Bulletin 1365 Installation Guide . . . . .

Bulletin 1365
Installation Guide
ATTENTION: The user is responsible for conforming to the National Electrical Code and all other applicable local codes
. Failure
to comply with codes could result in severe bodily injury or loss of life
.
ATTENTION: This equipment is at line voltage when AC power is connected
. Disconnect and lockout all ungrounded conductors
of the AC power line. Failure to observe these precautions could result in severe bodily injury or loss of life
.
Note: All remote operation wiring must not exceed 250 feet
.
Ground the Controller and Enclosure, the Motor and the Operator
’s Control Station.
ATTENTION: Connect the ground wire brought in with the incoming AC power line to the controller ground point
. Connect an
appropriate equipment grounding conductor unbroken from the controller ground point, the motor frame, the
transformer enclosure if used, the controller electrical enclosure, the wiring conduits, and the operator’s control
station to an appropriate grounding electrode. Failure to observe this precaution could result in severe bodily injury
or loss of life.
1. Locate the ground point provided at the bottom edge of the heat sink
.
2. Run a suitable equipment grounding conductor unbroken from this controller ground point to the plantround
g (grounding
electrode). A ring lug is required at the ground point.
3. Connect a suitable grounding conductor from each conduit to this controller ground point
.
4. Connect a suitable equipment grounding conductor to the motor frame, the transformer enclosure if used, and the controller
enclosure. Run this conductor unbroken to the grounding electrode
.
5. Connect the ground wire brought in with the incoming AC power line to the controller ground point
.
Wiring AC Power to the Controller
ATTENTION: Do not operate the controller with available short
-circuit currents in excess of 10,000 amperes. Failure to observe
this precaution could result in severe bodily injury or loss of life
.
1. Size the AC line supply conductors for the specific controller rating and according to all applicable codes
.
2. Run the AC line supply through a conduit entry in the bottom of the controller to terminals TB1
-L1 and TB1-L2/F1.
Wiring the DC Motor to the Controller
1. Size the motor armature circuit conductors A1 and A
2 according to all applicable codes.
2. Run the DC motor armature leads and the shunt field supply leads (if a permanent magnet field motor is not used) through the
same conduit entry used for the AC line supply
.
3. Use the appropriate tightening torque as listed in Table .1A for wire connections to input and output terminals
.
Table 1.A. Terminal Strip TB1/TB2 Tightening Torque’s (lbs-in).
TB
TB1
Terminals
Input Terminals 51, L1, L2/F2
Torque
TB2
Output Terminals A1, A2/F2
12 maximum in-lbs
TB1
Thermostat 32, 132
4 in-lbs
All: 9 minimum -
ATTENTION: If motors other than a straight shunt are used with the 1365 controller and an S1 and S2 winding is present on the
motor, additional motor connections other than those detailed in this instruction manual are applicable
. Refer to
the motor manufacturer instructions when wiring other types of motors
. Failure to observe this precaution could
result in damage to the equipment.
4. For ALL Catalogs (except 1365-DAF): If CCW motor rotation is desired (looking from the back of the motor or the shaft end),
connect motor armature leads A1 and A2 to controller terminals TB1
-A1 and TB1-A2/F2, respectively, as shown in Figure .11.
If CW motor rotation is desired (looking from the back of the motor or the shaft end), reverse the motor armature connections at
the motor.
For 1365-DAF ONLY, if CCW motor rotation is desired when the Forward/Off/Reverse switch is in the FORWARD position
(looking from the back of the motor or the shaft end), connect motor armature leads A1 and A2 to controller terminals TB3
-A1
and TB3-A2, respectively. If CW motor rotation is desired (looking from the back of the motor or the shaft end), reverse the
motor armature connections at the motor.
5. Connect the motor shunt field supply (when available) leads F1 and F2 to controller terminals TB1
-L2/F1 and A2/F2,
respectively. See Figure 1.1.
6. Verify that the field is connected as shown on the motor namep
late or the connection diagram in the terminal box on the motor
.
7. Connect the motor thermostat leads P1 and P2 to controller terminal TB2
-32 and TB2-132, respectively. See Figure 1.1. If a
motor thermostat is not used, another means of motor overload thermal protection must be used and a jumper must be placed
between terminals 132 and 32 on TB2.
Wiring the Start/Stop Circuit
For drives without operator devices on the controller (Catalog 1365
-SAN, 1365-PAN, 1365-TAN):
1. Run the Start/Stop push-button or normally open contact wiring in the remaining conduit entry separate from the AC and DC
power wiring.
ATTENTION: The factory installed jumper must be removed from between controller terminals 51 and L1 if the stop switch is to
be wired to these terminals. Failure to observe this precaution could result in bodily injury
. A maintained closed
contact can cause the controller to automatically restart if line input power is removed and then -re
applied. Do not
use a maintained contact unless the machine is suitably protected
. Failure to observe these precautions could result
in bodily injury.
2. Use the appropriate tightening torque as listed in Table .1B for wire connections to input and output terminals
.
Table 1.B. Terminal Strip TB/TB4 Tightening Torque’s (lbs-in).
TB
TB2
Terminals
Torque
32, 132, 35, 38, 419, 519, 4 in-lbs
326, 156,157,126
TB4
6+, 5-
4 in-lbs
3. Connect the Start/Stop push-button or normally open contact as shown in Figure.21.
4. If Start/Stop control is remote, remove the facto
ry-installed jumper between terminals TB2-35 and TB2-132. See Figure 1.2.
With the operator’s Start/Stop controls mounted remotely from the controller, the AC fused disconnect or circuit breaker must
be mounted in close proximity to the operator controls
.
ATTENTION: A start/stop switch that does not include an AC power disconnect function in the Stop position is not recommended
for use with the 1365 drive. The 1365 drive does not have an armature loop contactor and a single fault like a
thyristor short could cause motor rotation when in the stop mode, if used with a switch that did not disconnect AC
power. If a Start/Stop switch without a power disconnect function is used, an AC power disconnect switch MUST
be mounted next to the operator controls
. Failure to observe this precaution could result in bodily injury
.
Wiring the Run/Jog Circuit
For drives without operator devices on the controller:
1. Run the Run/Jog wiring in conduit separate from the AC and DC power wiring
.
2. Use the appropriate tightening torque as listed in Table .1B for wire connections to input and output terminals
.
3. Wire the Run/Jog switch as indicated in Figure .13.
Wiring the Reference Signal Potentiometer (1365-SAN, 136SPAN, 1365-TAN)
For drives without operator devices on the controller:
1. Run all reference wiring in the same conduit as the Start/Stop control wiring separate from the AC and DC power wiring
.
2. Use the appropriate tightening torque as listed in Table .1B for wire connections to input and output terminals
.
3. Use minimum #16 AWG cable that is twisted triple conductor with at least two twists per inch
.
4. Connect a 5K ohm, 0.25 watt pot having an insulated operator shaft and knob, such as available in Catalog 1365
-OP or
equivalent, as shown in Figure 1.4.
ATTENTION: Because the Reference Potentiometer is connected through the regula
tor to the Armature Power Circuit, its
terminals are at line potential. Use a potentiometer that has plastic shaft to insulate the operator knob from the
power circuit. Potentiometer must be rated to withstand Hi
-Pot tests at 2000 volts DC for one minute. Failure to
observe this precaution could result in severe bodily injury or loss of life
.
Wiring the Process Control and/or Automatic/Manual Devices (if required)
Controller catalog 1365-PAN and 1365-PAF have a high impedance input to interface with process signals
. If both manual control
(controller responds to a reference potentiometer) and process control (controller responds to an automatic signal) are desired, an
Automatic/Manual switch is included in selected controller models (cat 1365
-PAF).
1. Use minimum #16 AWG unshielded cable that is twisted double conductor with at least two twists per inch
.
2. Use the appropriate tightening torque as listed in Table .1B for wire connections to input and output terminals
.
3. Wire the process control signal to terminals TB4 ( 6+ ) and TB4 ( 5- ). See Figure 1.4.
4. Wire the process control buffered output TB2
-126 to TB2-326. See Figure 1.4.
5. Wire the Automatic/Manual switch, if required, as shown in Figure .14.
Wiring the DC Tachometer Speed Feedback Signal
ATTENTION: Because the Tachometer is connected through the regulator to the Armature Power Circuit, its terminals are at line
potential. Disconnect all input power to the drive before servicing
. Failure to observe this precaution could result in
severe bodily injury or loss of life
.
All of the controllers, except catalog 1365
-DAF or one the user has configured for motor reversing, can utilize a DC tachometer as
speed feedback. The tachometer must have a voltage range of 18
.5 to 21.0 volts per 1000 RPM or 6.5 to 7.0 volts per 1000 RPM,
maximum of 37 volts at maximum speed
.
1. Run the two tachometer signal leads in a separate conduit from the motor to the controller
.
2. Use minimum #16 AWG unshielded two wire cable that is twisted at least two ists
tw per inch.
3. Use the appropriate tightening torque as listed in Table .1B for wire connections to input and output terminals
.
4. Connect the DC tachometer so that the tach lead connected to terminal 519 is more positive than the tach lead connected to
terminal 419 for the desired direction of rotation. Refer to Figure 1.5.
ATTENTION: Reverse connection will cause the motor to run at maximum uncontrolled speed
. The DC tachometer must be
connected so that the tach lead connected to terminal 519 is more positive than the negative tach lead connected to
terminal 419 for the desired direction of rotation. Failure to observe this precaution could result in bodily injury
.
5. An isolation transformer must be used between the AC power source and the controller to isolate the controller from the AC
power source ground. Each such controller must have it’s own isolation transformer
.
IMPORTANT: Any 1365 controller used in a motor reversing application cannot employ a DC tachometer speed feedback
.
NOTE: A DC tachometer used as a speed feedback signal for one controller cannot be used as the speed reference signal for another
controller.