GV3000/SE AC Drive Hardware Reference, Installation, and

GV3000/SE AC Drive
Hardware Reference, Installation,
and Troubleshooting
30-100 HP @ 230 VAC
Version 6.04
Instruction Manual D2-3417-1
The information in this manual is subject to change without notice.
Throughout this manual, the following notes are used to alert you to safety considerations:
!
ATTENTION: Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and understanding of the product.
!
ATTENTION: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this equipment.
Read and understand this manual and other applicable manuals in their entirety before
proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: DC bus capacitors retain hazardous voltages after input power has been
disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors
to discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could
result in severe bodily injury or loss of life.
ATTENTION: The drive can operate at and maintain zero speed. The user is responsible for
assuring safe conditions for operating personnel by providing suitable guards, audible or visual
alarms, or other devices to indicate that the drive is operating or may operate at or near zero
speed. Failure to observe this precaution could result in severe bodily injury or loss of life.
ATTENTION: Do not install modification kits with power applied to the drive. Disconnect and
lock out incoming power before attempting such installation or removal. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: The user must provide an external, hardwired emergency stop circuit outside of
the drive circuitry. This circuit must disable the system in case of improper operation.
Uncontrolled machine operation may result if this procedure is not followed. Failure to observe
this precaution could result in bodily injury.
ATTENTION: The user is responsible for conforming with all applicable local, national, and
international codes. Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
DeviceNet is a trademark of the Open DeviceNet Vendor Association.
ControlNet is a trademark of ControlNet International, Ltd.
PROFIBUS is a trademark of PROFIBUS International.
GV3000/SE, AutoMax, ControlNet, and Reliance are trademarks of Rockwell International.
© 1999 Rockwell International Corporation.
CONTENTS
Chapter 1
Chapter 2
Chapter 3
Table of Contents
Becoming Familiar with the Manual
1.1 Finding Information ...................................................................................
1.2 Assumptions About the Audience .............................................................
1.3 Understanding Terms Used in this Manual ..............................................
1.4 If You Want to Know More ........................................................................
1.5 Getting Assistance from Reliance Electric ...............................................
1-1
1-2
1-2
1-2
1-2
About the Drive
2.1 Identify the Drive by Model Number .........................................................
2.2 Enclosures ................................................................................................
2.3 30-100 HP GV3000/SE Drive Components and Locations ......................
2.4 Regulator Board Description .....................................................................
2.4.1 Jumper Locations and Settings ...................................................
2.4.1.1 Analog Input Speed Reference Jumper ............................
2.4.1.2 Analog Output Jumper ......................................................
2.4.2 Wiring the Terminal Strip .............................................................
2.4.3 RS-232 Communication Port .......................................................
2.4.4 Option Board Connector ..............................................................
2.4.5 Operator Interface Module Connector .........................................
2.4.6 Keypad/Display .............................................................................
2.5 Jumpers on Base Board (PISC-40) ..........................................................
2.6 Drive Kit Options .......................................................................................
2-1
2-2
2-3
2-5
2-7
2-7
2-8
2-9
2-10
2-10
2-10
2-11
2-11
2-13
Planning Before Installing
3.1 Requirements for the Installation Site .......................................................
3.1.1 Making Sure Environmental Conditions are Met ........................
3.1.2 Determining Total Area Required Based on Drive
Dimensions ...................................................................................
3.1.3 Verifying the Site Provides for Recommended Air Flow
Clearances ....................................................................................
3.1.4 Verifying Power Module AC Input Ratings Match
Supplied Power .............................................................................
3.2 Wiring Requirements for the Drive ...........................................................
3.2.1 Meeting Terminal Strip Input and Output Specifications ...........
3.2.2 Determining Wire Size Requirements .........................................
3.2.2.1 Recommended Power Wire Sizes ....................................
3.2.2.2 Recommended Control and Signal Wire Sizes .................
3.2.2.3 Recommended Motor Lead Lengths .................................
3.2.2.4 Recommended Serial Communication Cable Lengths .....
3.2.3 Selecting AC Input Line Branch Circuit Fuses, Circuit
Breakers, and AC Reactors .........................................................
3.2.4 Meeting Encoder Specifications (FVC Regulation Only) ...........
3.2.4.1 Encoder Wiring Guidelines ..............................................
3-1
3-1
3-2
3-4
3-5
3-5
3-5
3-5
3-5
3-6
3-6
3-8
3-8
3-9
3-9
I
3.2.5 Verifying Power Module Output Current Rating is Greater
Than Motor Full Load Amps .........................................................
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
Chapter 9
Mounting the Drive, Grounding, and Finding Wire Routing Locations
4.1 Mounting the Drive ....................................................................................
4.1.1 Verifying the Drive's Watts Loss Rating ......................................
4.2 Routing Input, Motor Output, Ground, and Control Wiring
for the Drive ..............................................................................................
4.3 Grounding the Drive ..................................................................................
Installing Input Power Wiring
5.1 Installing Transformers and Reactors (Optional) ......................................
5.2 Installing Fuses for Branch Circuit Protection ..........................................
5.3 Installing a Required External/Separate Input Disconnect .......................
5.4 Installing Power Wiring from the AC Input Line to the Drive's
Power Terminals .......................................................................................
5.5 Installing Power Wiring from an External DC Bus to the
Drive's Internal DC Bus Terminals ............................................................
3-9
4-1
4-1
4-1
4-2
5-1
5-2
5-2
5-5
5-5
Installing Output Power Wiring
6.1 Installing Output Contactors (Optional) ....................................................
6.2 Installing Mechanical Motor Overload Protection (Optional) ....................
6.3 Installing Output Wiring from the Drive Output Terminal to the Motor .....
6-1
6-1
6-1
Wiring the Regulator Board Terminal Strip
7.1 Stopping the Drive ....................................................................................
7.2 Wiring the Encoder Feedback Device (FVC Regulation Only) .................
7.3 Wiring the Signal and Control I/O .............................................................
7-6
7-6
7-9
Completing the Installation
8.1 Checking the Installation ...........................................................................
8.2 Powering Up After Installation is Complete ..............................................
8-1
8-2
Troubleshooting the Drive
9.1 Test Equipment Needed to Troubleshoot .................................................
9.2 Drive Alarms and Faults ...........................................................................
9.3 Verifying That DC Bus Capacitors are Discharged ..................................
9.4 Checking Out the Power Module with Input Power Off ............................
9.5 Replacement Parts ...................................................................................
9-1
9-1
9-1
9-2
9-4
Appendix A Technical Specifications .................................................................................... A-1
Appendix B 30-100 HP GV3000/SE System Wiring Diagram ............................................... B-1
II
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
List of Figures
Table of Contents
Figure 2.1 – Identifying the Drive Model Number .............................................
2-1
Figure 2.2 – 30 to 50 HP Drive Components and Locations ............................
2-3
Figure 2.3 – 60 to 100 HP Drive Components and Locations ..........................
2-4
Figure 2.4 – Regulator Board Components and Locations ..............................
2-6
Figure 2.5 – Jumper J4 Settings for Analog Input Speed Reference ...............
2-8
Figure 2.6 – Jumper J17 Settings for Analog Outputs .....................................
2-9
Figure 2.7 – Typical Terminal Strip Connections ..............................................
2-10
Figure 2.8 – Keypad/Display .............................................................................
2-11
Figure 2.9 – Base Board Jumper Locations .....................................................
2-12
Figure 3.1 – Drive Dimensions .........................................................................
3-3
Figure 3.2 – Recommended Air Flow Clearances ............................................
3-4
Figure 3.3 – How to Measure Motor Lead Lengths ..........................................
3-7
Figure 4.1 – Terminal Locations .......................................................................
4-3
Figure 5.1 – Typical AC Input Electrical Connections ......................................
5-3
Figure 5.2 – Typical DC Input Electrical Connections ......................................
5-4
Figure 7.1 – Two-Wire Start/Stop Sample Control Wiring ................................
7-4
Figure 7.2 – Three-Wire Start/Stop Sample Control Wiring .............................
7-5
Figure 7.3 – Encoder Wiring Connections ........................................................
7-8
Figure 9.1 – DC Bus Voltage Terminals ...........................................................
9-2
III
List of Tables
Table 2.1 – Power Ratings ..............................................................................
2-2
Table 2.2 – Settings of Jumpers on Base Board .............................................
2-11
Table 2.3 – Available Kits and Options ...........................................................
2-13
Table 3.1 – Ambient Conditions ......................................................................
3-2
Table 3.2 – Drive Dimensions and Weights ....................................................
3-2
Table 3.3 – Recommended Power Wire Sizes for 30 to 50 HP Drives ...........
3-5
Table 3.4 – Recommended Power Wire Sizes for 60 to 100 HP Drives .........
3-6
Table 3.5 – Recommended Terminal Strip Wire Sizes ...................................
3-6
Table 3.6 – Motor Lead Lengths ......................................................................
3-7
Table 3.7 – Reactors .......................................................................................
3-7
Table 3.8 – AC Input Line Fuse Selection Values ...........................................
3-8
Table 3.9 – Circuit Breaker Selection Values ..................................................
3-9
Table 3.10 – AC Reactor Selection Values .......................................................
3-9
Table 5.1 – AC Line Reactors .........................................................................
5-2
Table 7.1 – RS-232 Connections (Terminals 1-3) ...........................................
7-1
Table 7.2 – Encoder Connections (Terminals 4-9) ..........................................
7-1
Table 7.3 – Analog Output Connections (Terminals 10 and 11) .....................
7-2
Table 7.4 – Analog Speed/Torque Reference Connections
(Terminals 12-15) .........................................................................
7-2
Table 7.5 – Digital Input Connections (Terminals 16-25) ................................
7-2
Table 7.6 – Snubber Resistor Braking Connections (Terminals 26 and 27) ...
7-3
Table 7.7 – Status Relay Connections (Terminals 28-31) ..............................
7-3
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip .....................
7-9
Table 9.1 – Resistance Checks .......................................................................
9-3
Table 9.2 – Replacement Parts for the GV3000/SE Drives ............................
9-4
Table A.1 – Service Conditions ........................................................................
A-1
Table A.2 – Environmental Condition ..............................................................
A-2
Table A.3 – Terminal Strip Input Specifications ...............................................
A-2
Table A.4 – Terminal Strip Output Specifications ............................................
A-2
Table A.5 – Terminal Strip RS-232 Specifications...........................................
A-3
Table A.6 – Encoder Feedback Device Specifications
Table of Contents
(FVC Regulation Only) .................................................................
A-3
Table A.7 – Input Signal Response Times (Maximum) ...................................
A-4
V
CHAPTER 1
Becoming Familiar with the Manual
This chapter provides help in finding information in the manual and describes the
intended audience. Also included are references to other related publications and
instructions on receiving assistance from Reliance Electric.
1.1
Finding Information
This instruction manual describes the GV3000/SE drive's Power Module and
regulator hardware. It does not cover the GV3000/SE software. For additional
software information, refer to the GV3000/SE 230 VAC General Purpose (V/Hz) and
Vector Duty Drive Software Start-Up and Reference Manual (D2-3416-1).
As an aid in finding information in this manual, each chapter is briefly described below:
•
Chapter 1
- Becoming Familiar with the Manual
Provides information on how the manual is organized and where
to find additional information.
•
Chapter 2
- About the Drive
Identifies drive components and shows their locations.
•
Chapter 3
- Planning Before Installing
Presents information that must be considered when planning a
drive installation.
•
Chapter 4
- Mounting the Drive, Grounding, and Finding Wire Routing
Locations
Describes how to mount the drive and properly ground it.
•
Chapter 5
- Installing Input Power Wiring
Describes incoming AC and DC line components and how to
properly connect them.
•
Chapter 6
- Installing Output Power Wiring
Describes output AC line components and how to properly
connect them to the motor.
•
Chapter 7
- Wiring the Regulator Board Terminal Strip
Provides information on the I/O wiring that connects the terminal
strip on the Regulator board.
•
Chapter 8
- Completing the Installation
Provides instructions on how to perform a final check of the
installation before power is applied.
•
Chapter 9
- Troubleshooting the Drive
Becoming Familiar with the Manual
1-1
Describes the equipment that is needed to troubleshoot the drive
and how to measure DC bus voltage. A replacement part list is
also provided.
1.2
•
Appendix A - Technical Specifications
Lists drive specifications in table form.
•
Appendix B - 30-100 HP GV3000/SE System Wiring Diagram
Provides additional wiring information for the 30-100 HP drives.
Assumptions About the Audience
This manual is intended for qualified electrical personnel. It is task-oriented and is
organized according to a logical progression of steps to be followed to install and
troubleshoot the drive.
1.3
Understanding Terms Used in this Manual
The following terms are defined according to the way they are used in this manual:
1.4
•
GV3000/SE drives will typically be referenced by horsepower. If additional
clarity is required, drive model numbers will also be included.
•
Parameters will be referenced either as parameter (P.030) or Elapsed Time
Meter Reset (P.030).
If You Want to Know More
Refer to the following related publications as necessary for more information:
1.5
•
GV3000/SE 230 VAC General Purpose (Volts/Hertz) and Vector Duty Drive
Software Start-up and Reference manual (D2-3416-1).
•
Instruction manuals listed in Table 2.3.
Getting Assistance from Reliance Electric
If you have any questions or problems with the products described in this instruction
manual, contact your local Reliance Electric sales office. For technical assistance,
call 1-800-726-8112.
1-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
CHAPTER 2
About the Drive
This chapter describes how to identify the drive using the model number matrix.
Major components of each drive are also shown.
The GV3000/SE AC drive is a PWM (Pulse-Width-Modulation) drive that provides
vector and general purpose regulation for a wide range of applications.
Using vector regulation, the drive can provide high dynamic response, maintain full
rated motor torque to zero speed, and precisely control motor speed in both
directions. The drive can provide this functionality either with encoder feedback
(flux vector control or FVC) or without (sensorless vector control or SVC).
Using general purpose (volts/hertz or V/Hz) regulation, the drive is suited for a
broad range of applications requiring adjustable speed control of motors.
2.1
Identify the Drive by Model Number
Each GV3000/SE AC Drive can be identified by its model number. See figure 2.1.
This number appears on the shipping label and on the drive's nameplate. The
drive's model number includes the Power Module and the regulator. Drive power
ratings are provided in table 2.1.
NNN
V
2
0
NN
Horsepower Ratings
30 = 30 HP
40 = 40 HP
50 = 50 HP
60 = 60 HP
75 = 75 HP
100 = 100 HP
GV3000/SE
V = V/Hz or Vector
Voltage
2 = 200 - 230 VAC
Enclosure
0 = Chassis
Regulator Version
60 = Vector and V/Hz Regulator
Figure 2.1 - Identifying the Drive Model Number
About the Drive
2-1
Table 2.1 - Power Ratings
(1)
(2)
Model
Number
Input Volts
(AC)
Input
KVA
Input Amps
(Maximum)
Output Amps
(Maximum) (1) (2)
Power Loss Watts
(Full Load)
30V2060
200-230 VAC
+/– 10%
41.8
105 A
105 A
660
40V2060
200-230 VAC
+/– 10%
53.8
135 A
135 A
900
50V2060
200-230 VAC
+/– 10%
59.8
150 A
150 A
1100
60V2060
200-230 VAC
+/– 10%
77.7
195 A
195 A
1350
75V2060
200-230 VAC
+/– 10%
97.6
245 A
245 A
1650
100V2060
200-230 VAC
+/– 10%
109.6
275 A
275 A
2250
With vector regulation, 150% output current capability for one minute.
These values are for operation with 4 kHz carrier frequency. For operation with 8 kHz carrier frequency, derating by 20% is required.
2.2
Enclosures
This manual describes GV3000/SE chassis style drives. These drives should be
installed in cabinets.
2-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
2.3
30-100 HP GV3000/SE Drive Components and Locations
The 30-100 HP GV3000/SE drives have the following main components. The
identification numbers provided correspond to the number used in figures 2.2 and
2.3. Replacement parts are listed in chapter 9.
1.
Fan Assembly
2.
Membrane Switch (Keypad/Bracket)
3.
Regulator Printed Circuit Board
4.
Base Board (PISC Board)
5.
Bus Capacitor
6.
Internal Fan Assembly.
7.
Cover
▲
▲
TO
AUAN
M
.
D
EE
SP LTS
VO PS
AM
Hz
UE
KwRQ ord
TOssw
Pa
G
IN
NN TE
RUMO
REG
JO TO ARD
AURW SE
FOVER AM
R
E
G
R O
PR
RAM
ard
rw e
Fo vers
Re
N
RUG
JO
2
OG
PR
R
TE
EN
T
AR
ST
OP
STSET
RE
7
6
3
4
5
1
Figure 2.2 - 30 to 50 HP Drive Components and Locations
About the Drive
2-3
▲
▲
TO
AUAN
M
.
D
EE
SP LTS
VO PS
AM
Hz
UE
KwRQ ord
TOssw
Pa
G
IN
NN TE
RUMO
REG
JO TO ARD
AURW SE
FOVER AM
REOGR
PR
RAM
ard
rw e
Fo vers
Re
N
RUG
JO
2
OG
PR
R
TE
EN
T
AR
ST
7
OP
STSET
RE
3
4
6
5
1
Figure 2.3 - 60 to 100 HP Drive Components and Locations
2-4
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
2.4
Regulator Board Description
GV3000/SE drive regulation is performed by a microprocessor on the Regulator
board. See figure 2.4. Drive operation is adjusted by the parameters entered
through the keypad. The Regulator board accepts power circuit feedback signals
and an external speed reference signal, as well as data from an encoder that is
attached to the motor when set up for FVC regulation. The Regulator board
provides:
•
PWM gating signals to the IGBT power devices
Based on the output of the control loop, the regulator sends PWM gating signals
through the Current Feedback board to isolated drivers on the Gate Driver
board. These drivers switch the Insulated Gate Bi-polar Transistors (IGBTs),
producing a pulse-width-modulated (PWM) waveform that corresponds to the
speed (FVC regulation) or frequency (volts/hertz regulation) reference. The
IGBTs can be switched at either a 2, 4 or 8 kHz carrier frequency.
•
Form A and B contacts for drive status indicators
The Form A and B contacts are under control of the user via programmable
parameters. A Form A or B transition can indicate drive status. The contacts
are rated for 5 amps resistive load at 250 VAC/ 30 VDC and are made available
through the terminal strip.
•
Display data for a four-character display and fourteen indicator LEDs
The four-character display is used to indicate drive parameters, parameter
values, and fault codes. The fourteen single LEDs indicate drive status and
mode, as well as identifying drive outputs whose values are displayed on the
four-character display.
•
An analog output
The analog output is a scaled voltage (0-10 VDC) or current (4-20 mA) signal
proportional to either motor speed (RPM) or motor torque or current (%TORQUE).
The current signal selection (via jumper J17) requires a power supply for
operation. The power can be sourced from the encoder terminals (4 and 9) or
from an external 15V power supply. See table 7.8, terminals 10 and 11, for
more information. The analog output signal is available through the terminal
strip.
•
A snubber resistor braking signal
The Regulator board provides a signal for use by an optional snubber resistor
braking kit. The signal is available through the terminal strip.
About the Drive
2-5
USER DISPLAY
J5
26-Pin Ribbon Cable
34-Pin Ribbon Cable
J3
J9
J7
J8
J17
1
2
3
4
J3
J4
J5
J7
5
-
6
7
8
J4
USER I/O TERMINAL STRIP
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Option Board Connector
Analog Input Jumper
Power Module Feedback Cable
OIM (optional) Connector
J8 - RS232C Port
J9 - Keypad/Display Connector
J17 - Analog Output Jumper
Figure 2.4 - Regulator Board Components and Locations
2-6
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
2.4.1 Jumper Locations and Settings
Jumpers J4 and J17 on the Regulator board are factory-set for voltage in and
voltage out signals. Refer to figure 2.4 for their locations on the Regulator board. If
you need to change the jumpers' settings, use the following procedures.
!
ATTENTION: Do not alter the setting of any jumper not described in
this instruction manual. Failure to observe this precaution could result
in damage to, or destruction of, the equipment.
2.4.1.1 Analog Input Speed Reference Jumper (J4)
Jumper J4 is the analog speed/torque (U.000) reference jumper. This jumper
selects either +/– 10 VDC or 0-20 mA input . Parameters P.009, P.010, and P.011
are used in conjunction with the jumper. Note that if the position of jumper J4 is
changed after the parameters are programmed, the software will not recognize that
the input reference or polarity has been changed. Be sure to verify that parameters
P.009, P.010, and P.011 are correct before starting the drive. Refer to the
GV3000/SE Software Start-Up and Reference manual for more information.
Use the following procedure to set jumper J4:
!
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe
this precaution could result in severe bodily injury or loss of life.
Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the two attaching screws.
Step 3. Verify that the DC bus voltage is zero by following the procedure in section
9.3.
Step 4. Locate jumper J4 on the Regulator board. Refer to figure 2.4.
Step 5. Locate pin 1 on jumper J4. Move the jumper to the desired setting as
shown in figure 2.5.
Step 6. Re-attach the cover.
Step 7. Re-apply input power.
Step 8. Verify that the Terminal Strip Analog Input Offset (P.009), Terminal Strip
Analog Input Gain (P.010), and Terminal Strip Analog Input Configure
(P.011) are correctly set. Note that the jumper settings must match the
software settings otherwise the reference value may differ from what is
expected. Refer to the GV3000/SE Software Start-Up and Reference
manual for more information.
About the Drive
2-7
Voltage Input Option
Pins 2-3
Current Input Option
Pins 1-2
10 VDC
0-20 mA
J4
J4
(default)
Figure 2.5 - Jumper J4 Settings for Analog Input Speed Reference
2.4.1.2 Analog Output Jumper (J17)
Jumper J17 is the analog output jumper. This jumper selects either a 0-10 VDC or
4-20 mA scaled signal output that is programmable for either speed or torque,
parameter P.012. The jumper only selects a 0-10 VDC source voltage or 4-20 mA
sink current to represent speed or torque. Note that the 4-20 mA current selection
requires a power supply for operation as shown in table 7.8, terminals 10 and 11.
Use the following procedure to set jumper J17:
!
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe
this precaution could result in severe bodily injury or loss of life.
Step 1. Turn off input power to the drive and wait five minutes.
Step 2. Remove the cover from the drive by unscrewing the two attaching screws.
Step 3. Verify that the DC bus voltage is zero by following the procedure in section
9.3.
Step 4. Locate jumper J17 on the Regulator board. Refer to figure 2.4.
Step 5. Locate pin 1 on jumper J17. Move the jumper to the desired setting as
shown in figure 2.6.
Step 6. Re-attach the cover.
Step 7. Re-apply input power.
Step 8. Verify that parameter P.012 is set correctly for either speed or torque.
2-8
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Voltage Output Option
Pins 2-3
Current Output Option
Pins 1-2
10 VDC
4-20 mA
J17
J17
(default)
Figure 2.6 - Jumper J17 Settings for Analog Outputs
2.4.2 Wiring the Terminal Strip
The terminal strip on the Regulator board provides terminals for connecting
customer I/O devices. See figures 2.4 and 2.7. The following terminals are
provided:
About the Drive
•
Terminals 1-3
: RS-232 connections
•
Terminals 4-9
: encoder connections
•
Terminals 10-11: analog output connections
•
Terminals 12-15: analog speed/torque reference connections
•
Terminals 16-25: 24 VDC digital input connections
•
Terminals 26-27: snubber resistor braking control connections for older
Snubber Resistor Braking Kits (for example, the M/N 2DB2010 series)
•
Terminals 28-31: status relay connections
2-9
16
N.O. RELAY COMMON
N.O. RELAY CONTACT
N.C. RELAY COMMON
N.C. RELAY CONTACT
+24 VDC COMMON
SNUBBER RESISTOR BRAKING SIGNAL
+24 VDC COMMON
START
9 10 11 12 13 14 15
STOP
8
RESET
7
RUN/JOG
6
FUNCTION LOSS
5
DIGITAL INPUT 6 (FORWARD/REVERSE)
4
DIGITAL INPUT 7 (RAMP 1/RAMP 2)
REGULATOR COMMON
3
DIGITAL INPUT 8 (REMOTE/LOCAL)
PHASE B NOT
2
+24 VDC
PHASE B
ISOLATED REFERENCE GND
PHASE A NOT
mA SPEED REFERENCE
PHASE A
VDC SPEED REFERENCE
+15 VDC
ISOLATED REFERENCE VOLTAGE
REGULATOR COMMON
REGULATOR COMMON
RX
ANALOG METER OUTPUT
TX
1
20
17 18 19
21 22 23 24 25 26 27 28 29 30 31
CONFIGURABLE
RS-232
CONNECTIONS
ENCODER
CONNECTIONS
ANALOG
OUTPUT
ANALOG
SPEED
REFERENCE
Factory Installed
SNUBBER
BRAKING
STATUS
RELAYS
DIGITAL INPUTS
(ISOLATED 24 VDC)
Figure 2.7 - Typical Terminal Strip Connections
2.4.3 RS-232 Communication Port
The Regulator board contains a 9-pin D-shell RS-232 communication port (J8). This
port provides RS-232 communication between the GV3000/SE drive and a personal
computer running the Control and Configuration (CS3000) software. See figure 2.4.
Refer to instruction manual D2-3348, for more information about the CS3000
software.
2.4.4 Option Board Connector
The flat-ribbon cable connector (J3) on the left side of the Regulator board is a
parallel bus connection port that provides a means of attaching optional boards
such as the DeviceNet Option board, the RMI board, or the AutoMax Network
Option board, or similar boards to the GV3000/SE drive. See figure 2.4. The option
board is mounted below the Regulator board inside the drive. Refer to the appropriate
board instruction for more information. Refer to section 2.5 of this manual for more
information on optional drive kits.
2.4.5 Operator Interface Module Connector
The flat-ribbon connector J7 provides a means of attaching the optional Operator
Interface Module (OIM). The OIM is available for use as a remote keypad for the
GV3000/SE drive.
2-10
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
2.4.6 Keypad/Display
The front panel keypad/display is used to program and operate the GV3000/SE
drive. See figure 2.8. Refer to the GV3000/SE Software Start-Up and Reference
manual for more information.
Drive Status LEDs
Display
Keypad
£ ¥
.
Monitor Mode
LEDs
Password LED
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
STOP
RESET
Stop / Reset
Key
AUTO Forward
RUNNING MAN Reverse
REMOTE
JOG
RUN
PROGRAM
AUTO
JOG
FORWARD
REVERSE
PROGRAM
ENTER
START
Start Key
Figure 2.8 - Keypad/Display
2.5
Jumpers on Base Board (PISC-40)
Jumpers JP1 through JP4 on the Base board (PISC-40) are used for selection of
current feedback gain as shown in table 2.2. On the Base board, there is another
jumper, JP6, to be used for selection of ON/OFF level of precharge relay. Table 2.2
also shows the factory settings of these jumpers. For the locations of these jumpers,
see figure 2.9.
Table 2.2 - Settings of Jumpers on Base Board
Jumpers
JP1
(for U-phase)
JP2
(for V-phase)
JP3
(for bus current)
JP4
(for bus current)
JP6
About the Drive
Description
Factory Setting
These jumpers are used for selection of
current feedback gain as follows:
A:
for 30 to 50 HP units
B:
for 60 to 100 HP units
For 30 to 50 HP units:
: A
For 60 to 100 HP
units: B
This jumper is used for selection of ON/OFF
level of precharge relay as follows:
A: ON at 175 V, OFF at 155 V
B: ON at 220 V, OFF at 200 V
Set to A position
2-11
CN1
JP6
JP1 JP2 JP3 JP4
Figure 2.9 - Base Board Jumper Locations
2-12
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
2.6
Drive Kit Options
Table 2.3 provides a listing of the available GV3000/SE kit options.
Table 2.3 - Available Kits and Options
Kit Description (1)
Snubber Resistor Braking
(2)
(2)
About the Drive
Instruction
Manual
2SR20450
2TC3025 (3)
2TC3075 (3)
2TC4025 (3)
2TC4075 (3)
2TC4100 (4)
2TC4300 (4)
D2-3305
ControlNet Network Option Board
2CN3000
D2-3390
Interbus-S Network Option Board
2NB3000
49'1333
AutoMax Network Option Board with 762
mm (30") of Cable
2AX3000
D2-3308
AutoMax RS-232 Adapter Cable
2CA3001
D2-3348
Super Remote Meter Interface (RMI)
2SI3000
D2-3341
DeviceNet Network Option Board
2DV3000
HE-HGV3DN
Operator Interface Module (OIM)
2RK3000
D2-3342
CS3000 Control and Configuration
Software
2CS3000
D2-3348
CS3000 RS-232 Computer Cable
2CA3000
D2-3348
115 VDC Interface Option Board
2LB3000
D2-3376
PROFIBUS™ Interface Board
2PB3000
49.1355
Motor Encoder Cable
(1)
Option Kit Model
Number
Consult the factory for options desired when not shown. Option kits are subject to change for
feature or performance enhancements.
Up to two snubber kits can be connected to a drive in parallel.
(3)
These cables are for use with Reliance NEMA Vector Inverter Duty Motors (encoder connector and
exposed wire pairs).
(4)
These cables are for use with Reliance NEMA Vector Inverter Duty Motors (exposed wire pairs on
both ends).
2-13
CHAPTER 3
Planning Before Installing
This chapter provides information that must be considered when planning a
GV3000/SE drive installation. Installation site requirements, drive requirements,
and wiring requirements are presented.
!
ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.
ATTENTION: When the level-sense start feature is enabled (P.054 =
ON), the user must ensure that automatic start up of the driven
equipment will not cause injury to operating personnel or damage to
the driven equipment. In addition, the user is responsible for providing
suitable audible or visual alarms or other devices to indicate that this
function is enabled and the drive may start at any moment. Refer to
the GV3000/SE Software Start-Up and Reference manual for
additional information. Failure to observe this precaution could result
in severe bodily injury or loss of life.
ATTENTION: Use of power correction capacitors on the output of the
drive can result in erratic operation of the motor, nuisance tripping,
and/or permanent damage to the drive. Remove power correction
capacitors before proceeding. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.
ATTENTION: The user is responsible for conforming with all applicable
local, national, and international codes. Failure to observe this precaution
could result in damage to, or destruction of, the equipment.
3.1
Requirements for the Installation Site
It is important to properly plan before installing a GV3000/SE drive to ensure that
the drive's environment and operating conditions are satisfactory. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all
control and power wiring. Read the following recommendations before continuing
with drive installation.
3.1.1 Making Sure Environmental Conditions are Met
Before deciding on an installation site, consider the following guidelines:
Planning Before Installing
•
Verify that drives can be kept clean, cool, and dry.
•
The area chosen should allow the space required for proper air flow as defined
in section 3.1.3.
3-1
•
Be sure that drives are away from oil, coolants, or other airborne contaminants.
•
Do not install the drive above 1000 meters (3300 feet) without derating output
power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet), derate
the output current 1%.
•
Verify that the drive location will meet the environmental conditions specified in
table 3.1.
Table 3.1 - Ambient Conditions
Condition
Specification
Operating Temperature (Ambient)
0° to 55°C (32° to 131°F)
Storage Temperature (Ambient)
–40° to +65°C (–40° to +149°F)
Humidity
5 to 95% (non-condensing)
3.1.2 Determining Total Area Required Based on Drive Dimensions
Drive dimensions and weights are listed in table 3.2. Overall drive dimensions are
illustrated in figure 3.1 as an aid in calculating the total area required by the
GV3000/SE drives.
Table 3.2 - Drive Dimensions and Weights
GV3000/SE
Drive
Dim. H1
Dim. H2
Dim. H3
Dim. H4
Dim. W
Dim. D
Weight
30V2060
50V2060
544 mm
21.4"
564 mm
22.2"
504 mm
19.8"
606 mm
23.9"
235 mm
9.3"
354 mm
13.6"
34 kg
75 lbs
60V2060
100V2060
714 mm
28.1"
734 mm
28.9"
674 mm
26.5"
776 mm
30.6"
245 mm
9.6"
366 mm
14.4"
44 kg
97 lbs
GV3000/SE
Drive
Dim. A1 Dim. A2 Dim. A3 Dim. A4 Dim. B1 Dim. B2
Dim. C1 Dim. C2
Dim. C3
Dia. d
9 mm
0.35"
9 mm
0.35"
30V2060
50V2060
10 mm
0.4"
30 mm
1.2"
10 mm
0.4"
30 mm
1.2"
51 mm
2.0"
51 mm
2.0"
100 mm
3.9"
100 mm
3.9"
9 mm
0.35"
60V2060
100V2060
10 mm
0.4"
30 mm
1.2"
10 mm
0.4"
30 mm
1.2"
51 mm
2.0"
51 mm
2.0"
200 mm 200 mm
7.9"
7.9"
9 mm
0.35"
3-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Ventilation Duct (Option)
T
P
N
S T
H1
U&W
V
C3
A3
A4
GND
B2
R
P, N
H2
S
A1
A2
C1
R
H4
H3
B1
d dia.
(Mounting Hole)
U
V
W
GND
C2
W
U
D
V
W
Figure 3.1 - Drive Dimensions
Planning Before Installing
3-3
3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances
Be sure there is adequate clearance for air ventilation around the drive. For best air
movement, do not mount GV3000/SE drives directly above each other. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all
control and power wiring. Refer to figure 3.2 for recommended air flow clearances.
150 mm (6 in.)
<1
150 mm
(6 in.)
150 mm
(6 in.)
150 mm (6 in.)
<1
1> IF ADJACENT TO OTHER DRIVES,
THIS CLEARANCE MUST BE
250 MM (10 IN.).
Figure 3.2 - Recommended Air Flow Clearances
When installing a GV3000/SE drive, prepare an opening for its ventilating duct at
the top of the cabinet and, if necessary, provide an extension of the duct to connect
between the opening and the duct.
3-4
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
3.1.4 Verifying Power Module AC Input Ratings Match Supplied Power
It is important to verify that plant power will meet the input power requirements of
the GV3000/SE drive's Power Module circuitry. Refer to table 2.1 for input power
rating specifications. Be sure input power to the drive corresponds to the drive
nameplate voltage and frequency.
3.2
Wiring Requirements for the Drive
Certain drive requirements should be checked before continuing with the drive
installation. Wire sizes, branch circuit protection, speed feedback (for FVC
regulation), and E-stop wiring (see chapter 7), are all areas that need to be
evaluated.
3.2.1 Meeting Terminal Strip Input and Output Specifications
The terminal strip on the Regulator board provides terminals for 24 VDC power for
the eight remote control inputs. Refer to tables A.3 and A.4 for control input and
output specifications.
3.2.2 Determining Wire Size Requirements
Wire size should be determined based on applicable local, national, and
international codes (e.g., NEC/CEC regulations).
!
ATTENTION: The user is responsible for conforming with all
applicable local, national, and international codes. Failure to observe
this precaution could result in damage to, or destruction of, the
equipment.
3.2.2.1 Recommended Power Wire Sizes
Input power wiring should be sized according to applicable codes to handle the
drive's continuous-rated input current. Output wiring should be sized according to
applicable codes to handle the drive's continuous-rated output current. See tables
3.3 and 3.4 for recommended power wire sizes.
Important: Use only copper (Cu) wire with a temperature rating of 60/75°C.
Table 3.3 - Recommended Power Wire Sizes for 30 to 50 HP Drives
Planning Before Installing
Type of Wiring
Terminals
AC Input Power
R/L1, S/L2, T/L3
Output Power
U/T1, V/T2, W/T3
DC Input Power
P, N
Size of Wire (Maximum)
3/0 AWG (or 85 mm2)
3-5
Table 3.4 - Recommended Power Wire Sizes for 60 to 100 HP HP Drives
Type of Wiring
Terminals
AC Input Power
R/L1, S/L2, T/L3
Output Power
U/T1, V/T2, W/T3
DC Input Power
P, N
Size of Wire (Maximum)
500 Kcmil (or 250 mm2)
3.2.2.2 Recommended Control and Signal Wire Sizes
The recommended wire size to connect I/O signals to the terminal strip on the
Regulator board are shown in table 3.5. Recommended terminal tightening torque
is 0.5 Newton-meters (4.5 in-lb). Operator controls can be up to 303 meters (1000
feet) from the GV3000/SE drive.
Table 3.5 - Recommended Terminal Strip Wire Sizes
Terminals
Wire Size
1 to 31
20 to 14 AWG, 0.5 to 2 (mm2)
3.2.2.3 Recommended Motor Lead Lengths
The following motor lead lengths are recommended to reduce line disturbances and
noise. See figure 3.3.
•
For applications using one motor, motor lead length should not exceed 76
meters (250 feet). Note that drives using vector regulation can only be
connected to one motor at a time.
•
For applications with multiple motors, total motor lead length should not exceed
76 meters (250 feet).
When total lead length exceeds 76 meters (250 feet), nuisance trips can occur,
caused by capacitive current flow to ground. Note that these capacitively-coupled
currents should be taken into consideration when working in areas where drives are
running. If the motor lead length must exceed these limits, the addition of output
line reactors or other steps must be taken to correct the problem. See tables 3.6
and 3.7. Note that the motor lead lengths shown in table 3.6 are only guidelines.
Your application may be restricted to shorter lead length due to:
3-6
•
the type of wire
•
the placement of wire (for example, in conduit or a cable tray)
•
the type of line reactor
•
the type of motor.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
GV3000/SE
Drive
GV3000/SE
Drive
GV3000/SE
Drive
GV3000/SE
Drive
15 m (50')
38 m (125')
38 m (125')
61 m (200')
Motor
76 m (250')
61 m (200')
Motor
Motor
8 m (25')
Motor
8 m (25')
Motor
Motor
Motor
All examples represent 76 m (250') of motor lead length.
Figure 3.3 - How to Measure Motor Lead Lengths
Table 3.6 - Motor Lead Lengths
Maximum Lead Length in Feet with
230 VAC Motor
GV3000/SE
HP Rating
Carrier Frequency
2 kHZ
4 kHZ
8 kHZ
30
800
500
500
40
800
500
500
50
Filter Type
None
800
500
500
60
800
500
500
75
800
500
500
100
800
500
500
30
1000
1000
1000
40
1000
1000
1000
1000
1000
1000
1000
1000
1000
75
1000
1000
1000
100
1000
1000
1000
50
60
A 5%MTE
reactor/filter
at the drive.
Note that the lead lengths listed are valid with Reliance Electric inverter duty motors.
Table 3.7 - Reactors
GV3000/SE
HP Rating
240 Volt
5% MTE Reactor
GV3000/SE
HP Rating
240 Volt
5% Reactor
30
RL-08002
60
RL-16002
40
RL-10002
75
RL-20002
50
RL-13002
100
RL-25002
These part numbers are for a reactor with a cacitor filter.
MTE standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHZ.
All reactors are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).
Planning Before Installing
3-7
3.2.2.4 Recommended Serial Communication Cable Lengths
Connector J8 on the Regulator boards is an RS-232 serial communication port.
This connector allows the GV3000/SE drive to communicate with external devices
such as a personal computer using RS-232 protocol. See table A.5. Two RS-232
cables are available from Reliance: a 3 meter (10 feet) D-shell 9-pin to 9-pin cable
(M/N 2CA3000) and a 0.3 meter (1 foot) D-shell 9-pin to 25-pin adapter cable
(M/N 2CA3001). User-constructed cables can be up to 15 meters (50 feet) in
length. Note that for communication between a GV3000/SE drive and a personal
computer, the Control and Configuration software must also be used. Refer to
instruction manual D2-3348 for more information.
The Regulator boards have one set of RS-232 transmit/receive lines. These lines
can be accessed by only one device at a time: connector J8, the RS-232 terminals
(1-3) on the terminal strip, or an Operator Interface Module (OIM).
3.2.3 Selecting AC Input Line Branch Circuit Fuses, Circuit
Breakers, and AC Reactors
!
ATTENTION: Most codes require that upstream branch circuit
protection be provided to protect input power wiring. Install the fuses
recommended in table 3.8. Do not exceed the fuse ratings. Failure to
observe this precaution could result in damage to, or destruction of,
the equipment.
Input line branch circuit protection fuses must be used to protect the input power
lines. See figures 5.1 and 5.2. Recommended fuse values are shown in table 3.8.
The input fuse ratings listed in table 3.8 are applicable for one drive per branch
circuit. No other load may be applied to that fused circuit.
Table 3.8 - AC Input Line Fuse Selection Values
Horsepower Rating
Input AC Fuse
Rating (1)
30V2060
30 HP
200 A
40V2060
40 HP
250 A
50V2060
50 HP
300 A
60V2060
60 HP
350 A
75V2060
75 HP
450 A
100V2060
100 HP
500 A
Model Number
(1)
3-8
Recommended fuse type: UL Class J, 600V, time-delay, or equivalent.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
AC reactor must be installed in the AC input line. Tables 3.9 and 3.10 show
selection values for the circuit breakers and AC reactors respectively.
Table 3.9 - Circuit Breaker Selection Values
Model Number
Horsepower Rating
Circuit Breaker
Rating
30V2060
30 HP
150 A
40V2060
40 HP
200 A
50V2060
50 HP
250 A
60V2060
60 HP
300 A
75V2060
75 HP
350 A
100V2060
100 HP
400 A
Table 3.10 - AC Reactor Selection Values
Model Number
Horsepower Rating
AC Reactor
30V2060
30 HP
LS3-125/3-1
(125 A/84 mH)
40V2060
40 HP
LS3-160/3-1
(160 A/66 mH)
50V2060
50 HP
LS3-160/3-1
(160 A/66 mH)
60V2060
60 HP
LS3-200/3-1
(200 A/54 mH)
75V2060
75 HP
LS3-250/3-1
(250 A/42 mH)
100V2060
100 HP
LS3-300/3-1
(300 A/36 mH)
3.2.4 Meeting Encoder Specifications (FVC Regulation Only)
GV3000/SE drives set up for FVC regulation require an encoder for closed loop
operation. Encoder specifications are provided in table A.6. Drives set up for V/Hz
or SVC regulation do not require an encoder for feedback because they operate in
open loop mode.
3.2.4.1 Encoder Wiring Guidelines
Encoder connections are considered signal level wiring and, therefore, must be run
separate from control and power wiring. Reliance Electric recommends 18 AWG
unshielded twisted pair wires with 2-3 twists per inch for applications to a maximum
distance of 303 meters (1000 feet). The recommended Reliance Electric part
number is 417900-207CG, 18 AWG, 6 conductor (3 twisted pairs).
3.2.5 Verifying Power Module Output Current Rating is Greater Than
Motor Full Load Amps
Verify that the GV3000/SE output current rating is greater than the motor's full load
current (amps). Table 2.1 lists the output current values.
Planning Before Installing
3-9
CHAPTER 4
Mounting the Drive, Grounding, and
Finding Wire Routing Locations
This chapter shows how to mount the drive and properly ground it.
4.1
Mounting the Drive
Attach the drive to the vertical surface selected using the four (4) mounting holes
provided. In order to maintain a flat mounting surface and to ensure that bolt
tightness is maintained, use washers under the bolt heads. Refer to figure 3.1 and
table 3.2 for drive mounting dimensions. Use the following user-supplied mounting
bolts and washers:
•
30 to 50 HP drives: M8 (5/16")
•
60 to 100 HP drives: M8 (5/16").
4.1.1 Verifying the Drive's Watts Loss Rating
When mounting the drive inside of another enclosure, you should determine the
watts loss rating of the drive shown in table 2.1. This table lists the typical full load
power loss watts value under all operating carrier frequencies. Ensure
adequate ventilation is provided based on the drive's watts loss rating.
4.2 Routing Input, Motor Output, Ground, and Control
Wiring for the Drive
All wiring should be installed in conformance with the applicable local, national, and
international codes (e.g., NEC/CEC). Signal wiring, control wiring, and power wiring
must be routed in separate conduits to prevent interference with drive operation.
Note that no wires are to be routed behind the drive. Figure 4.1 shows the locations
of the power terminals and the grounding terminals of the GV3000/SE drives.
!
ATTENTION: Do not route signal and control wiring with power wiring
in the same conduit. This can cause interference with drive operation.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
Mounting the Drive, Grounding, and Finding Wire Routing Locations
4-1
Do not route more than three sets of motor leads through a single conduit. This will
minimize cross-talk that could reduce the effectiveness of noise reduction methods.
If more than three drive/motor connections per conduit are required, shielded cable
must be used. If possible, each conduit should contain only one set of motor leads.
!
4.3
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if
a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled to eliminate the possible shock hazard
from cross-coupled motor leads. Failure to observe these precautions
could result in bodily injury.
Grounding the Drive
!
ATTENTION: The user is responsible for conforming with all
applicable local, national, and international codes. Failure to observe
this precaution could result in damage to, or destruction of, the
equipment.
Use the following steps to ground the drive:
Step 1. Remove the drive's cover.
Step 2. Run a suitable equipment grounding conductor unbroken from the drive's
ground terminal to the motor's ground terminal and then to earth ground.
See figures 4.1, 5.1 and 5.2.
Step 3. Connect a suitable grounding conductor to the motor frame, the remote
control station (if used), and the transformer. Run each conductor
unbroken to earth ground.
When adding more than one grounding conductor wire to a single chassis
ground, twist the conductors together.
Step 4. Reattach the drive's cover.
4-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
R
S
P
T
R
P, N
N
GND
U
V
S T
W
GND
U&W V
FRONT VIEW
U
V
W
Terminals:
R, S, T: Drive input power terminals
U, V, W: Drive output power terminals
P (+), N (–): DC bus terminals
GND: Ground terrminal
BOTTOM VIEW
Figure 4.1 - Terminal Locations
Mounting the Drive, Grounding, and Finding Wire Routing Locations
4-3
CHAPTER 5
Installing Input Power Wiring
This chapter describes incoming line components and how to install them.
5.1
Installing Transformers and Reactors (Optional)
Input isolation transformers might be needed to help eliminate the following:
•
Damaging line voltage transients from reaching the drive.
•
Line noise from the drive back to the incoming power source.
•
Damaging currents that could develop if a point inside the drive becomes
grounded.
Observe the following guidelines when installing an isolation transformer:
•
A power disconnecting device must be installed between the power line and the
primary of the transformer.
•
If the power disconnecting device is a circuit breaker, the circuit breaker trip
rating must be coordinated with the inrush current (10 to 12 times full load
current) of the transformer.
•
An additional impedance is required between the drive and the transformer. An
appropriate three-phase AC line reactor should be used as shown in table 5.1.
!
ATTENTION: Distribution system capacity above the maximum
recommended system KVA (500 KVA for 230 VAC) requires the use of
an isolation transformer, a line reactor, or other means of adding
similar impedance to the drive power input. Failure to observe these
precautions could result in damage to, or destruction of, the equipment.
ATTENTION: When the AC line is shared directly with other SCRrectified drives, an optional snubber resistor braking kit might be
required to alleviate excess DC bus voltage. Failure to observe these
precautions could result in damage to or destruction of the equipment.
The GV3000/SE AC line distribution system capacity is 500 KVA, three-phase with
30,000 amps symmetrical fault current capacity with a line impedance of less than
5%. The symmetrical fault current may be increased to 85,000 amps if the appropriate
three-phase AC line reactor is used as shown in table 5.1.
Installing Input Power Wiring
5-1
Table 5.1 - AC Line Reactors
GV3000/SE Drive
5.2
Line Reactor Inductance (+/–10%)
30 HP
84 µH
40 HP
66 µH
50 HP
66 µH
60 HP
54 µH
75 HP
42 µH
100 HP
36 µH
Installing Fuses for Branch Circuit Protection
Install the required, user-supplied branch circuit protection fuses according to the
applicable local, national, and international codes (e.g., NEC/CEC). The fuses must
be installed in the line before the drive input terminals. See figures 5.1 and 5.2.
Fuse value selections are provided in table 3.6.
!
5.3
ATTENTION: Most codes require that upstream branch protection be
provided to protect input power wiring. Failure to observe this
precaution could result in severe bodily injury or loss of life.
Installing a Required External/Separate Input Disconnect
An input disconnect must be installed in the line before the drive input terminals in
accordance with local, national, and international codes (e.g., NEC/CEC). The
disconnect should be sized according to the in-rush current as well as any additional
loads the disconnect might supply. The trip rating for the inrush current (10-12
times full load current) should be coordinated with that of the input isolation
transformer, if used. Refer to section 5.1 for additional information.
5-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
3-Phase AC
Input Voltage 230 V
181
182
183 GND
Manual
Disconnect
Fuse
User-Supplied
AC Reactor
R
1L1
S
1L2
T
IL3
GND
(PE)
‘
–
–
U
User-Supplied
‘
V
GV3000/SE
Power Module
W
GND
Motor Overload Relay
(Optional if Electronic
Overload is Used)
M
Figure 5.1 - Typical AC Input Electrical Connections
Installing Input Power Wiring
5-3
DC Input
Voltage 310 V Nominal
–
+
Manual
Disconnect
DC Fuse
User-Supplied
R
1L1
S
1L2
T
IL3
GND
(PE)
‘
–
P
47
45
N
–
U
User-Supplied
‘
V
W
GV3000/SE
Power Module
GND
Motor Overload Relay
(Optional if Electronic
Overload is Used)
M
Figure 5.2 - Typical DC Bus Electrical Connections
5-4
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
5.4
Installing Power Wiring from the AC Input Line to the
Drive's Power Terminals
Use the following steps to connect AC input power to the drive:
Step 1. Wire the AC input power leads. Tables 3.3 and 3.4 contain the recommended
power wiring sizes.
!
ATTENTION: Do not route signal and control wiring in the same
conduit with power wiring. This can cause interference with drive
operation. Failure to observe this precaution could result in damage
to, or destruction of, the equipment.
Step 2. Connect the three-phase AC input power leads (three-wire 200-230 VAC)
to terminals R/L1, S/L2, T/L3. Refer to figure 4.1 for the locations of the
terminal.
Step 3. Tighten the AC input power terminals to 9.8-11.7 Newton-meters (87-104
lb-in) for 30-100 HP drives.
5.5
Installing Power Wiring from an External DC Bus to the
Drive's Internal DC Bus Terminals
Use the following steps to connect DC input power to the drive:
Step 1. Wire the DC input power leads. Tables 3.3 and 3.4 contain the recommended
power wiring sizes.
!
ATTENTION: Do not route signal and control wiring in the same
conduit with power wiring. This can cause interference with drive
operation. Failure to observe this precaution could result in damage
to, or destruction of, the equipment.
ATTENTION: If the GV3000/SE drive is connected to an external DC
bus, the user is responsible for DC bus short-circuit protection. Failure
to observe this precaution could result in damage to, or destruction of,
the equipment.
Step 2. Connect the DC input power leads (two-wire 310 VDC nominal) to
terminals + and –. See figure 4.1 for the locations of the terminals.
Note that the maximum discharge rate of the DC bus supply should be 200
V/second.
Step 3. Tighten the DC input power terminals to 9.8-11.7 Newton-meters (87-104
lb-in) for 30-100 HP drives.
Installing Input Power Wiring
5-5
CHAPTER 6
Installing Output Power Wiring
This chapter provides instructions on wiring output contactors, motor overload
protection, and output wiring to the motor.
6.1
Installing Output Contactors (Optional)
Output contactors provide a positive means of disconnecting the motor from the
drive. If the application requires the use of output contactors, contact Reliance
Electric for assistance.
6.2
Installing Mechanical Motor Overload Protection
(Optional)
To provide the motor with overload protection, local, national, and international
codes (e.g., NEC/CEC) require that a motor thermostat, internal to the motor, be
installed or an electronic thermal motor overload relay, sized to protect the motor,
be installed between the motor and the drive's output terminals.
The Motor Overload Enable parameter (P.040) can be used in place of the
electronic thermal motor overload relays in single motor applications. Note,
however, that temperature measuring devices integral to the motor are the best way
to thermally protect AC motors under all conditions. Parameter P.040 must be
enabled to provide overload protection. Refer to the GV3000/SE Software Start-Up
and Reference manual for more information.
In multiple motor applications (V/Hz regulation only), each motor must have its own
user-supplied overload protection.
6.3
Installing Output Wiring from the Drive Output Terminals
to the Motor
Use the following steps to connect the AC output power wiring from the drive to the
motor:
Step 1. Wire the three-phase AC output power motor leads. Tables 3.3 and 3.4
contain the recommended power wiring sizes.
Do not route more than three sets of motor leads through a single conduit.
This will minimize cross-talk that could reduce the effectiveness of noise
reduction methods. If more than three drive/motor connections per conduit
are required, shielded cable must be used. If possible, each conduit
should contain only one set of motor leads.
Installing Output Power Wiring
6-1
!
ATTENTION: Do not route signal and control wiring with power wiring
in the same conduit. This can cause interference with drive operation.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if
a drive sharing a conduit is being serviced or installed, all drives using
this conduit should be disabled to eliminate the possible shock hazard
from cross-coupled motor leads. Failure to observe these precautions
could result in bodily injury.
Step 2. Connect the three-phase AC output power motor leads to terminals U/T1,
V/T2, W/T3. See Figure 4.1 for the locations of the terminals.
Step 3. Tighten the three-phase AC output power terminals to 9.8-11.9
Newton-meters (87-104 lb-in) for 30-100 HP drives.
6-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
CHAPTER 7
Wiring the Regulator Board
Terminal Strip
This chapter describes how to wire the Regulator board terminal strip for stop,
encoder feedback, and remote control signals.
The signals available through the terminal strip are shown in tables 7.1 to 7.7 and
figures 7.1 and 7.2. Table 7.8 provides additional information.
Note that when the Control Source parameter (P.000) is set to remote (rE), the drive
will be controlled by the signals connected to the terminal strip. Refer to the
GV3000/SE Software Start-Up and Reference manual for more information on how
parameter P.000 is used to specify where the drive is controlled from.
Table 7.1 – RS-232 Connections (Terminals 1-3)
Signal
Terminal #
1
Transmit (Tx)
2
Receive (Rx)
3
Regulator Common
Notes: The RS-232 terminals should only be used when the RS-232 communication port
(J8) or an Operator Interface Module (OIM) are not being used, as all three devices use
the same transmit/receive lines.
Table 7.2 – Encoder Connections (Terminals 4-9)
Signal
Terminal #
4
+15 VDC
5
Phase A
6
Phase A Not
7
Phase B
8
Phase B Not
9
Regulator Common
Notes: An encoder feedback device must be installed if FVC regulation is used.
Wiring the Regulator Board Terminal Strip
7-1
Table 7.3 – Analog Output Connections (Terminals 10 and 11)
Signal
Terminal #
10
Analog Meter Output
11
Regulator Common
Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the
setting of jumper J17 on the Regulator board. The analog output must also be
programmed via parameter P.012 for an indication of speed and direction or percent of
torque.
Table 7.4 – Analog Speed/Torque Reference Connections (Terminals 12-15)
Signal
Terminal #
12
Isolated Reference Voltage
13
VDC Speed/Torque Reference
14
mA Speed/Torque Reference
Isolated Reference Common
15
Notes: The analog speed/torque (P.008/U.000) reference is either +/–10 VDC or
+/–20 mA, as determined by the setting of jumper J4 on the Regulator board. The analog
reference can be adjusted using parameters P.009, P.010, and P.011.
Table 7.5 – Digital Input Connections (Terminals 16-25)
Signal
Terminal #
16
+24 VDC (Current Limited) (For remote control digital inputs only)
17
Digital Input 8 (Remote/Local) - Programmable
18
Digital Input 7 (Ramp 1/Ramp 2) - Programmable
19
Digital Input 6 (Forward/Reverse) - Programmable
20
Function Loss
21
Run/Jog
22
Reset
23
Stop
24
Start
25
+24 VDC Common
Notes: When a user-installed function loss input, a coast-to-stop pushbutton, or another
external interlock is installed, the factory-installed jumper connecting terminals 16 and 20
must be removed so that a contact, when open, will stop the drive.
Terminals 17, 18, and 19 (remote control inputs 8, 7, and 6) are programmed using
parameters P.007, P.008, and P.031 through P.038. Factory default settings are shown
here in parentheses. Refer to the GV3000/SE Software Start-Up and Reference manual
for more information.
7-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table 7.6 – Snubber Resistor Braking Connections (Terminals 26 and 27)
Terminal #
Signal
26
Snubber Resistor Braking Signal
27
+24 VDC Common
Notes: These terminals are used with older Snubber Resistor Braking kits that require a
gate turn-on signal from the drive (for example, the M/N 2DB2010 series).
Table 7.7 – Status Relay Connections (Terminals 28-31)
Signal
Terminal #
28
N.C. Relay Contact
29
N.C. Relay Common
30
N.O. Relay Contact
31
N.O. Relay Common
Notes: Relay contact closure is programmable through parameter P.013. Refer to the
GV3000/SE Software Start-Up and Reference manual for more information.
Wiring the Regulator Board Terminal Strip
7-3
7-4
RX
REGULATOR COMMON
+15 VDC
PHASE A
PHASE A NOT
PHASE B
PHASE B NOT
REGULATOR COMMON
ANALOG METER OUTPUT
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16
Remote 4-20 mA
Speed/Torque
Reference
+ —
+20 mA
IMPORTANT: A maintained function loss switch
should be used if P.054 (Level Sense Start Enable)
= ON and P.026 (Function Loss Response) = 1.
17 18 19
N.O. RELAY COMMON
N.O. RELAY CONTACT
N.C. RELAY COMMON
N.C. RELAY CONTACT
+24 VDC COMMON
SNUBBER RESISTOR BRAKING SIGNAL
+24 VDC COMMON
START
STOP
RESET
RUN/JOG
FUNCTION LOSS
DIGITAL INPUT 6 (FORWARD/REVERSE)
DIGITAL INPUT 7 (RAMP1/RAMP2)
DIGITAL INPUT 8 (REMOTE/LOCAL)
+24 VDC
ISOLATED REFERENCE GND
mA SPEED REFERENCE
VDC SPEED REFERENCE
ISOLATED REFERENCE VOLTAGE
REGULATOR COMMON
TX
1
20 21 22 23 24 25 26 27 28 29 30 31
5 K ohm
12 13 14 15
FWD
REV
FUNCTION LOSS
RUN
JOG
RESET
START/STOP
Figure 7.1 - Two-Wire Start/Stop Sample Control Wiring
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
RX
REGULATOR COMMON
+15 VDC
PHASE A
PHASE A NOT
PHASE B
PHASE B NOT
REGULATOR COMMON
ANALOG METER OUTPUT
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16
Remote 4-20 mA
Speed/Torque
Reference
Wiring the Regulator Board Terminal Strip
+ —
+20 mA
IMPORTANT: A maintained function loss switch
should be used if P.054 (Level Sense Start Enable)
= ON and P.026 (Function Loss Response) = 1.
17 18 19
N.O. RELAY COMMON
N.O. RELAY CONTACT
N.C. RELAY COMMON
N.C. RELAY CONTACT
+24 VDC COMMON
SNUBBER RESISTOR BRAKING SIGNAL
+24 VDC COMMON
START
STOP
RESET
RUN/JOG
FUNCTION LOSS
DIGITAL INPUT 6 (FORWARD/REVERSE)
DIGITAL INPUT 7 (RAMP1/RAMP2)
DIGITAL INPUT 8 (REMOTE/LOCAL)
+24 VDC
ISOLATED REFERENCE GND
mA SPEED REFERENCE
VDC SPEED REFERENCE
ISOLATED REFERENCE VOLTAGE
REGULATOR COMMON
TX
1
20 21 22 23 24 25 26 27 28 29 30 31
5 K ohm
12 13 14 15
FWD
REV
FUNCTION LOSS
RUN
JOG
RESET
STOP
START
Figure 7.2 - Three-Wire Start/Stop Sample Control Wiring
7-5
7.1
Stopping the Drive
!
ATTENTION: The user must provide an external, hardwired
emergency stop circuit outside of the drive circuitry. This circuit must
disable the system in case of improper operation. Uncontrolled
machine operation may result if this procedure is not followed. Failure
to observe this precaution could result in bodily injury.
ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety
precaution, Reliance Electric recommends that an emergency stop
push button be located near the drive in an easily accessible location.
As a further safety precaution, you should post a warning on the drive
to alert personnel that the STOP/RESET key is not functional. Failure
to observe this precaution could result in severe bodily injury or loss of
life.
Depending upon the requirements of the application, the GV3000/SE drive can be
programmed to provide either a coast-to-rest or a ramp-to-rest operational stop
without physical separation of the power source from the motor. A coast-to-rest
stop turns off the transistor power device drivers. A ramp-to-rest stop fires the
transistor power device drivers until the motor comes to a stop, and then turns off
the power devices. The user can also program zero speed with power maintained
to the motor, but in this condition, the drive is not actually stopped. See the
description of terminal 23 and 24 or Stop Type (P.025) for more information on how
to program the operational stop.
In addition to the operational stop, the user must provide a hardwired emergency
stop external to the drive. The emergency stop circuit must contain only hardwired
electromechanical components. Operation of the emergency stop must not depend
on electronic logic (hardware or software) or on the communication of commands
over an electronic network or link.
Parameter P.055 (STOP/RESET Key Disable) can be used to change the operation
of the STOP/RESET key. See the parameter P.055 description in the software
manual for more information.
Note that the user-installed hardwired emergency stop may be used at any time to
stop the drive.
7.2
Wiring the Encoder Feedback Device
(FVC Regulation Only)
If the GV3000/SE drive is programmed to provide FVC regulation, an encoder must
be installed. Drives using V/Hz or SVC regulation do not require the use of an
encoder feedback device. The encoder connects to terminals 4 to 9 of the
regulator's terminal strip:
7-6
•
Terminal 4: Encoder Supply +15 VDC (250 mA capacity)
•
Terminal 5: Encoder Phase A Differential Input
•
Terminal 6: Encoder Phase A Not Differential Input
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
•
Terminal 7: Encoder Phase B Differential Input
•
Terminal 8: Encoder Phase B Not Differential Input
•
Terminal 9: Encoder/Regulator Common
Use the following procedure to connect an encoder to the regulator's terminal strip:
Step 1. Connect the encoder's wires to terminals 4 through 9 of the terminal strip.
See figure 7.3. See table A.6 for additional encoder specifications. Refer
to section 3.2.4.1 for encoder wiring guidelines.
Step 2. Set the following parameters to establish the maximum motor speed:
•
P.004: Maximum Speed
•
U.001: Encoder PPR
•
U.002: Motor Poles
•
U.003: Motor Nameplate Base Frequency
•
U.005: Motor Nameplate RPM
•
U.017: Motor Top Speed
Refer to the GV3000/SE Software Start-Up and Reference manual for more
information.
Wiring the Regulator Board Terminal Strip
7-7
REAR OF ENCODER CONNECTOR
Tamagawa FA Style
(M/N 2TC4025 and 2TC4075)
1
5
2
6
3
7
10 11
Regulator
Terminal Strip
Terminal 6
Terminal 5
Terminal 4
Terminal 9
Terminal 8
Terminal 7
14 15
Connector/Cable End
WHITE/ORANGE
ORANGE
BROWN
WHITE/BROWN
WHITE/GREEN
GREEN
Pin 1
Phase A
Pin 2
Phase A Not
Pin 6
0 VDC
Pin 12
+15 VDC
Pin 8
Phase B
Pin 9
Phase B Not
REAR OF ENCODER CONNECTOR
Dynapar H20 Style
(M/N 2TC3025 and 2TC3075)
Regulator
Terminal Strip
Terminal 6
Terminal 5
Terminal 4
Terminal 9
Terminal 7
Terminal 8
ORANGE
RED
WHITE/RED
BROWN
WHITE/BROWN
Pin A
Phase A
Pin H
Phase A Not
Pin F
0 VDC
Pin D
+15 VDC
Pin B
Phase B
Pin I
Phase B Not
REAR OF ENCODER CONNECTOR
Lakeshore SL56 and RL67 Style Slim-Tach Encoder
Regulator
Terminal Strip
Terminal 6
Terminal 5
Terminal 4
Terminal 9
Terminal 7
Terminal 8
8
12
9
13
16
A
H
B
I
C
J
D
Connector/Cable End
WHITE/ORANGE
4
G
F
E
1
2
3
4
5
6
7
8
9
10
Connector/Cable End
WHITE/ORANGE
ORANGE
RED
WHITE/RED
BROWN
WHITE/BROWN
Pin 3
Phase A
Pin 8
Phase A Not
Pin 1
0 VDC
Pin 6
+15 VDC
Pin 2
Phase B
Pin 7
Phase B Not
Figure 7.3 - Encoder Wiring Connections
7-8
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
7.3
Wiring the Signal and Control I/O
Wire the drive's signal and control I/O to the terminal strip as shown in table 7.8.
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip
Terminal
Number
Parameters/Wiring Connections
Description
Wiring RS-232 Signals
1
RS-232 Transmit
2
RS-232 Receive
3
RS-232 Signal/Regulator
Common
Note that RS-232 communication between the GV3000/SE drive
and a personal computer requires the use of the Control and
Configuration software. Refer to instruction manual D2-3348 for
more information.
These terminals should only be used when the RS-232 port
(J8) or an Operator Interface Module (OIM) are not being used, as
all three devices use the same transmit/receive lines.
PERSONAL COMPUTER
TERMINAL STRIP
1
1 2 3
TXD [DATA OUT] TERMINAL 1
RXD [DATA IN] TERMINAL 2
COMMON TERMINAL 3
25 PIN D–SHELL, MALE –OR–
9 PIN D–SHELL, PLUG
1
–OR–
PIN–2 RXD [DATA IN]
PIN–3 TXD [DATA OUT]
COMMON
PIN–7 (25– PIN D–SHELL)
–OR–
PIN–5 (9–PIN D–SHELL)
WIRE LENGTH – 50 FEET [MAX]
Wiring Encoder Inputs
4-9
Encoder Wiring
Wiring the Regulator Board Terminal Strip
See section 7.2.
7-9
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring Analog Outputs
10
0-10 VDC or 4-20 mA
Analog Output Reference
11
Regulator Common
The setting of parameter P.012 selects the terminal strip analog
output source (either speed or torque). Jumper J17 must also be
set. See figure 2.6.
The 4-20 mA current selection requires a power supply for
operation. The power can be sourced from the encoder supply,
terminal 4 (15 VDC), or from an external 15 V power supply.
Note that the maximum supply current from terminal 4 is 250 mA
(encoder and current source) at 15 V. Terminals 9 and 11 are
internally connected.
Terminal
Strip
1
2
Load
(Meter or Analog Input)
3
4+
+
5
–
6
7
8
9–
10 +
11 –
Connection to the negative
side of the power supply is
only required when an external
15 V power supply is used.
7-10
12
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Parameters/Wiring Connections
Description
Wiring Analog Speed Reference Inputs
12
Isolated Reference Voltage
(+10 VDC)
13
Analog Speed/Torque
Reference Input Voltage
(+/– 10 VDC)
14
Analog Speed/Torque
Reference Input Current
(0-20 mA)
15
Isolated Speed/Torque
Reference Common
(Voltage/Current)
Related parameters:
P.000:
P.009:
P.010:
P.011:
Control Source
Terminal Strip Analog Input Offset
Terminal Strip Analog Input Gain
Terminal Strip Analog Input Configure
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional parameter information.
Jumper J4 must also be set. See figure 2.6.
+10 V
12
13
+20 mA 0 V
0V
14
15
12
13
5K
+10 VDC
14
15
+ –
+20 mA
INPUT
SPEED REFERENCE
Wiring the Regulator Board Terminal Strip
7-11
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Remote/Local Input
16
+24 VDC Power Supply
Current limited for remote input logic use only.
17
Digital Input 8
(Default - Remote/Local)
Digital input 8 is control function programmable through
parameter P.007.
!
ATTENTION: If a maintained start contact is used when the control source = rE, switching from local to
remote from the terminal strip will cause power to be applied to the motor if the remote start contact is
closed. Stay clear of rotating machinery in this case. Failure to
observe this precaution could result in bodily injury.
The following parameters must be set:
P.000: Control Source (Only active when P.000 = rE)
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and assigns
a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or Preset
Speeds)
Note that based on the settings of parameters P.000, P.007, P.008,
and r.030 if an RMI board is used, the following parameters can
affect digital input 8.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
16
17
REMOTE
LOCAL
Terminal 17 On = Local Control
Diagram shows factory setting.
7-12
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Parameters/Wiring Connections
Description
Wiring an Additional Ramp Input
18
Digital Input 7
(Default - Ramp 1/Ramp 2)
Digital input 7 is control function programmable through
parameter P.007. The following parameters must be set:
P.000:
P.001:
P.002:
P.006:
P.007:
Control Source
Accel Time 1 (Ramp 1)
Decel Time 1 (Ramp 1)
Second Menu Password
Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or Preset
Speeds)
P.017: Accel Time 2 (Ramp 2)
P.018: Decel Time 2 (Ramp 2)
Note that based on the settings of parameters P.000, P.007, P.008,
and r.030 if an RMI board is used, the following
parameters can affect digital input 7.
P.023: MOP Accel/Decel Time
P.024: MOP Reset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
16
18
RAMP 1
RAMP 2
Terminal 18 On = Ramp 2
Diagram shows factory setting.
Wiring the Regulator Board Terminal Strip
7-13
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Forward/Reverse Input
19
Digital Input 6
(Default - Forward/Reverse)
Digital input 6 is control function programmable through
parameter P.007. The following parameters must be set:
P.000: Control Source
P.006: Second Menu Password
P.007: Terminal Strip Digital Inputs Configure (Selects and
assigns a control function to digital inputs 6 to 8).
P.008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or Preset
Speeds)
P.027: Forward/Reverse Configuration
Note that based on the settings of parameters P.000, P.007, P.008,
and r.030 if an RMI board is used, the following
parameters can affect digital input 6.
P.023: MOP Accel/Decel Time
P.024: MOP Preset Configuration
P.031 to P.038: Preset Speeds 1-8
Refer to the GV3000/SE Software Start-Up and Reference manual
for additional information.
16
19
FWD
REV
IF P.027 = 1,
FORWARD DIRECTION ONLY
Terminal 19 On = Reverse Direction
Diagram shows factory setting. From the encoder end of
the motor, clockwise rotation indicates forward motor
movement.
7-14
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Function Loss Input
20
Digital Input 5
(Function Loss)
The following parameters must be set:
P.026: Function Loss Response
A signal must be present at terminal 20 for the drive to be able to
start. See figures 7.1 and 7.2 The drive is shipped from the factory
with a jumper between terminals 16 and 20 which provides the
signal. The function loss input should be in series with the drive's
external interlocks. In this case, the jumper must be removed
before the connections are made. See figure 2.7.
TERMINAL STRIP
16 17 18 19 20 21
REMOVE FACTORY FUNCTION
LOSS JUMPER HERE.
16 17 18 19 20 21
FUNCTION LOSS
COAST-STOP
PUSH-BUTTON
SAFETY INTERLOCKS
Terminal 20 On = No Function Loss
Wiring a Run/Jog Input
21
Digital Input 4
(Run/Jog)
The following parameters must be set:
P.000: Control Source
P.020: Jog Speed Reference
P.021: Jog Ramp Accel Time
P.022: Jog Ramp Decel Time
16
21
RUN
JOG
Terminal 21 On = Jog Operation
Wiring the Regulator Board Terminal Strip
7-15
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Parameters/Wiring Connections
Description
Wiring the Reset Input
22
Digital Input 3
(Reset)
The following parameter must be set:
P.000: Control Source
16
22
RESET
Terminal 22 On = Reset
Wiring the Stop/Start Inputs
23
Digital Input 2
(Stop)
24
Digital Input 1
(Start)
The following parameters must be set:
P.000: Control Source
P.025: Stop Type
16
23
STOP
16
24
START
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
25
24 VDC Isolated Common
Wiring the Snubber Resistor
26
Snubber Resistor Braking
Control Signal
27
+24 VDC Isolated Common
Used with older Snubber Resistor Braking Kits that require a gate
turn-on signal from the drive (for example, the M/N 2DB2010
series).
Note that terminals 26 and 27 are not to be used with
Snubber Resistor Braking Kits M/N 2SR20400, 2SR20600,
2SR21200, 2SR21800, 2SR20300, and 2SR20450.
7-16
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the Output Status Relays
28
Normally-Closed Contact
(Form B)
Both Form A and Form B contacts are rated for 250 VAC/30 VDC at
5 amps resistive or 2 amps inductive load.
29
Normally-Closed Contact
Common (Form B)
The following parameter must be set:
30
Normally-Open Contact
(Form A)
P.013: Output Relay Configuration
31
Normally-Open Contact
Common (Form A)
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close and the
normally-closed contact will open). Refer to the GV3000/SE
Software Start-Up and Reference manual for more information.
N.C.
COM
N.O.
COM
28 29 30 31
USER SUPPLIED
DEVICE
PARAMETER P.013 SELECTS OUTPUT
INDICATION
Wiring the Regulator Board Terminal Strip
7-17
CHAPTER 8
Completing the Installation
This chapter provides instructions on how to perform a final check of the installation
before power is applied to the drive.
!
8.1
ATTENTION: Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should start and adjust it. Read and understand this manual in its
entirety before proceeding. Failure to observe this precaution could
result in severe bodily injury or loss of life.
Checking the Installation
Use the following procedure to verify the condition of the installation:
!
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to
observe this precaution could result in severe bodily injury or loss of
life.
Step 1. Turn off, lock out, and tag the input power to the drive. Wait five minutes.
Step 2. Verify that the DC bus voltage is zero. Refer to section 9.3.
Step 3. If a function loss coast-stop push-button has been installed, verify that it
has been wired correctly. Be sure the factory-installed jumper at terminals
16 and 20 has been removed so that the coast-stop push-button will work.
!
ATTENTION: The user must provide an external, hardwired
emergency stop circuit outside of the drive circuitry. This circuit must
disable the system in case of improper operation. Uncontrolled
operation may result if this procedure is not followed. Failure to
observe this precaution could result in bodily injury.
Step 4. Remove any debris, such as metal shavings, from around the drive.
Step 5. Check that there is adequate clearance around the drive.
Step 6. Verify that the wiring to the terminal strip and the power terminals is correct.
Step 7. Check that the wire size is within terminal specification and that the wires
are tightened properly.
Completing the Installation
8-1
Step 8. Check that user-supplied branch circuit protection is installed and correctly
rated.
Step 9. Check that the incoming power is rated correctly.
Step 10. Check the motor installation and length of motor leads.
Step 11. Disconnect any power correction capacitors connected between the drive
and the motor.
Step 12. Check that the rating of the transformer (if used) matches the drive
requirements and is connected properly.
Step 13. Verify that a properly-sized ground wire is installed and a suitable earth
ground is used. Check for and eliminate any grounds between the motor
frame and the motor power leads. Verify that all ground leads are
unbroken.
Step 14. Uncouple the motor from any driven machinery to initially start the drive.
8.2
Powering Up After Installation is Complete
Use the following procedure to verify that the drive is installed correctly and is
receiving the proper line voltage:
Step 1. Turn the drive's input power disconnect to the On position.
Step 2. Apply power to the drive.
Step 3. Follow the start-up procedure in the GV3000/SE Software Start-Up and
Reference manual.
8-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
CHAPTER 9
Troubleshooting the Drive
This chapter describes how to troubleshoot the drive and the equipment that is
needed to do so. Also provided are replacement part lists and information on
clearing faults.
9.1
Test Equipment Needed to Troubleshoot
An isolated multimeter will be needed to measure DC bus voltage and to make
resistance checks. Note that dedicated troubleshooting test points are not provided.
9.2
Drive Alarms and Faults
The drive will display alarm and fault codes to assist in troubleshooting when a
problem develops during self-tuning or drive operation.
If an alarm condition occurs, the drive will continue to run and a 2- or 3-digit alarm
code will flash on the display.
If a fault occurs, the drive will coast-to-rest stop and a 2- or 3-digit fault code will
flash on the display.
Refer to the GV3000/SE Software Start-up and Reference manual for more
information on drive alarms and faults.
9.3
Verifying That DC Bus Capacitors are Discharged
!
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to
observe this precaution could result in severe bodily injury or loss of
life.
The GV3000/SE drive's DC bus capacitors retain hazardous voltage after input
power has been disconnected. Perform the following steps before touching any
internal components:
Troubleshooting the Drive
9-1
Step 1. Turn off and lock out AC input power. Wait five minutes.
Step 2. Remove the drive's cover.
Step 3. Verify that there is no voltage at the drive's input power terminals.
Step 4. Measure the DC bus potential with a voltmeter at the DC bus power
terminals. See figure 9.1.
Step 5. Once the drive has been serviced, reattach the drive's cover.
Step 6. Reapply AC input power.
DC BUS
VOLTS
P (+)
R
S
T
N (–)
GND
U (T1)
W (T3)
V (T2)
Figure 9.1 - DC Bus Voltage Terminals
9.4
Checking Out the Power Module with Input Power Off
Use the following procedure to check the drive's Power Module circuitry with power
off:
!
ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait
five (5) minutes for the DC bus capacitors to discharge and then check
the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to
observe this precaution could result in severe bodily injury or loss of
life.
Step 1. Turn off and lock out input power. Wait five minutes.
Step 2. Remove the drive's cover.
Step 3. Verify that there is no voltage at the drive's input terminals.
9-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Step 4. Check the DC bus potential with a voltmeter as described in section 9.3 to
ensure that the DC bus capacitors are discharged.
Step 5. Disconnect the motor from the drive.
Step 6. Check all AC line and DC bus fuses.
Step 7. If a fuse is open, use a multimeter to check the input diodes and output
IGBTs. See table 9.1.
Note that the drives do not have replaceable transistor modules: the entire
drive must be replaced if a transistor malfunctions.
Step 8. Reconnect the motor to the drive.
Step 9. Reattach the drive's cover.
Step 10. Reapply input power.
Table 9.1 - Resistance Checks
Meter
Connection
(+) (–)
Input
Diode
No.
1
*
R/L1
2
*
S/L2
3
*
T/L3
4
R/L1
**
5
S/L2
**
6
T/L3
**
Component is OK if
resistance (R) is:
50 kW < R < 10 MW
Component is defective if:
Continuity (short circuit) or
open when the meter is
connected with reversed
polarity
* (+) DC Bus Volts power terminal
** (–) DC Bus Volts power terminal
IGBT
No.
Meter
Connection
(+)
(–)
1
*
W/T3
2
*
V/T2
3
*
U/T1
4
W/T3
**
5
V/T2
**
6
U/T1
**
Component is OK if
resistance (R) is:
50 kW < R < 10 MW
Component is defective if:
Continuity (short circuit) or
open when the meter is
connected with reversed
polarity
* (+) DC Bus Volts power terminal
** (–) DC Bus Volts power terminal
Troubleshooting the Drive
9-3
9.5
Replacement Parts
Table 9.2 lists the replacement parts that are available from Reliance Electric. See
figures 2.2 and 2.3 for the location of the parts.
Table 9.2 - Replacement Parts for the GV3000/SE Drives
Power Module
9-4
Description
Part Number
30V2060
40V2060
50V2060
60V2060
75V2060
100V2060
Regulator Board
0-56921-XXX
1
1
1
1
1
1
Base Board PISC-40
827711
1
1
1
1
1
1
Membrane Switch
Keypad/Bracket
Assembly
907021
1
1
1
1
1
1
Internal Fan Assembly
907017
1
1
1
1
1
1
Diode Module Fan
Assembly
907018
907019
2
–
2
–
2
–
–
1
–
1
–
1
IGBT Module Fan
Assembly
907020
2
2
2
2
2
2
IGBT Module
536664
536174
536175
3
–
–
3
–
–
3
–
–
–
3
3
–
3
3
–
3
3
Diode Bridge
512902
514706
1
–
1
–
1
–
–
6
–
6
–
6
DC Bus Fuse
286331
286325
1
–
1
–
1
–
–
1
–
1
–
1
DC Bus Capacitor
453136B
5
5
5
9
9
9
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
APPENDIX A
Technical Specifications
Table A.1 - Service Conditions
(1)
AC Line Distribution System Capacity
(maximum) for 230 VAC Units
Three-phase with 85,000 amps symmetrical fault current capacity
with AC line reactor with a line impedance of less than 5%.
Control Method
All-digital vector, sinusoidal pulse-width-modulated (PWM)
Displacement Power Factor
0.96
Line Frequency
50 ± 5 Hz or 60 ± 5 Hz
Line Voltage Variation
–10% to +10%
Line Dip Ride Through
Maximum 500 milliseconds - FVC
Adjustable up to 999.9 seconds (See P.042) - V/Hz, SVC
Motor Lead Lengths
76 meters (250 feet) total
Remote Operator Control Wire Length
Up to 303 meters (1000 feet) from the drive
Analog Speed Reference Resolution
1/1024 (10 bits) 0.1%
Acceleration Adjustment Range
0.1 to 999.9 seconds (within the ability of current)
Carrier Frequency
2 kHz, 4 kHz, or 8 kHz, software-selectable
Current Limit Adjustment
U.006 to 150% (based on motor nameplate rating) - vector
50 to 100% (based on motor nameplate rating) - V/Hz (1)
Service Factor
1.0
Speed Adjustable Range
From 0 RPM to maximum speed (vector)
Speed Regulation
Vector - 0.01% FVC, 0.5% SVC (steady-state)
V/Hz - motor slip-dependent
Speed Setpoint Resolution
1 RPM with local keypad, –4095 to +4095 counts with a
network or serial reference
Torque Control Response
180 to 220 Hz
Torque Linearity
±3% with optimal parameter setting (typical)
(see parameter U.005)
For V/Hz regulation, the overload current is limited to 100% of the drive nameplate rating.
(For vector regulation, the overload current is limited to 150% of the drive nameplate rating.)
Technical Specifications
A-1
Table A.2 - Environmental Condition
Condition
Specification
Operating Temperature (Ambient)
0° to 40°C (32° to 104°F)
Storage Temperature (Ambient)
–40° to 65°C (–40° to 149°F)
Humidity
5 to 95% non-condensing
Table A.3 - Terminal Strip Input Specifications
Signal Type
Speed Reference Input
Terminal(s)
Specification
12-15
5 KW potentiometer (0 to +/– 10 VDC
@ 50 KW input impedance) or 0-20
mA (@250 W input
impedance) with 10-bit resolution.
(Jumper-selectable by jumper J4;
refer to section 2.4.1.)
Note that the drive provides +15 VDC
buffered through a 1.875 KW resistor.
Digital Inputs (1 - 8)
16
+24 VDC Isolated Supply
17
Remote/Local (Default)
18
Ramp1/Ramp2 (Default)
19
Forward/Reverse (Default)
20
Function Loss
21
Run/Jog
22
Reset
23
Stop
24
Start
Table A.4 - Terminal Strip Output Specifications
Signal Type
Analog Output
Snubber Resistor
A-2
Terminal(s)
10 - 11
scaled signal
26-27
Specification
0-10 VDC or 4-20 mA
Used with older Snubber Resistor
Braking Kits such as M/N 2DB2010
series that requires a gate turn-on
signal from the drive.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
Table A.5 – Terminal Strip RS-232 Specifications
Signal Type
RS-232 Communications
Specification
Terminal(s)
1
XMIT
2
RECV
3
COMMON
Table A.6 – Encoder Feedback Device Specifications (FVC Regulation Only)
Specification
Technical Specifications
Rating
Motor Poles
2, 4, 6, or 8 poles
Overcurrent IET
200% load (based on drive nameplate
rating)
Overload Current Rating
150% for 1 minute (based on drive
nameplate rating)
Speed Control Range
1:600 with 1024 PPR
Speed Control Response
15 Hz (typical)
Encoder Feedback
15 V differential quadrature, encoder
incremental (512 PPR, 1024 PPR, 2048
PPR, 4096 PPR)
Service Factor
1.0
A-3
Table A.7 – Input Signal Response Times (Maximum)
Volts/Hertz Regulation (1)
Vector Regulation (1)
150 milliseconds
130 milliseconds
START
126 milliseconds
105 milliseconds
STOP, RESET, FL
75 milliseconds
75 milliseconds
Preset Speeds
75 milliseconds
75 milliseconds
Analog Speed/Trim
Reference
16 milliseconds
5 milliseconds
N/A
0.5 milliseconds
Signal Type and Source
Keypad START
Terminal Strip:
Analog Torque
Reference
Network:
START
46 milliseconds +
network transport time
25 milliseconds + network
transport time
STOP, RESET, FL
26 milliseconds +
network transport time
25 milliseconds + network
transport time
Analog Speed/Trim
Reference
5 milliseconds +
network transport time
5 milliseconds +
network transport time
Torque Reference
(1)
A-4
N/A
0.5 milliseconds + network
transport time
These are the maximum times from transitioning the input to the drive reacting to the input.
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
APPENDIX B
MOV2
DM1
4>
R/L1
S/L2
T/L3
Manual
Disconnect
Fuse
AC Reactor
1>
CT5
CT4
1
2
3
4
R2
MOV1
R1
10Ω/120 W
FU1
3 > Fuse
250 A
MOV3
2.0KΩ/40 W 5 >
30-100 HP GV3000/SE System Wiring Diagram
>6
4700 µF/400 V
C5
C1 +C2 +C3 +C4 + +453136B
G1
7>
G3
G2
G1
G1
U1
E1
1
2
3
4
W/T3
G1
V1
E1
E1
W1
CT2
TH1
MC-B6002
V/T2
C9
G2
G2
2>
PR
U2
E2
0.003 µF/500 V
G2
V2
E2
E2
1234
W2
U/T1
T
CN10 CN10
CN8
1
2
3
4
Current
CN9 CN9 Feedback CN7
1
Circuit
2
3
4
CN6
DC Bus
Volts
–
CN21 CN19
DC Bus
CN11
1
2
3
4
DC Bus Common
P
LED 1
LED
G2
E2
G2
E2
G2
E2
12
12
12
12
12
12
12
CN13 CN14 CN15 CN16 CN17 CN18
W2
U1 V1
W1 U2 V2
Heatsink
Overheat
Gate Signals
CN20
1
2
Bus Voltage
Circuit
DC Bus
Power Supply
24 VDC
24 VDC Common
+15 VDC
–15 VDC
+5 VDC
Regulator Common
Isolated +15 VDC
Isolated Common
Gate Power
CN12
P
Gate Power Supply
Regulator Power Supply
PISC-40
S-B6027-2
Pre-Charge
Control
1
2
Gate Circuit &
Dead Band
Circuit
Bus Voltage Feedback
T
1
2
3
1
2
3
CN2
827711
Red
Black
Yellow
1
2
3
Red
Black
Yellow
CN1
1
2
3
1
2
3
1.87 KΩ
12
Speed Reference
Input Wiring
13
14
15
Voltage
Current
250 Ω
23
22
Digital
Inputs
21
20
19
Configurable
Digital Inputs
18
17
16
+15 VDC
Encoder Phase A
C
Encoder Phase A
Encoder Phase A
Encoder Phase B
C
Encoder Phase B
Encoder Phase B
Reg. Com.
J17
Analog
Current Source
Meter Output
IGBT Gate Signals
Analog Speed Ref.
START
Voltage Source
STOP
Dynamic Braking Control
24 VDC
Common
RESET
24 VDC Common
RUN/JOG
Function Loss
IET/Controller Running
IET
Digital Input 6 (FWD/REV)
N.O.
J7
+15 VDC
N.C.
Digital Input 7 (RAMP1/RAMP2)
Digital Input 8 (REMOTE/LOCAL)
Microprocessor
System
+12 VDC
+24 VDC
TXD
RXD
Ribbon Cable
Reg. Common
–15 VDC
J9
Membrane Switch
DTR
–12 VDC
Local Operator Interface
Display and Indicator LEDs
30-100 HP GV3000/SE System Wiring Diagram
RS-232 TXD
RS-232 RXD
8.8.8.8.
Reg. Common
Regulator Board
Reg. Common
0-56921
T
T
Red
Black
Yellow
<8
AWG #26
Fan 4
80D
For Diode
Fan 3
180D
For IGBT
AWG #24
907020
AWG #24
Fan 2
180D
For IGBT
Fan 1
40D
For Power Supply
907020
AWG #24
907017
Note: Fan 2 to Fan 5 are ON/OFF-controlled by temperature (48/41°C).
Bus Voltage Feedback
Phase W Current Feedback
Phase V Current Feedback
Phase U Current Feedback
J4
Isolated Common
24 VDC Common
25
24
Isolated +15 VDC
T
For Diode
J6
Regulator Power Supply
A/D
Converter
AWG #26
Fan 5
80D
T
Red
Black
Yellow
MB-B6010*
Heat Sensor
T
Red
Black
Yellow
1
2
3
CN4
CN3
12 34
1
2
3
CN5
Phase U/W Bus Sensor
Phase V Current Feedback
Phase U Current Feedback
+
G1
E1
12
P
G1
E1
P
G1
E1
User-supplied
CT1
TXD J8
RXD
TXD
RXD
4
5
6
7
8
9
10
11
26
27
28
30
31
29
1
2
3
4
5
6
7
8
9
10
2
3
5
1
2
3
1>
Capacity of AC reactor is 84 µH/125 A for 30 HP unit, 66 µH/160 A
for 40 HP and 50 HP units, 54 µH/200 A for 60 HP unit, 42 µH/250 A
for 75 HP unit, and 36 µH/300 A for 100 HP unit.
2>
One 512902 diode bridge is required for 30 HP to 50 HP units,
and six 514706 diode bridges for 60 HP to 100 HP units.
3>
286331 fuse is used for 30 Hp to 50 HP units, and 286325 fuse for
60 HP to 100 HP units.
4>
One 10 Ohms/120 W resistor is used for 30 HP to 50 HP units, and
one 10 Ohms/220 W resistors for 60 HP to 100 HP units.
5>
One 1 KOhm/40 W resistor is used for 30 HP to 50 HPunits, and two
1 KOhm/40 W resistors for 60 to 100 HP units.
6>
Five capacitors are used for 30 HP to 50 HP units, and nine capacitors
for 60 HP to 100 HP units.
7>
Three 536664 IGBT modules are used for 30 HP to 50 HP units,
and three 536174 IGBT modules and three 536175 IGBT modules
for 60 HP to 100 HP units.
8>
Two 907018 diode module fan assemblies are used for 30 HP to
50 HP units, and one 907019 diode module fan assembly is used
for 60 HP through 100 HP units. For 60 HP through 100 HP units,
pins 2 and 3 of CN6 are jumpered.
Meter Output Signal
To optional
Dynamic Braking kit
Relay Contacts
To Operator
Interface Module
PC Communications
Port (RS-232)
Control Terminal
PC Communications
(RS-232)
B-1
Publication D2-3417-1 - August 1999
© 1999 Rockwell International Corporation, All rights reserved. Printed in Japan.